Delta DVP-EH

Delta DVP-EH: First-Generation High-Performance PLC Family

Delta DVP-EH is the first-generation high-performance PLC CPU family within the Delta DVP PLC series range. It handles machine sequencing, counting, timing, communication and high-speed pulse motion functions on suitable models. Program capacity is 16k steps. Distinguish the main CPU from its expansion modules.

The main units covered here with the 00 supply code use 100–240 V AC. Their auxiliary 24 V DC output is not the main supply input. Built-in total I/O options are 16, 20, 32, 40, 48, 64 and 80 points; analog and other special functions require suitable cards or modules.

EH, EH2 and EH3 generations

DVP32EH00R/T identifies first-generation EH; DVP32EH00R2/T2 belongs to Delta DVP-EH2; DVP32EH00R3/T3 belongs to Delta DVP-EH3. Read the suffix together with memory, instruction and hardware specifications. Do not present EH2/EH3 specifications as first-generation EH capabilities.

I/O arrangements and R, T, M outputs

Examples include DVP16EH00R with 8 inputs/8 outputs, DVP20EH00T with 12 inputs/8 outputs, and DVP32EH00R or DVP32EH00T with 16 inputs/16 outputs. R identifies relay outputs; T identifies NPN transistor outputs. DVP32EH00M combines differential high-speed outputs and relay outputs in a distinct terminal arrangement.

Y0 and Y2 on DVP20EH00T and DVP32EH00T provide pulse output up to 200 kHz. DVP32EH00M has two differential high-speed output groups. Do not apply these pulse capabilities to every EH model or to relay outputs. Match the electrical command input when selecting a servo motor drive or stepper motor drive.

Speed control and position control serve different purposes. Configure pulse/direction wiring, electronic gearing and mechanical transmission correctly. For position control, compare actual travel with the commanded pulse count first.

Important high-speed input voltage distinction

Do not assume that ordinary digital inputs and encoder inputs have identical electrical requirements. X0, X1, X4 and X5 on DVP32EH00M are 5 V differential line-driver inputs. Do not wire them as ordinary 24 V sensor inputs. Check terminal diagrams, input filtering and counter mode against the exact CPU code on other models as well.

Programming software

First-generation EH can use WPLSoft and ISPSoft with supported EH CPU targets. These provide programming, PLC readout, project transfer and online monitoring. Select the EH CPU type; a similar code does not make an EH2 or EH3 project directly suitable for an EH. Match software release and firmware to the instructions used.

COMMGR manages the ISPSoft communication connection. Back up the existing project, required retained registers and communication settings before downloading. Also inspect the BAT.LOW indicator and the maintenance conditions for battery-supported memory.

Programming cable and serial communication

The DVPACAB2A30 programming cable connects to the COM1 8-pin Mini-DIN RS-232 port; its computer end uses a 9-pin D-sub connection. If the computer has no serial port, use a suitable USB-to-RS-232 adapter with its driver. An ordinary USB cable does not connect directly to a first-generation EH.

In COMMGR, select an RS232 driver, the correct COM number and matching PLC serial parameters. Configure WPLSoft through its communication menu. Observe the differences between RS-232, RS-422 and RS-485; a USB-to-TTL cable is not a substitute for RS-232 hardware.

For COM2 Modbus/RS-485 communication, match station address, baud rate and Modbus RTU or Modbus ASCII settings. Inspect any fitted communication cards or network modules separately; connector shape alone does not establish an Ethernet interface.

Expansion and commissioning

For analog input, analog output or temperature measurement, select compatible Delta DVP expansion modules or EH function cards. Check card model, power budget and program addressing together. X/Y addressing is octal: X10 follows X7.

On motion applications, test homing direction and limit switches at low speed. When replacing a CPU, compare terminal layout, normal/high-speed output functions and instruction compatibility as well as the I/O count.

Editor’s Note

Read R, T, M and any 2/3 suffix clearly on the nameplate. A similar 32-point enclosure does not establish the same terminals or motion capabilities.

Do not rely only on POWER and RUN indicators. Confirm program readout, then test every digital input and output with a suitable load. An audible relay click alone does not prove that its contacts can switch the load.

If BAT.LOW is on, back up the program and required retained data before battery replacement. Follow the manufacturer’s replacement-time and memory-retention conditions; do not assume that data will survive an extended period without the battery.

Do not confuse the M model’s 5 V high-speed inputs with normal 24 V inputs. Use a suitable oscilloscope or counter to inspect pulse frequency and waveform rather than declaring the output healthy from a multimeter reading alone.

For communication interruptions or incorrect counts, inspect cables, shielding and grounding first. Loose terminals, supply instability and faulty adapters can resemble CPU faults.

Do not erase a working machine program as a first troubleshooting step. Assess emergency stopping and the safety relay arrangement against machine risk. Disconnect power before board repair or component replacement.

PDF documents and related topics

Use Delta DVP PLC files for series documents. Consult the EH sections of the DVP-PLC programming manual for legacy instructions and addressing, and the ISPSoft user manual for software communication.

Navigation: Delta DVP PLC series · Delta DVP-EH2 · Delta DVP-EH3 · Delta WPLSoft · Delta ISPSoft · Used Delta equipment.

External references

Delta DVP-EH manufacturer instruction sheet, 6 July 2006 English archive · Delta explanation of WPLSoft and ISPSoft. Distinguish first-generation EH documentation from EH2/EH3 documentation.