Delta DVP04AD-H2

Delta DVP04AD-H2 analog input module

Delta DVP04AD-H2 is a four-channel voltage/current input module used with the DVP-EH2 family. It converts field analog signals into digital data for the PLC program. Each channel can be selected separately for voltage or current. It performs analog input duties; do not confuse it with the DVP04DA-H2 analog output module.

Applications include reading pressure sensors, process transmitters and suitable signal converters. Do not connect bare PT100 or thermocouple leads from temperature sensors directly. Use the voltage/current output of a suitable device such as a PT100 converter, or a temperature module designed for the sensor itself.

Input modes and digital scaling

Each channel has four standard modes: Mode 0: −10…+10 V; Mode 1: −6…+10 V; Mode 2: −12…+20 mA; Mode 3: −20…+20 mA. The factory mode is 0. Voltage conversion is 14-bit and current conversion 13-bit; registers transferred to the PLC are 16-bit words carrying signed data.

With the standard Mode 0 curve, −10 / 0 / +10 V corresponds to −8000 / 0 / +8000. A 0–10 V signal reads 0–8000. Mode 1 has a zero point of 2 V, so the same voltage does not produce the same number in Modes 0 and 1.

Mode selection is particularly important for 4–20 mA. With standard settings, Mode 2: 4 / 12 / 20 mA → 0 / 2000 / 4000; Mode 3: 4 / 12 / 20 mA → 800 / 2400 / 4000. Mode 3's full current range is −20…+20 mA, corresponding to −4000…+4000. These examples assume standard OFFSET/GAIN curves; field calibration changes can affect scaling.

For example, a 0–10 bar sensor with a 4–20 mA output read in Mode 2 gives 2000 at 5 bar. Record both physical range and PLC scale for pressure measurement. When multiplying values for PLC scaling, use appropriate 32-bit arithmetic to avoid intermediate overflow.

Power supply, wiring and isolation

The supply is 24 V DC, with a permitted range of 20.4–28.8 V DC and specified maximum consumption of 2.5 W. Size the DIN rail power supply for the module and field sensors together. Keep sensor signal terminals separate from the module's 24 V power terminals.

Read voltage through the channel's V+–COM terminals. For current input, bridge V+ and I+ on the same channel, connect the current signal to this joined terminal and its return to COM. CR#1 must also select a current mode. Remove the current bridge before using that channel for voltage.

The current manufacturer table specifies input impedance of 200 kΩ for voltage and 250 Ω for current. Consider total loop resistance and the transmitter's available supply headroom. Separate shielded signal cable from power wiring and follow the manufacturer's FG and grounding diagram.

The digital and analog sections are isolated; analog channels are not isolated from each other. Sources at different potentials may require suitable analog signal conditioning or isolation. Response time is specified as 3 ms × number of channels, approximately 12 ms for four channels. Averaging and PLC scan time add to overall measurement latency.

Model identification and module number

The DVP04AD-H2 CR#0 model code is H6400. DVP04AD-H uses H0400, while DVP04AD-H3 is a separate generation. DVP06XA-H2 is also different, providing mixed inputs and outputs. Check the CPU, complete module suffix and firmware together.

Special expansion modules are numbered 0–7 by their distance from the CPU. Intervening digital I/O modules do not count toward this special-module number. DVP04AD-H2 occupies no standard X/Y points. The FROM/TO module number must match the physical arrangement.

Programming software and cable

The module is controlled through FROM/TO instructions in the connected CPU's ladder program. Use a version of WPLSoft or ISPSoft supporting that CPU. COMMGR manages the communication channel for ISPSoft; no separate USB project is downloaded to the module.

A common cable for the CPU's COM1 RS-232 port is DVPACAB2A30: approximately 3 m, with a 9-pin female D-sub PC connector and an 8-pin mini-DIN PLC connector. Without a PC serial port, add a USB-to-RS-232 converter with its driver installed and select the assigned COM number. Observe the differences between RS-232, RS-422 and RS-485 when selecting Delta PLC programming cables; the module's D+/D− terminals serve a different purpose from the CPU programming port.

CR registers and reading example

CR#1 uses b0–b2 for CH1, b3–b5 for CH2, b6–b8 for CH3 and b9–b11 for CH4; leave b12–b15 reserved. H0010 selects Mode 2 current input for CH2 and Mode 0 voltage input for the other three channels. This word affects all four channel settings.

CR#2–5 set the averaging count for each channel: 1–20, default 10. CR#6–9 contain CH1–CH4 averaged inputs, while CR#12–15 contain instantaneous input readings. CR#30 contains error status and CR#34 the firmware version.

For special-module number 0 only: under a first-scan condition, TO K0 K1 H0010 K1 selects the modes above. Cyclic FROM K0 K6 D100 K4 reads the four averaged values into D100–D103. FROM K0 K30 D200 K1 reads error information. CH2 requires the V+–I+ current-input bridge in this example. On the HMI panel, read raw data as signed 16-bit values and scale them to engineering units according to the selected mode.

CR#18–21 are OFFSET and CR#24–27 are GAIN adjustments, not normal measurement registers. Changing the channel mode can reload standard conversion settings, so do not continuously execute the mode write. Back up existing values before calibration.

RS-485 and process control

Standalone operation supports Modbus RS-485 using ASCII or RTU. RS-485 cannot be used simultaneously with the CPU expansion connection. Standalone PC access requires a USB-to-RS-485 converter with its driver installed. CR#31 sets the address and CR#32 the serial format; the default is 9600 bps, ASCII, 7E1. Check serial-format options against the firmware.

In PID control with a PLC, this module supplies the feedback measurement. Send the calculated PID command to suitable output hardware. DVP04AD-H2 acquires measurements; it does not itself generate an analog command for a valve or drive.

Editor's Note

For a used module, record the complete label, terminal block, CPU model and CR#0 identification first. Do not treat the -H, -H2 and -H3 suffixes as the same device.

If a reading is missing, measure the 24 V supply at the module terminals under load. Then compare channel mode with V+/I+/COM wiring. A missing current bridge can make a healthy module appear faulty.

With control outputs disconnected, test voltage channels using a suitable calibrator at 0, 5 and 10 V. Test current channels at 4, 12 and 20 mA, using the expected values for the selected Mode 2 or Mode 3.

For a Mode 2 channel reading zero at 4 mA, do not identify a broken wire from raw zero alone. Evaluate below-range signals, error status and process behaviour together. Measure current in series and voltage in parallel.

If values jump when contactors operate, inspect shielding, commons, terminals and power-cable routing. Increasing averaging can reduce fluctuations, but it does not remove the interference source and delays response.

Back up OFFSET/GAIN and CR#33 settings before changing them. Do not assume TO-written settings remain stored after power loss. Test initialization when the CPU returns to RUN and output behaviour when a sensor disconnects.

PDF manuals and related topics

Use our Delta DVP PLC files page for wiring, CR tables and conversion curves. Chapter 1 of the special-modules manual covers DVP04AD-H2; do not confuse the adjacent DVP06AD table with this four-channel model. The programming manual provides additional CPU connection and FROM/TO guidance.

DVP -H2 modules · DVP04AD-H · DVP04AD-H3 · DVP04DA-H2 · DVP06XA-H2 · DVP PLC series · Delta PLC · Second-hand Delta equipment

External references

Delta DVP04AD-H2 manufacturer instruction sheet archive · Delta DVP-PLC Special Modules, 2013, chapter 1