Delta DVP -H2 modules
Delta DVP -H2 modules
Delta DVP -H2 modules add analog measurement and control, temperature inputs, positioning, high-speed counting and fieldbus communication to DVP-EH2 PLC systems. When replacing a card in an existing machine, match the full module code, CPU model and field signal. For the basics, see what a PLC does and how PLC input and output modules work.
Compare the 11 modules
Select a model code to open the dedicated device page and its specifications.
| Model | Channels and function |
|---|---|
| DVP04AD-H2 | 4 analog inputs, voltage or current |
| DVP04DA-H2 | 4 analog outputs, voltage or current |
| DVP06XA-H2 | 4 analog inputs + 2 analog outputs |
| DVP04PT-H2 | 4 RTD inputs, Pt100 and other RTD types depending on revision |
| DVP04TC-H2 | 4 thermocouple inputs |
| DVP08TC-H2 | 8 thermocouple inputs, J/K/R/S/T/E/N |
| DVP01PU-H2 | Single-axis positioning, pulse output |
| DVP01HC-H2 | Single-channel high-speed counter, encoder input |
| DVPPF02-H2 | PROFIBUS DP slave, up to 12 Mbit/s |
| DVPCP02-H2 | CANopen slave, up to 1 Mbit/s |
| DVPDT02-H2 | DeviceNet slave, up to 500 kbit/s |
Choose by field signal
AD measures, DA sends an analog command, and XA does both. A 4–20 mA pressure transmitter needs a current input. A drive that accepts a 0–10 V speed reference needs a voltage output. When both are needed, plan the DVP06XA-H2’s four inputs and two outputs separately. Match the channel mode, terminal and raw-value scaling in the program. See analog and digital input differences.
Read the temperature sensor type on the label. Use the DVP04PT-H2 for a Pt100 and a four- or eight-channel TC module for a thermocouple. Verify the channel’s sensor selection, polarity and extension cable. Pt100 and thermocouple comparison · Thermocouple standards · Thermocouple types.
PU sends pulses to a drive. HC counts pulses from an encoder. The DVP01PU-H2 can generate up to 200,000 pulses per second for one axis. The DVP01HC-H2 can accept a counting signal of up to 200 kHz, depending on the wiring and count mode. Check the drive’s pulse/direction interface and the encoder’s supply and output type. Servo basics · PLC high-speed pulse output · Incremental encoders · Line driver encoders.
Check the fieldbus master project. For PROFIBUS DP, verify the GSD file for DVPPF02-H2. For CANopen and DeviceNet, verify the EDS file for the exact module. Match the node address, network speed, termination and I/O data length to the existing project. Industrial communications · CANopen · DeviceNet · SCADA.
CPU compatibility, FROM/TO and programming cable
DVP-EH2 is the host PLC. -H2 units are expansion modules. Delta’s programming manual lists H2 module IDs for DVP-EH3. For the DVPPF02-H2, DVPCP02-H2 and DVPDT02-H2, Delta’s general catalogue lists EH2/EH3. The individual product pages specify EH2 only. Confirm support for the exact CPU and module revisions before moving to EH3. When comparing -H and -H3 cards, check the terminal diagram, module ID and CR table.
CR means control register. On modules that support these instructions, FROM reads a register and TO writes one. For a DVP04AD-H2 installed as the first special module, FROM K0 K0 D100 K1 reads module 0’s CR#0 ID into D100. The expected value is H6400. Use the physical module order for the module number and check the model’s CR table for channel modes and writable registers. PLC programming · Ladder diagrams.
Connect to the CPU project with WPLSoft or a compatible version of ISPSoft. Select the ISPSoft communication channel in COMMGR. The standard EH2 COM1 RS-232, 8-pin mini-DIN port can use DVPACAB230 (3 m) or DVPACAB215 (1.5 m). For a USB-equipped PC, add a suitable USB-to-RS-232 adapter to the serial cable. Check fieldbus settings in the relevant master software.
Editor’s Note
Get a clear nameplate photo. Check the suffix, side connector, terminals and latch on used modules. Switch off power and record the module order before removal.
Test an analog channel with a known value. Use an appropriate calibrator for the current input and a suitable test load for the selected output mode. Compare the PLC’s raw value with the field measurement.
Check the sensor type first if the temperature is wrong. A J sensor configured as K, reversed polarity or the wrong extension cable can shift the reading. Check the two- or three-wire RTD diagram for the installed module.
Test PU and HC separately. Measure the PU command pulse with drive motion disabled. Feed the HC a known pulse signal and check the count and direction. Review electromagnetic interference and panel grounding if readings are unstable.
Keep a backup of the fieldbus project. Save the node address, device description file and I/O map. Confirm that the master exchanges data after the card is replaced.
Related topics and OtomasyonAVM PDF archive
Delta DVP expansion modules · Delta DVP PLC series · Delta PLC main category · Second-hand Delta products.
Delta DVP PLC files · DVP-EH2 wiring and installation sheet (PDF).
External references
Delta special modules manual · DVP08TC-H2 instruction sheet · PROFIBUS DP manual · Delta fieldbus catalogue · CANopen product page · DeviceNet product page.