Delta DVP80EH00R
Delta DVP80EH00R Relay Output PLC
The Delta DVP80EH00R is an original DVP-EH PLC CPU with 40 digital inputs and 40 relay outputs. It takes a 100–240 V AC supply and stores up to 15,872 program steps in battery-backed SRAM. It handles sequence automation on packaging lines, conveyors and machines with numerous sensors, valves and control signals.
24 V DC inputs and high-speed counting
The 40 inputs at X0–X47 use octal addressing, so X7 is followed by X10. An inductive proximity sensor can detect product position, a photoelectric sensor can detect a passing product, and a limit switch can report end of travel. Wire the S/S input common to match the 24 V DC field device’s PNP or NPN output.
For suitable original EH high-speed counter channels, Delta specifies up to 200 kHz in single-phase mode and up to 100 kHz in two-phase A/B mode. The channel, counting mode and input filter determine the applicable limit. For conveyor travel or cut-length measurement, check the encoder output type and A/B phase order. Run a known distance first and compare it with the PLC count.
40 relay outputs and common terminals
Relay outputs Y0–Y47 are grouped by commons C0–C9. Typical loads include an interposing relay, a contactor control circuit or a panel indicator. Delta’s legacy selection table lists 1.5 A per output. Its 2006 wiring sheet lists 2 A per output and 5 A per common. Size loads using the unit label, the documentation matching its hardware and the load’s inrush current. Select the fuse and coil suppression for the load circuit.
Programming software, cable and communication
Use WPLSoft to read, back up and monitor the existing program. In the PLC programming software, select the original EH CPU type for the Ladder project. If using ISPSoft, check that the installed release includes the legacy EH target and configure the serial connection in COMMGR.
The DVPACAB2A30 programming cable connects the PC’s DB9 serial port to the PLC’s 8-pin Mini-DIN COM1 (RS-232) port. For a USB-only PC, fit a USB-to-RS-232 adapter with its driver at the DB9 end. Select the COM number assigned by Windows and match the PLC’s serial settings.
COM2 RS-485 can connect to an operator panel or drive. Record the station address, baud rate, parity and frame format on the Modbus link. Route serial and encoder cables away from motor wiring to reduce electrical interference.
Editor’s Note
When buying used, read the full DVP80EH00R code on the label. Check that all terminal blocks are present and look for loose or discoloured terminals around C0–C9.
If the old CPU still runs, back up the program, retained data and communication settings first. If BAT.LOW is on, complete the backup before servicing the battery.
Photograph and label each terminal block before removing it for a CPU swap. If several loads on the same common stop together, start by checking that group’s supply.
The output LED shows the command. With the machine loads disconnected, test the contacts on the bench with a suitable low-voltage load. If the LED lights and the load stays off, check the common supply and the contact separately.
If the PLC or HMI drops out when a contactor pulls in, measure the supply under load. Check coil suppression, serial cable routing and cabinet grounding together.
Related models and topics
In the same generation, the DVP64EH00R has 32 inputs and 32 relay outputs. The DVP80EH00T has the same 40+40 I/O count with transistor outputs. The DVP80EH00R2 belongs to EH2 and the DVP80EH00R3 belongs to EH3. Before changing generations, compare terminal assignments, common groups, expansion modules and program instructions.
RS-232, RS-422 and RS-485 compared · Delta DVP PLC series · Used Delta equipment
Internal references and PDF files
OtomasyonAVM Delta DVP PLC Files
External references
Delta DVP-EH installation and wiring sheet (PDF, 2006, EN) · Delta DVP technical information and model selection table (PDF, EN) · Delta DVP-PLC user manual covering the original EH series (PDF, RU) · Delta serial programming cable FAQ (EN)