Delta DVP32HN00R
Delta DVP32HN00R — 32 Relay Output Expansion Unit
Delta DVP32HN00R is a Delta automation expansion unit providing 0 digital inputs and 32 relay outputs. It belongs to the DVP EH module family and adds switching points to a host PLC. It has no independent CPU program or standalone machine-control function.
Typical applications include contactor coils, suitably rated solenoid valves, indicator lamps and auxiliary control circuits. HN identifies output expansion and R identifies relay outputs. When selecting DVP expansion modules, compare the supply, common-terminal arrangement and host compatibility as well as the I/O count.
Power supply and basic specifications
Supply: 100–240 V AC, 50/60 Hz; the manufacturer sheet specifies −15% / +10% voltage tolerance and 30 VA consumption. The L/N supply and the field circuits switched by the contacts serve separate purposes. Do not confuse this unit with a 24 V DC-powered HN11 module. The 500 mA auxiliary 24 V output stated for HP models in the same sheet must not be assigned to this model.
I/O: 0 DI / 32 relay DO. Dimensions: approximately 143.5 × 90 × 82.2 mm (width × height × depth). Mounting: 35 mm DIN rail or direct screw mounting. Operating temperature: 0–55 °C. Allow enclosure space for ventilation and wiring.
Relay outputs and load selection
The unit switches loads through relay contacts, rather than NPN/PNP transistors. The sheet gives voltage ceilings of 250 V AC and 30 V DC. Its detailed output table specifies 1.5 A per output and 5 A per common, while the model overview states 2 A per output. Use the lower detailed limit for this edition and check documentation matching the installed hardware revision.
The total current of each common group must also remain within its limit; a per-channel rating does not permit all 32 channels to carry that current simultaneously. The stated relay response is approximately 10 ms. These outputs are unsuitable for high-speed pulse, PWM or servo pulse commands. Select intermediate relays/contactors and suitable coil suppression for the actual current, inrush and switching frequency.
Host compatibility and output addressing
The unit belongs to the DVP-EH expansion family; Delta’s EH3 catalogue explicitly lists DVP32HN00R. For replacement in DVP-EH2 or DVP-EH3 systems, check the host expansion table, hardware revision and total I/O limits. Compatibility with other Delta families cannot be inferred from the brand name.
The 32 local outputs use Y0–Y37 octal numbering. Program addresses depend on the CPU and preceding modules. For example, when this is the first digital extension after an EH CPU with 16 outputs, the allocation is Y20–Y57. This example is not a universal fixed address range. The unit adds no X input group.
Programming software and connection cable
No separate program is downloaded to DVP32HN00R. Outputs are controlled by the host PLC program. Select WPLSoft or ISPSoft according to the CPU and project; Delta’s EH3 application note uses both tools. For legacy EH CPUs, verify that the chosen software version supports the actual target.
Connect the computer to the host CPU, not to this expansion unit. The manufacturer cable guide shows UC-PRG020-12A for USB-to-RS-232 COM1 connection to EH3 CPUs. UC-MS020-01A is used with a suitable PC serial port or appropriate USB-to-RS-232 converter. Check the port and pinout when selecting a Delta PLC cable, and verify the USB driver and COM-port assignment. The expansion connection is not a programming interface.
Editor’s Note
Start with the complete label on a used unit. DVP32HN00R and transistor-output HN00T units can look similar; check the output technology before using existing wiring.
A relay click and an illuminated LED do not prove that the contact is sound. With power isolated and field wiring disconnected, check for welded contacts; then use a compatible CPU and a fused low-voltage test load to check channels individually.
For a single failed channel, inspect the contact, terminal and solder joints. If a whole group fails, also check its common supply and fuse before condemning every relay.
Discoloured, loose or melted terminals call for an actual load-current check. Replacing a relay while leaving excessive inrush or coil transients unresolved can repeat the fault.
Replacement relays must match coil voltage, contact arrangement, pinout and load class. Work on the mains section and insulation checks require qualified technical personnel.
Rebuild the Y-address list after changing module order, remove test forces and retain a program backup. These general inspection suggestions do not certify the condition of any particular unit offered for sale.
Related models and functional differences
DVP32HN00T: 32 transistor outputs, requiring a wiring review before replacement. DVP32HP00R: 16 inputs + 16 relay outputs. DVP48HP00R: 24 inputs + 24 relay outputs. DVP08HN11R: 8 relay outputs. DVP16HP11R: 8 inputs + 8 relay outputs.
For input expansion, consider DVP32HM11N, or the smaller DVP08HM11N and DVP16HM11N. These provide a different function from an output unit; select them against the host compatibility and field requirements.
PDF files and related topics
Use our Delta DVP PLC files page for series documentation. External references below include the legacy 2008 DVP-EH DIDO instruction sheet and the host-CPU cable guide. The instruction sheet contains English and Chinese sections; it is not a Turkish translation.
What is a PLC? · Delta PLC · Delta DVP PLC series · Modbus RS-485 communication
Navigation: Delta main page · EH expansion modules · DVP PDF archive