Delta UC-PRG020-12A
Delta UC-PRG020-12A
Delta UC-PRG020-12A is a 2-metre programming cable with an integrated converter, connecting a computer's USB port to a suitable device's RS-232 port. It has USB Type-A at the computer end and 8-pin male mini-DIN and female DB9 serial connection options. Select the connector using the device's port drawing.
Mini-DIN, DB9 and adapter use
The mini-DIN connection serves appropriate Delta DVP PLC series models in the manufacturer's support table. DB9 examples include Delta AH500, Delta DOP-B and specific Delta TP text panels. The documentation specifies a male-to-male DB9 adapter for AH5xx; verify the complete model and pin assignment.
The guide shows the male-to-male DB9 adapter as an accessory. Check whether it is included, particularly when buying used equipment. A gender changer does not establish the required Rx/Tx connections for every device. Interpret mini-DIN and DB9 drawings together with the receiving and transmitting directions of the other device.
Serial communication and power
The 2015 manufacturer instruction sheet specifies USB 2.0 compatibility and documented serial speed options up to 115200 bps. It lists 7 or 8 data bits, 1 or 2 stop bits and None/Odd/Even parity. Match speed, data format and protocol to the supported settings of the target device.
The converter is USB-powered and needs no separate external supply for itself. The PLC or panel still requires its own specified supply. The instruction sheet describes a steady indicator as normal power and blinking as RS-232 communication; this alone does not establish that a project transfer has completed.
CP210x driver and virtual COM port
The installation shown in the 2019 manufacturer cable guide uses a CP210x USB to UART Bridge driver. After installation, Device Manager displays Silicon Labs CP210x USB to UART Bridge (COMx). Verify the driver package for the actual hardware and operating system, preserving the 32/64-bit distinction.
Select the displayed COM number in Delta WPLSoft or Delta ISPSoft. In installations using Delta COMMGR, configure the corresponding channel for that port as well. Choose software for the CPU generation through Delta PLC software. The same driver appendix also covers Delta IFD6500; a shared driver section does not mean that every port function of the two products is identical.
Related cable differences and documentation
Serial cables such as Delta UC-MS020-01A are covered under Delta DVP communication cables; they are different hardware from the USB-converting UC-PRG020-12A. Review Delta UC-PRG030-10A for DB9 serial, Delta UC-PRG030-01A for mini-USB and Delta UC-PRG030-02A for USB Type-B connections. Select the complete code through Delta DVP programming cables.
Start document selection at Delta PLC accessories files. In the Delta PLC/HMI Cable Selection Guide, Figure 3A/3B on printed page 1-81 shows connector arrangements, while Appendix B.1 on printed page B-2 covers driver and COM-port installation. Review panel-side alternatives under Delta HMI Programming and HMC Cables.
Editor's Note
Inspect the cable together with its adapter. Check the USB plug, mini-DIN pins, DB9 housing and any required male-to-male adapter. A missing adapter can prevent an otherwise working cable from connecting to the machine.
Distinguish COM-port recognition from a PLC response. First establish that the computer recognises the converter, then test communication using the correct COM port, serial format and device address. Check whether another application is holding the port open.
This is an active converter. Continuity measurements alone cannot establish that the complete unit works. Perform an actual read or data-transfer test with a suitable known-good device.
If movement causes disconnections, inspect both sides. The USB port, serial connector and broken conductors near a cable exit can produce similar symptoms. Do not force the PLC socket in an attempt to fix a loose mini-DIN connection.
Preserve the working program backup first. Do not reload an existing project merely to test a connection. Record CPU type, port settings and project version after changing a cable, and separate incorrect settings from hardware faults.
Related topics
Review other supporting hardware under Delta PLC accessories and model documentation under Delta PLC and HMI manuals.
External references: Delta PLC/HMI Cable Selection Guide — 2019, English · Delta UC-PRG020-12A Manufacturer Instruction Sheet — 2015 · Delta official USB-to-RS-232 cable explanation.