Delta DVP08HP11T

Delta DVP08HP11T – 4-input, 4-transistor-output digital expansion module

Delta DVP08HP11T is a mixed digital expansion module with four 24 VDC inputs and four NPN open-collector transistor outputs for the DVP-EH family. The 08 means eight I/O points in total, rather than eight inputs or eight outputs. The connected PLC CPU executes the control program.

It can add several sensor signals and DC control outputs to a machine. Typical duties include reading an inductive sensor, photoelectric sensor, pushbutton or limit switch, and controlling suitably rated DC relay or valve coils. In an automation project, check output polarity and load current as well as the number of points.

Power supply and digital inputs

The manufacturer's EH digital I/O instruction sheet specifies 24 VDC supply, with a permitted range of 20.4–28.8 VDC. Size the DIN rail power supply for the module, sensors and external output loads. The AC supply arrangement of larger EH expansion units must not be applied to this small DC model.

The four inputs are rated at 24 VDC, approximately 5 mA. The sheet specifies ON above 16.5 VDC, OFF below 8 VDC, and approximately 20 ms input response time. Do not treat the intermediate voltage region as a guaranteed logic state. The input circuit uses photocoupler isolation and status LEDs.

For an NPN sensor, connect S/S to +24 V; for a PNP sensor, connect S/S to 0 V. Connect the sensor signal to its X input. Select NPN or PNP wiring together with the input common arrangement. Do not mix incompatible sensor polarities on one S/S group. X0–X3 on the module identify its local input channels.

Transistor outputs and load wiring

The four outputs are NPN open collector. A typical DC load circuit is +V → load → Y output, with C0 connected to the load supply's 0 V. C0 is the common for Y0–Y3. When enabled, the transistor output sinks load current; it is neither a dry contact nor a PNP output supplying +24 V.

The model table lists a 5–30 VDC load supply range. Maximum output current per channel is temperature dependent: 0.3 A at 40°C, 0.2 A at 45°C, 0.15 A at 50°C and 0.1 A at 55°C. The 2 A/COM limit does not override individual channel ratings. For example, four 0.1 A loads at 55°C total 0.4 A.

The stated switching times are approximately 15 µs OFF-to-ON and 25 µs ON-to-OFF. These figures do not establish a high-speed pulse-generation function. With approximately 20 ms input response, the module should not be selected as a high-speed encoder counter simply because it has digital inputs.

Use a suitable suppression diode or the coil manufacturer's recommended suppression circuit with DC relay and valve coils. Compare contactor coil voltage, holding current and inrush current with the output ratings; add a suitable interface relay or driver where needed. Provide appropriate circuit fuse protection and do not assume a load short circuit will leave the output transistor undamaged.

CPU compatibility and I/O addressing

DVP08HP11T belongs to the DVP EH digital expansion module family. It appears in the older DVP-EH instruction sheet and in the EH3 expansion list of the 2023 DVP catalogue. For EH2 or another host, match the full CPU code, generation, expansion connection and system limits against the host hardware manual. Compatibility with the slim S-series expansion connection must not be assumed.

Inputs use X addresses and outputs use Y addresses, with octal numbering: X7 is followed by X10, and Y7 by Y10. The local X0/Y0 marking on a module does not mean that its channels always appear at CPU addresses X0/Y0. The CPU and preceding expansion units determine the actual starting addresses.

For the arrangement illustrated in the EH sheet: an 08HP mixed module installed as the first digital expansion of a 16EH CPU uses X20–X23 and Y20–Y23. Treat this as a specific example and confirm the real allocation online before using it in a project. Ordinary digital I/O access is different from configuring analog-module CR registers using FROM/TO instructions.

Programming software and programming cable

DVP08HP11T does not receive a separate user program. Perform PLC programming with a WPLSoft or ISPSoft version supporting the actual CPU. Its X/Y signals are handled in the CPU's ladder program. Select the correct CPU and preserve the existing project and version information. With ISPSoft, configure the appropriate communication driver and COM port through COMMGR.

For an EH3 CPU COM1 RS-232 port, Delta's cable guide lists UC-MS020-01A, 2 m and UC-MS030-01A, 3 m. These have an 8-pin male mini-DIN PLC connector and a female DB9 PC connector. A computer without RS-232 needs a suitable USB-to-RS-232 adapter, its driver and the correct COM selection.

The same EH3 connection diagram also lists UC-PRG020-12A, a 2 m USB programming cable, with its compatible USB driver. These connections belong to the CPU's COM1 port. DVP08HP11T has no independent USB, Ethernet or RS-485 communication port. Connect the programming cable to the CPU; confirm the correct port and cable separately for another CPU generation.

Installation and field checks

Isolate power before connecting the module through the appropriate EH expansion interface. Inspect the connector, ribbon cable and retaining parts. Provide proper grounding, ventilation and separation between signal cables and power cables. Check that the sensor supply still has enough capacity after adding more input devices.

Start by checking S/S wiring and input LEDs, then monitor the corresponding X addresses in the CPU. If an output LED turns on but the load remains off, inspect C0, the external load supply, the load return path and the output device. An unloaded voltage reading alone does not prove that a channel can supply its intended load current.

Editor's Note

Start with the label: it must say DVP08HP11T. Confusing HP with HN or T with R changes the I/O arrangement or output technology. When buying a used unit, ask for a test of every input and output, rather than relying on one photograph of illuminated LEDs.

If an input does not respond, check the sensor polarity, S/S connection and sensor 0 V before condemning the module. Measure the sensor signal both disconnected and connected. Leakage current or a poor common connection can produce misleading readings.

Test outputs with a small, known DC load. If using a resistor, calculate current with I=V/R and power with P=V²/R; allow a suitable resistor power margin and respect the temperature-dependent output rating. A large coil is a poor first test load.

If the output LED is on but the load is off, check the common and supply first. Avoid shorting a Y terminal directly to +24 V. Before replacing a failed output device, inspect the field coil, suppression diode and cable so the original fault does not destroy the replacement.

Back up the CPU program, photograph the I/O order and label the wires before replacement. Keep the machine in a safe test state and remove any temporary forces afterward. Finish by checking stable operation with the actual intended loads.

Related modules and topics

DVP08HP11R: four inputs and four relay outputs. DVP08HN11T: eight transistor outputs only. DVP16HP11T: eight inputs and eight transistor outputs. DVP08HM11N: eight digital inputs only. These are functional comparisons, not guaranteed drop-in replacements.

Use our Delta DVP PLC PDF files page for documentation. Select documents by the full module code and CPU family; a catalogue, installation sheet and programming manual serve different purposes.

Navigation: DVP08HP11T main page · EH modules · DVP PLC series · Delta PLC models · Used Delta products · DVP PDF files

External references

Delta DVP-EH DIDO instruction sheet – 25 April 2008, English/Chinese · Delta DVP catalogue – EH3 expansion list, English · Delta PLC/HMI Cable Selection Guide – 2019, English · Delta ISPSoft user manual – CPU support and COMMGR