Delta DVP08HN11R – 8-Point Relay Output Expansion Module
Delta DVP08HN11R adds eight digital relay outputs to a DVP-EH installation. It has no digital inputs and is not a standalone PLC CPU. Its outputs operate through the host PLC program's Y addresses. The manufacturer's table identifies it as a 24 V DC unit consuming 1.5 W; the exact model also appears in the DVP-EH3 catalogue.
Typical automation duties include switching suitable indication lamps, solenoids, interposing relays and contactor coils. The R suffix identifies relay outputs. DVP08HN11T is a transistor-output version; changing between them requires a load and wiring review.
Module supply versus switched load voltage
The electrical table specifies 24 V DC, 20.4–28.8 V DC, with 1.5 W consumption. These figures describe the unit's electronics, rather than the voltage of the external circuit switched by its contacts. Check the expansion power arrangement and host supply capacity together. Do not copy the L/N supply wiring of larger AC-powered units such as DVP32HN00R onto this module.
C0 and C1 are the relay contact-group commons. External load circuits connect through these terminals; the module does not generate load voltage. With a power supply or DIN rail power supply for 24 V loads, calculate load current, conductor size and protection separately. The sheet gives 250 V AC/30 V DC switching voltage limits. Never apply mains voltage to an expansion connector or an unused terminal.
Output ratings, common groups and drawing discrepancy
The manufacturer's selection table says 2 A per point, while its detailed resistive-load table specifies 1.5 A per point and 5 A per COM. Use the detailed table and actual hardware revision for load calculations. Four outputs at 1.5 A would total 6 A, exceeding the 5 A common rating. The stated relay response is approximately 10 ms.
The HD00 terminal drawing shows C0 for Y0–Y3 and C1 for Y4–Y7. Edition discrepancy: one terminal in the second 08HN group is printed “C6” in HD02 and “Y6” at the same position in HD00. Verify the physical terminal label and the correct revision's wiring diagram before connection. Do not wire the unused positions marked with a dot.
For inductive loads such as a contactor or valve coil, consider inrush, switching frequency and contact life. Use suitable fuses and suppression: a suitable diode for a DC coil, or an appropriate RC/varistor solution for an AC coil. A correctly selected interposing relay and socket can reduce the load switched directly by the module. A clicking relay does not establish healthy operation under load.
When switching a variable frequency drive control input through a dry contact, check the drive's sink/source arrangement and input common. PNP/NPN transistor-output selection does not apply to DVP08HN11R itself; that distinction belongs to the connected input circuit. Mechanical contacts are unsuitable for PWM or servo pulse trains.
Host compatibility, software and programming cable
DVP08HN11R belongs to the DVP-EH module family. In DVP-EH2 and DVP-EH3 applications, check the exact CPU, expansion interface, module order and supply budget. The DVP name alone does not prove compatibility with every CPU or slim S-series expansion chain.
Edit the host CPU program using WPLSoft or an ISPSoft version supporting that CPU. No separate user program is downloaded to this module; ordinary digital outputs use the CPU's Y area. The ISPSoft connection may require suitable COMMGR settings. Analogue-module FROM/TO measurement-register access is unnecessary for ordinary output operation.
The programming cable connects to the host CPU. The catalogue lists UC-PRG020-12A, DB9 female to 8-pin mini-DIN male, for suitable DVP RS-232 ports. DVPACAB2A30 also occurs in older installations; verify the CPU port and pinout. A computer without a serial port requires a suitable USB-to-RS-232 converter, driver and COM setting. The expansion ribbon is separate from the PLC programming cable.
Y addressing and commissioning
Delta X/Y addresses use octal numbering. Local Y0–Y7 terminal labels do not necessarily correspond to Y0–Y7 in the CPU program. Example: if the host outputs occupy Y0–Y17 and there is no preceding output expansion, the first eight-output module may occupy Y20–Y27. Verify this against the actual CPU and expansion sequence. This output-only unit has no X input addresses.
After confirming addresses, a bench-test relationship using LD M100 and OUT Y20 can operate the first relay with a low-power test load. Do not force outputs casually with machine motors or valves connected. Compare an HMI or SCADA command with the CPU Y bit, output LED and physical contact result separately.
Inductive sensors, photoelectric sensors and capacitive sensors connect to suitable host or input-module terminals; sensor wiring does not add inputs to DVP08HN11R. High-speed encoder signals also require appropriate counter inputs. Approximate dimensions are 40 × 90 × 82 mm (width × height × depth), with 35 mm DIN rail or screw mounting and a 0–55 °C operating range. Allow ventilation and separate signal/power wiring when arranging panel components.
Editor's Note
Read the full code first: HN identifies this output module and R identifies relay outputs. Do not confuse it with the DVP08HM11N input module or DVP08HP11R mixed-I/O module.
Check the two common groups independently. If four outputs fail together, inspect the relevant common supply, fuse and terminal before condemning the complete board.
Test every relay separately with a low-power load. Welded contacts, slow release, excessive voltage drop and heating matter when assessing a used unit.
Remember the C6/Y6 edition discrepancy. Verify the physical terminal label before moving a wire. Photograph and number the existing wiring before removal.
Back up the host program and existing Y addresses before replacement. Equal output counts do not mean a module moved elsewhere in the chain keeps the same addresses.
Do not insert or remove the module while powered. Isolate load power before continuity measurements. Replacement relays must match coil voltage, contact arrangement and current rating together.
PDF documents and related topics
Use our Delta DVP PLC PDF files page for wiring diagrams. This model is linked to the shared DVP-EH DIDO HD02 sheet dated 15 August 2013 and HD00 dated 25 April 2008. HD00 is an older edition retained for terminal comparison. The DVP/TP catalogue dated 3 January 2023 is also a selection reference. Original English/Chinese PDF content is preserved.