Delta DVP48HP00R

Delta DVP48HP00R - 24 Input / 24 Relay Output Extension Unit

Delta DVP48HP00R is a mixed digital extension unit for the DVP-EH family, providing 24 digital inputs and 24 relay outputs with a 100-240 V AC supply. It operates through a compatible host PLC rather than executing its own user program.

Check hardware revision in DVP-EH and DVP-EH2 installations. Delta also lists this exact model among DVP-EH3 digital extensions. Verify the CPU code, extension order and system I/O limit together.

Power supply and inputs

Main supply: 100-240 V AC, -15%/+10% tolerance, 50/60 Hz; consumption 30 VA. Connect mains to L-N. The +24V/24G sensor supply is rated 500 mA; include the inputs and sensors in its load budget. Do not parallel an external power supply with this output.

Inputs: 24 V DC sink/source, nominal 5 mA, approximately 20 ms response. Typical signals include inductive sensors, photoelectric sensors, limit switches and pushbuttons. For PNP wiring, connect S/S to 0 V; for NPN wiring, connect S/S to +24 V. These standard inputs do not replace high-speed counter inputs for fast encoder signals.

Relay outputs and commons

Outputs: 24 relay contacts, up to 250 V AC / 30 V DC, approximately 10 ms response. The detailed terminal table specifies 1.5 A per output and 5 A per common. The same sheet’s selection table states 2 A; because these figures differ, use the detailed rating and the applicable hardware revision when sizing loads. Assess inductive loads and inrush separately.

Common groups: C0: Y0-Y3; C1: Y4-Y7; C2: Y10-Y13; C3: Y14-Y17; C4: Y20-Y27. The last eight-output group still has a 5 A total limit. Relay contacts do not generate a 24 V supply; provide the load supply at the appropriate common. Use suitable suppression for contactor coils and suitable circuit protection.

Addressing, software and programming cable

X/Y addresses are octal: X10 follows X7. X0-X27 / Y0-Y27 on the unit are local terminal labels. For example, the first 24/24 extension after a compatible 16-input/16-output EH CPU may occupy X20-X47 and Y20-Y47. Confirm the actual allocation against preceding modules and the CPU manual.

Which software? Read the inputs and drive the outputs in the host CPU program using WPLSoft or ISPSoft where supported by that CPU generation and version. Delta documents both tools for EH3. Configure COMMGR and the appropriate communication driver for ISPSoft. DVP48HP00R has no separate user program or independent Modbus station setting.

Which cable? Connect the computer to the host CPU. For example, the EH3 COM1 RS-232 connection supports the UC-PRG020-12A USB programming cable or a UC-MS020-01A serial cable. Check the USB-serial driver and assigned COM port. Select the Delta PLC cable for the CPU port and pinout; the extension connector is not a computer interface.

Related models and selection differences

DVP48HP00T provides the same 24/24 point count with transistor outputs. DVP32HP00R has 16 inputs/16 relay outputs, DVP16HP11R has 8/8, and DVP08HP11R has 4/4. DVP32HN00R provides 32 outputs. These are selection alternatives requiring a fresh power, terminal and addressing review.

Editor’s Note

For used equipment, request a clear label photo showing DVP48HP00R. Establish the HP/EH and R/T distinctions from the actual unit.

A clicking relay does not prove that its contacts are healthy. Test every output with a controlled load and check that it opens again when its command is removed.

If a whole group fails, inspect its common supply, terminals and protection first. A single failed channel calls for a closer check of that contact and its drive circuit.

For input testing, isolate the field sensor and apply a suitable 24 V test signal. Compare the terminal LED with the CPU address to separate wiring, mapping and module faults.

Before replacing a damaged relay, find the cause of overheating or welded contacts. Check grounding, coil suppression and the 24 V power supply as part of the repair.

Back up the CPU program and photograph the terminals and extension order before removal. Perform the first test with machine movement prevented and controlled test loads.

PDF files and related topics

Find manuals and catalogues on our Delta DVP PLC files page. Related topics include optocouplers in input circuits and fuses for output protection.

Navigation: DVP48HP00R main page · DVP extension modules · Delta PLC · Used Delta equipment · Used digital input modules.

External references

DVP-EH DIDO installation and wiring sheet - legacy 2008 edition · Delta DVP/TP catalogue - EH3 extension models · Delta PLC/HMI cable selection guide - host CPU connection

DVP-PLC Application Manual: Programming - EN