Delta DVP-EH2

Delta DVP-EH2 PLC Series

Delta DVP-EH2 is a PLC family for machine sequencing, high-speed counting and model-dependent positioning. Its CPU provides 16k steps of program capacity, with a family expansion limit of 512 I/O points. Typical applications include packaging, cutting and handling machinery. Actual system capacity depends on the selected main unit, modules and power budget.

Models, I/O and power supply

DVP16EH00R2 has 8 inputs/8 relay outputs; DVP20EH00T2 has 12 inputs/8 transistor outputs; DVP32EH00R2 and DVP32EH00T2 have 16 inputs/16 outputs. DVP40EH00T2 has 24 inputs/16 outputs. The R2 suffix identifies relay outputs, while T2 identifies NPN transistor outputs.

EH00 main units use 100–240 V AC, 50/60 Hz. The +24V/24G terminals are an auxiliary DC output, not a 24 V DC CPU power input. Account for field input consumption when calculating the auxiliary load. Check the nameplate and terminal diagram before applying power.

Programming software

Program the DVP-EH2 with WPLSoft or ISPSoft. Select the correct EH2 CPU for the ladder diagram project. For ISPSoft, configure a serial driver in COMMGR; depending on the release, its type is labelled RS232 or RS232/422/485. Match the actual PC COM port, PLC station address and serial settings.

Set the COMMGR driver to START, then select it in ISPSoft communication settings. Back up the existing program and retained data before making changes. A PLC upload does not guarantee recovery of all comments and symbols from the original engineering project.

Programming cable and communication ports

The standard PC connection uses COM1 RS-232 with an 8-pin mini-DIN connector. Suitable cable examples include DVPACAB215 (1.5 m) and DVPACAB230 (3 m). A PC without a serial port needs a USB-to-RS-232 adapter, its driver and the appropriate DVP cable. An ordinary USB cable cannot connect directly to the EH2 for programming.

The main unit also includes COM2 RS-485. Modbus ASCII/RTU supports data exchange with an HMI, SCADA or other field devices. A standard EH2 CPU has no built-in USB or Ethernet port; Ethernet access requires separately selected compatible communication hardware and protocol support.

200 kHz pulse output depends on the model

Check the complete model code before selecting high-speed pulse outputs. DVP20EH00T2 and DVP32EH00T2 use Y0/Y2; DVP40EH00T2 uses Y0/Y2/Y4/Y6 for pulse output up to 200 kHz. The 2014 instruction sheet also identifies Y0–Y3 on DVP60EH2 as high-speed points. Do not extend this rating to every T2 model. Relay models are unsuitable for high-speed pulse generation.

DVP32EH00M2 provides two differential output channels using terminals Y0–Y3. Its entire output bank is not differential. For a servo application, match the servo drive input interface, pulse/direction format and electronic gearing to the servo motor system.

Encoders and field inputs

For an encoder, check signal level, common wiring, input filtering and counting mode. Single-phase and A/B quadrature counting with an incremental encoder do not imply the same frequency limit. Verify the home position, limit switch, inductive sensor and photoelectric sensor inputs online before testing controlled machine motion. X/Y addresses use octal numbering: X10 follows X7.

Analog expansion and module compatibility

Digital EH2 main units require a suitable card or module to process an analog signal. Analog input examples include DVP-F2AD and DVP04AD-H2; digital-to-analog conversion examples include DVP-F2DA and DVP04DA-H2. The analog I/O range and resolution depend on the module. A temperature sensor requires an input module matching its PT100 or thermocouple type.

Distinguish standard right-side expansion from the left-side support of DVP32EH00R2-L/T2-L. Check the complete part number and EH2 support when selecting DVP expansion modules. Replacing an EH2 with a DVP-EH3 requires a review of the program, retained data, output type and addressing.

Safety, battery and technical files

Design the emergency stop and required safety relay circuit according to the machine risk assessment. Grounding and signal shielding are particularly relevant to high-speed inputs. Investigate a BAT.LOW indication and back up the program and retained data before battery work.

Use Delta DVP PLC files for manuals and wiring documents. Our 2006 English EH2 instruction sheet is useful for older hardware. For later models or revised electrical ratings, follow the applicable manufacturer edition.

Editor's Note

Read the entire nameplate before buying or replacing a controller. R2, T2, M2 and -L identify different hardware. Photograph the terminals and module order before removing a working PLC.

If the PC cannot connect, check its COM number, adapter driver, DVP cable and COMMGR status before concluding that the PLC is faulty. Confirm that another application is not holding the same serial port open.

A RUN indicator alone is insufficient for a used unit. Monitor the inputs and test each relay or transistor output with a suitable load. If pulse operation is required, verify the output with an oscilloscope or suitable instrument.

If an output indicator operates but its load does not, measure the common connection, field supply and load wiring first. A worn relay contact or damaged transistor is possible; confirm the fault with a known suitable load before replacing the board.

Take a backup before battery or board work. Inspect hardware with power removed and capacitors confirmed discharged. Resetting a controller before preserving its program can turn a communication problem into a machine shutdown.

Related topics and navigation

Delta DVP-EH3 · Delta DVP-PM · Delta PLC software · Delta DVP PLC series · Delta PLC · DVP PLC files

External references

Delta DVP-EH2 Instruction Sheet, 2014 · Delta DVP Catalogue, 2011 · Delta WPLSoft / ISPSoft FAQ · Delta ISPSoft / COMMGR FAQ