Delta DVP08HN11T

Delta DVP08HN11T – 8 NPN Transistor Output Expansion Module

Delta DVP08HN11T is an 8-point NPN transistor output expansion module in the Delta DVP EH module family. It has no input channels. It adds outputs to a suitable host PLC rather than operating as a standalone CPU.

Typical tasks include operating additional DC valves, indicator lamps or suitable interposing relays. When selecting DVP expansion modules, check load voltage, current and output polarity together. The T suffix identifies transistor outputs; do not copy a relay model’s field wiring without checking it.

Technical specifications

I/O: 0 inputs, 8 outputs. Supply class: 24 V DC; the sheet specifies 20.4–28.8 V DC. Outputs: NPN open collector, 5–30 V DC load circuit. Assess the expansion-system power budget separately from the field-load supply.

Current per channel: 0.3 A at 40°C; 0.2 A at 45°C; 0.15 A at 50°C; 0.1 A at 55°C. Common-terminal limit: 2 A/COM. Both the individual channel limit and simultaneous total current through each common must be respected.

Switching: 15 µs turn-on, 25 µs turn-off. Dimensions: approximately 40 × 90 × 82 mm (width × height × depth); 35 mm DIN rail or suitable screw mounting. Switching time alone does not establish a guaranteed pulse-output frequency.

NPN output wiring and load selection

An active NPN output sinks load current towards 0 V. In the basic circuit, connect the load between +DC and the relevant Y output, and connect the output group’s C common to DC 0 V. Match the C0/C1 groups to the unit’s terminal diagram.

There are no X input channels or S/S input-selection terminal to configure on this output-only model. Establish the load supply before expecting an output LED to correspond to an operating load. Transistor outputs are not dry contacts and must not switch AC loads directly. Use suitable suppression for inductive DC loads and check running and inrush currents.

Host PLC compatibility

DVP08HN11T is listed in the DVP-EH digital expansion sheet and the DVP-EH3 manufacturer catalogue. For an existing DVP-EH2 or other EH installation, check the exact CPU model, revision, expansion connection and power budget. Do not assume the same connection arrangement across every Delta DVP series.

The module connects through the PLC expansion connection, which is separate from the PC programming cable. Disconnect power before fitting, removing or rewiring the module.

Addressing and program use

The host CPU program operates the outputs through Y addresses. In a suitable EH installation whose host has 16 outputs and no preceding output expansion, the first eight-output module can use the example range Y20–Y27. This starting address is not universal; the host I/O arrangement and preceding modules determine the actual allocation.

DVP X/Y addresses use octal numbering: Y27 is followed by Y30. Distinguish local Y0–Y7 terminal labels from the system addresses used in the CPU project. Verify the allocation from the module order and online monitoring.

Programming software and cable

No separate program is downloaded to DVP08HN11T. A suitable host CPU project can be prepared using WPLSoft. ISPSoft is an option when the exact host CPU and version are supported. Do not select DVP08HN11T as the CPU; choose the appropriate tool from Delta PLC software.

For a suitable EH CPU with an RS-232 port, use the appropriate PC RS-232 → UC-PRG020-12A → CPU connection. UC-MS020-01A is another cable used for suitable RS-232 connections. A computer without a serial port requires a suitable USB-to-RS-232 adapter and driver. Check the CPU port and pinout; the programming cable does not connect to this output module.

Related models and differences

DVP08HN11R provides eight relay outputs; its load wiring must not be treated as identical to the NPN transistor version. DVP08HP11T provides 4 inputs/4 transistor outputs, while DVP16HP11T provides 8 inputs/8 transistor outputs.

For more outputs, compare the 32-output DVP32HN00T. If inputs are also needed, DVP32HP00T provides 16 inputs/16 outputs. Different point counts, supplies and terminals mean these models should not be assumed to be direct replacements.

Editor’s Note – Workshop tests and used equipment

Read the complete HN11T code. Confusing it with the relay-output HN11R can produce misleading results when the same test wiring is used.

Establish a suitable host PLC, expansion connection and actual Y addresses first. An addressing mistake should not lead to a working module being rejected.

Test all eight outputs individually with a suitable low-current load. Check actual load switching as well as LEDs; an unloaded voltmeter reading is insufficient.

If a whole group fails, check the common terminal, field supply and wiring first. For a single-channel fault, compare the load and cable using a working channel under controlled test conditions.

For faults that appear as the unit warms up, check coil current, simultaneous total load and cabinet temperature together. Correct a faulty load before reinstalling a repaired module.

When buying used equipment, request clear label, terminal and expansion-connection photographs. A loaded output test is more informative than evidence that the unit merely powers up.

PDF documents

Documentation centre: Delta DVP PLC PDF files. The DVP-EH DIDO instruction sheet and DVP series catalogue are associated with this model. Shared documents remain linked to the other EH models in the archive. Compare older instructions and ratings with the actual equipment label and revision.

Related topics

For additional inputs, see DVP08HM11N, DVP16HM11N and DVP32HM11N. Mixed relay-output modules include DVP08HP11R and DVP16HP11R.

Navigation: Delta main page · Delta PLC · EH modules · DVP PDF archive

External references

Delta DVP manufacturer catalogue, printed pp. 43 and 48. Delta DVP-EH DIDO instruction sheet, 25 April 2008 edition; archived manufacturer document containing English and Chinese text.