Delta DVP40EH00T · DVP-EH PLC with 24 Inputs and 16 Transistor Outputs

The Delta DVP40EH00T is a first-generation DVP-EH PLC main unit with a 100–240 V AC supply, 24 digital inputs rated for 24 V DC, and 16 open-collector transistor outputs. It reads sensors, runs sequences and switches DC control signals on conveyor, packaging and assembly machines. Delta’s legacy specifications list 15,872 program steps and battery-backed SRAM for the original EH family.

Inputs, outputs and terminal addresses

Inputs X0–X27 and outputs Y0–Y17 use octal addressing. X10 follows X7. When wiring an inductive sensor, photoelectric sensor or limit switch, check the S/S input common and PNP or NPN signal type against the panel schematic.

The NPN open-collector outputs are for DC control circuits. Check the load supply, output-group common and load current together. For a contactor or valve coil, check both the steady-state and inrush current, along with the required transient suppression.

Pulse applications and related Delta models

When using an encoder, check its signal level, the input assignments and the counting mode in the project. Delta lists 200 kHz pulse output for the 20- and 32-point models in the original EH family. Before commissioning a servo drive or stepper motor drive with the DVP40EH00T, verify the project’s pulse instruction, output address and the drive’s input circuit.

The DVP40EH00R has the same 24 inputs and 16 outputs with relay switching. The DVP40EH00T2 belongs to EH2 and the DVP40EH00T3 belongs to EH3. When replacing the CPU, compare terminal layouts, motion instructions, retained data areas and fitted modules by exact model code.

Programming software and cable

Use WPLSoft for PLC programming, ladder editing and online monitoring. If using ISPSoft, select the original EH target in the installed release and configure the serial channel in COMMGR. Keep the source project and required retained data for the running machine.

The computer connects through COM1, an 8-pin mini-DIN RS-232 port. Delta specifies the DVPACAB2A30 serial cable. For a USB-equipped computer, use a suitable USB-to-RS-232 adapter and its driver. Select the COM number assigned by Windows and match the machine’s existing serial settings.

The RS-485 interface on COM2 handles industrial communication with an HMI panel and other field devices. On a Modbus RTU link, match the station address, baud rate, parity and data format.

Editor’s Note

On a used unit, look for DVP40EH00T on the nameplate. Photograph the supply terminals, output commons and fitted cards before taking the old unit out.

Read the program through COM1 first. Then monitor the inputs online and verify the outputs with a suitable DC test load. This gives you separate bench checks for the port and I/O.

If an output LED turns on and the load stays off, check the common terminal and external load supply. On a pulse channel, use a suitable instrument to check the frequency and waveform.

If counting or communication becomes unstable when the motor starts, check the signal cable route, shield and panel grounding. Inspect the drive’s EMC filter connection if fitted.

If BAT.LOW is lit, back up the program and required retained register values before a planned shutdown. Follow the original EH instruction sheet when servicing the battery.

Related topics and internal references

Delta DVP PLC PDF files · Delta ISPSoft user manual (English PDF)

Browse Delta · Used Delta equipment · Delta PLC · DVP PLC series

External references

Delta original DVP-EH installation and wiring sheet, 5011621601-EHE1 (EN) · Delta DVP series technical information (EN) · Delta hardware FAQ · pulse frequency and serial cable, Questions 7–8 (EN)