Delta DVP32HP00R

Delta DVP32HP00R – 16 Digital Inputs and 16 Relay Outputs

Delta DVP32HP00R is a 32-point mixed digital expansion unit with 16 inputs and 16 relay outputs for the DVP-EH family. It operates under a host PLC CPU and does not run an independent user program. Delta also lists it in the DVP-EH3 catalogue. Its unit supply is 100–240 V AC; its input signals are 24 V DC.

In automation systems, it adds field sensor, pushbutton and limit-switch inputs, together with outputs for suitable lamps, relays or contactor coils. The R suffix identifies relay outputs. The DVP32HP00T uses transistor outputs; changing between them requires a wiring and load review.

Power supply and digital input wiring

Unit supply: 100–240 V AC, 50/60 Hz, with −15%/+10% voltage tolerance and 30 VA consumption in the instruction sheet. Connect mains to L/N. Do not apply mains voltage to X inputs or the +24 V/24G terminals. Switch the host CPU and AC-powered expansion unit on and off together. When using an external power supply or DIN rail power supply, check the common reference and existing auxiliary supply arrangement; do not parallel supply outputs without an approved arrangement.

Inputs: 16 sink/source DC inputs, nominally 24 V DC and 5 mA. The specified ON threshold is above 16.5 V, the OFF threshold below 8 V, and response time approximately 20 ms. Review PNP versus NPN and sink/source wiring together with the S/S common terminal. A PNP sensor generally requires S/S at 0 V; an NPN sensor generally requires S/S at +24 V. Confirm the actual group diagram before connection.

For inductive sensors, photoelectric sensors and capacitive sensors, verify the supply, switching output and leakage current rather than relying on wire colours alone. These are ordinary digital inputs; do not assume they provide a high-speed encoder counter function. Use a suitable CPU input or dedicated counter module for short pulses.

Relay outputs and load limits

The 16 relay outputs switch an externally powered load circuit; the contacts do not generate load voltage. The sheet specifies 250 V AC/30 V DC voltage limits and approximately 10 ms relay response. Although its selection table says 2 A per point, the detailed resistive-load table specifies 1.5 A per point and 5 A per COM. Base load calculations on the detailed table and actual hardware revision. Do not interpret the selection figure as permission to load every output at 2 A simultaneously.

Inductive loads require a separate review of inrush, switching frequency and contact life. Fit suitable suppression and fuses when switching a contactor coil or solenoid. Select a DC flyback diode or an appropriate AC RC/varistor network according to the load manufacturer's instructions. A suitable interposing relay and socket can simplify maintenance where larger loads are involved. Mechanical relay outputs are unsuitable for servo pulse trains or PWM. When commanding a variable frequency drive, check the requirements of its digital control input.

Host compatibility, software and programming cable

DVP32HP00R belongs to the DVP-EH expansion module family. For DVP-EH2 and DVP-EH3 installations, check the exact CPU, expansion sequence and permitted I/O capacity. The DVP name alone does not establish compatibility with every PLC or with a slim S-series expansion chain.

Edit the host program using WPLSoft or an ISPSoft version supporting the selected CPU. No separate user program is downloaded into DVP32HP00R. COMMGR may be used for the CPU connection with ISPSoft. Select the correct CPU and software release; the expansion unit's model number does not establish firmware or operating-system support.

The programming cable connects to the host CPU. Delta's catalogue lists UC-PRG020-12A, DB9 female to 8-pin mini-DIN male, for suitable DVP RS-232 ports. DVPACAB2A30 is also encountered in older DVP installations; verify the actual CPU port and pinout. A PC without a serial port requires a suitable USB-to-RS-232 converter, its driver and the correct COM setting. The unit's expansion ribbon is separate from the PLC programming cable.

X/Y addressing and commissioning

The module uses the CPU's X input and Y output addresses; ordinary digital operation does not require analogue-module FROM/TO register access. Delta X/Y numbering is octal: X10 follows X7. The starting address depends on the CPU's built-in I/O and preceding expansion units.

Example: with a DVP32EH host having 16 inputs at X0–X17 and 16 outputs at Y0–Y17, the first DVP32HP00R occupies X20–X37 and Y20–Y37 in the manual's example. Do not copy this range into another module arrangement. A bench-test relationship such as LD X20 / OUT Y20 is only appropriate after confirming those physical addresses. Disconnect field loads before forcing machine outputs.

Compare an HMI or SCADA command with the actual contact state. An active Y bit does not prove that load power, the relevant COM group or the contact is healthy. Include terminal layout, ventilation and signal/power cable separation when choosing panel components. Approximate dimensions are 143.5 × 90 × 82.2 mm (width × height × depth), with 35 mm DIN rail or screw mounting and a 0–55 °C operating range.

Editor's Note

Start a used-unit inspection with the full label and terminals. DVP32HP00R and DVP32HP00T may look similar, but their output circuits differ. Photograph the wiring and COM groups before removing anything.

A clicking relay or illuminated LED does not prove a healthy output. Test each channel with a known, low-power load, then check voltage drop and heating within the intended operating limits.

Look for welded contacts, discoloured terminals and loose connections. Isolate load power before continuity measurements. Increasing a fuse rating is not a repair.

Test the inputs individually. An incorrect S/S connection can make a working sensor appear faulty; measure the sensor output first, followed by the input terminal.

If a whole output group fails, check its COM supply, field fuse and expansion connection before replacing the board. Back up the host program and record the existing addresses before changing module order.

Do not insert or remove the module while powered. Mains-side repairs, insulation checks and load tests belong on a suitable bench with qualified personnel. Test every channel before declaring the complete unit serviceable.

PDF documents and related models

Use our Delta DVP PLC PDF files page for wiring diagrams and technical documents. References for this description are the manufacturer's DVP-EH DIDO HD02 sheet dated 15 August 2013 and DVP/TP catalogue dated 3 January 2023. The original English/Chinese PDF content is preserved.

Related topics: DVP48HP00R · DVP32HN00R · DVP32HM11N · DVP16HP11R · DVP08HP11R · DVP08HP11T · DVP08HN11R · DVP08HN11T · DVP08HM11N · DVP16HM11N · DVP16HP11T. These links compare different I/O requirements; they are not a list of interchangeable replacements.

Navigation: DVP32HP00R main page · Delta PLC · Delta DVP PLC series · Delta PLC and HMI manuals · Second-hand Delta products · What is a PLC?.

External references

Delta DVP-EH DIDO HD02 – original manufacturer document hosted by a distributor · Delta DVP/TP manufacturer catalogue.