Delta DVP EH modules

Delta DVP EH modules

Delta DVP EH modules add digital field I/O to a compatible PLC through its right-side expansion bus. HM modules add inputs, HN modules add outputs, and HP modules add both. Count the X points needed for inductive sensors, photoelectric sensors and field contacts, then count the Y points for valves and interposing relays. Each model in the table links to its wiring and commissioning information.

Input and output counts for all 15 models

ModuleDigital inputsDigital outputsOutput type
DVP08HM11N80—
DVP16HM11N160—
DVP32HM11N320—
DVP08HN11R / DVP08HN11T08Relay / transistor
DVP32HN00R / DVP32HN00T032Relay / transistor
DVP08HP11R / DVP08HP11T44Relay / transistor
DVP16HP11R / DVP16HP11T88Relay / transistor
DVP32HP00R / DVP32HP00T1616Relay / transistor
DVP48HP00R / DVP48HP00T2424Relay / transistor

Selection example. For 12 new sensors and six outputs, consider the R or T version of the DVP32HP00, which provides 16 inputs and 16 outputs. If the machine only needs 12 more inputs, the DVP16HM11N may be enough. Count PLC inputs and outputs separately. A 32-point HN unit and a 32-point HP unit provide different combinations of field I/O.

EH, EH2 and EH3 compatibility

Delta’s EH digital I/O instruction sheet covers the original DVP-EH and shows the order of expansion. For an EH2 or EH3 CPU, confirm the full CPU and module part numbers, right-side bus connection and total I/O limit in the relevant manual. The DVP-EH3-L also supports certain left-side expansion modules. The HM, HN and HP units in the table connect to the right-side bus.

For analog signals such as temperature, current and voltage, see the DVP -H, DVP -H2 and DVP -H3 module pages. If the application needs data over a serial network, plan its Modbus RS-485 and industrial communications separately. Local EH I/O connects to the CPU’s expansion bus.

Power supply, sensor commons and R/T outputs

Check the 24 V DC input signal and the module’s main supply separately. The DVP16HP11R/T uses 24 V DC. Delta’s instruction sheet shows a 100–240 V AC main supply for the R/T versions of the DVP32HN00, DVP32HP00 and DVP48HP00. Mains wiring goes to the power input terminals. Wire X and the S/S common for the sensor’s PNP or NPN output, following the model’s sink/source diagram. Delta’s DC input example connects S/S to +24 V for an NPN sensor and to 0 V for a PNP sensor.

The R suffix indicates relay outputs, and T indicates NPN DC sinking transistor outputs. Check per-point and per-common current limits, inrush, switching frequency and ambient temperature. Select the fuse and the suppression device for inductive loads from the applicable wiring diagram. Confirm the common and polarity before commissioning DC valves or drive inputs with an optocoupler.

For an incremental encoder or a high-speed pulse output, check the CPU’s dedicated terminals and frequency limits. Use standard expansion X/Y points for field sensing and load control.

X/Y addresses, software and programming cable

Delta DVP X and Y addresses are octal. X10 follows X7. In Delta’s example with a 32EH CPU and a 32HP as the first module, the module uses X20–X37 / Y20–Y37. A 48HP fitted next uses X40–X67 / Y40–Y67. X0 or Y0 on the enclosure is a local terminal label. Check the address in the Ladder project against the CPU and installed module order.

Connect to the PLC program with WPLSoft or a release of ISPSoft that supports the CPU target. Use COMMGR for the ISPSoft serial connection. The PC connects to the host CPU. Delta’s cable guide lists UC-PRG020-12A for COM1 RS-232 on an EH3 CPU. Install the USB driver and select the COM port assigned by Windows. Confirm the cable for your CPU in the Delta DVP programming cables page and the manual.

Editor’s Note

When buying used, ask for photos of the full label, expansion connector and terminals. Read the R/T suffix and the 00/11 portion of the part number.

Before replacing a module, mark the field wires, record the module order and back up the PLC project. Isolate power before unplugging the module.

If an input LED changes and the PLC bit does not follow, check the actual X address first. If an output LED lights and the load stays off, measure the supply and check the C common and load circuit. Disable machine motion for the test.

If a fault appears only when a motor runs, inspect the variable-frequency drive output cable, field cable routing, sources of electromagnetic interference and cabinet grounding.

Test the commons and outputs you will use with a suitable test load. A single relay clicking on the bench only verifies part of the module.

Related Delta topics and PDF files

Delta DVP PLC PDF files · DVP expansion modules · DVP PLC series · DVP Slim digital modules

OtomasyonAVM EH2 CPU wiring sheet (EN PDF) · OtomasyonAVM DVP programming manual (EN PDF) · ISPSoft User Manual (EN PDF)

External references

Delta EH digital I/O instruction sheet (2008, EN/Chinese PDF) · Delta DVP/TP catalogue, EH3 model table (EN PDF) · Delta PLC/HMI Cable Selection Guide, EH3 section (EN PDF)