Delta DVP08HM11N adds eight 24 V DC digital inputs to DVP-EH control systems. It has no digital outputs. It transfers ON/OFF signals from pushbuttons, limit switches, relay contacts and suitable sensors to the host CPU, which executes the control program.
The HM designation identifies an input module. DVP08HN11R and DVP08HN11T are output expansions; an identical point count does not mean an identical function. For DVP-EH2 or DVP-EH3 installations, verify the host CPU, expansion connection and hardware revision together.
Input specifications
Point count: 8 inputs, 0 outputs. Nominal DC supply rating: 24 V DC, with a specified range of 20.4–28.8 V DC. Input current: approximately 5 mA per point at 24 V DC. ON threshold: above 16.5 V DC; OFF threshold: below 8 V DC. These thresholds concern the signal difference between the input and S/S; the selected circuit determines polarity.
Input response time is approximately 20 ms. The input circuitry uses photocouplers and status LEDs. Approximate dimensions are 40 mm wide × 90 mm high × 82 mm deep; the stated operating temperature is 0–55 °C. Use this module for ordinary status signals; assess short encoder pulses and high-speed counting separately.
NPN, PNP and S/S wiring
For a PNP sensor, use the arrangement with S/S connected to 0 V and the sensor signal connected to its X input. For an NPN sensor, connect S/S to +24 V; the active sensor output pulls the X input towards 0 V. Check the sensor supply and wire identification against its own label or documentation.
For a dry contact in the S/S=0 V arrangement, the contact can switch +24 V to the X input. S/S is an input common, not an arbitrary power terminal. Do not mix NPN and PNP wiring indiscriminately within a shared-common group. NO/NC describes contact or sensor switching behaviour and is a separate distinction from NPN/PNP.
Follow the actual module terminal diagram before wiring. Never apply mains voltage to an input. Route signal cables away from motor and drive power cables. A broken common or falling supply voltage can affect several channels simultaneously.
Addressing and programming
The physical input markings are X0–X7; actual addresses in the CPU program depend on the expansion arrangement. If the module is assigned X20 as its starting address, the eight points occupy X20–X27. X addresses use octal numbering, so X30 follows X27. Do not assume the same starting address for every CPU and panel.
DVP08HM11N does not receive a separate program. The host CPU project reads its X contacts. Use a version of WPLSoft or ISPSoft that supports the actual CPU. Back up the existing program and verify the CPU selection before downloading a project.
Connect the computer to the host CPU programming port. For a suitable DVP CPU RS-232 port, the UC-PRG020-12A USB programming cable is an option; confirm the connector and pinout in the CPU documentation. Install the USB driver and select the correct COM port. The module communicates with the CPU through its expansion connection.
Commissioning and model comparison
Fit the expansion connection with power isolated. Apply a controlled test signal to each channel and check both the module LED and the corresponding X address in the software. If the LED changes but the expected program contact does not, check address allocation. Forcing a software bit does not test the physical input circuit.
For more inputs, compare DVP16HM11N and DVP32HM11N. Smaller mixed I/O options include DVP08HP11R, DVP08HP11T, DVP16HP11R and DVP16HP11T. Replacement assessments must include terminal layout and address changes alongside point counts.
Related topics
Larger mixed expansions include DVP32HP00R, DVP32HP00T, DVP48HP00R and DVP48HP00T. For output-only expansion, see DVP32HN00R and DVP32HN00T; do not assume their supply arrangements match DVP08HM11N.
Measuring 0–10 V or 4–20 mA requires an analog input module such as DVP04AD-H2. Analog control and mixed analog tasks are covered by modules such as DVP04DA-H2 and DVP06XA-H2. DVP08HM11N reads ON/OFF states rather than analog values.
Editor’s Note
Check that a used unit is labelled DVP08HM11N. Similar-looking HN and HP models perform different tasks; an output module will not solve a requirement for eight inputs.
Testing one input is insufficient. Ask for all eight channels to be checked in both states using a suitable 24 V DC test arrangement, observing the LEDs and CPU input information together.
If every input is inactive, inspect S/S wiring, the sensor supply and the expansion connector first. A broken common can make a working module appear faulty.
For a permanently active channel, isolate the field wire safely and measure again. Sensor leakage, damp terminals and the module input circuit are separate possibilities; replacing a photocoupler should follow diagnosis.
Record the program and wiring before repair. Prevent test signals from starting machine movement, and never apply an insulation tester to connected electronic inputs. After repair, confirm the actual input changes in the CPU as well as the LEDs.