Delta DVP01PU-H2
Delta DVP01PU-H2 Single-Axis Positioning Module
The Delta DVP01PU-H2 is a single-axis positioning module with pulse output up to 200 kHz, connected to a compatible DVP PLC main unit. It generates position and speed commands for pulse-input servo systems and stepper drives. The external drive supplies and controls the motor.
Use our Delta DVP PLC files page for wiring diagrams and register information. The -H2 suffix matters: do not assume identical CPU compatibility or register arrangements for DVP01PU-H. The DVP01HC-H2 is a high-speed counter, rather than an equivalent pulse-output module.
Pulse outputs and operating modes
FP+/FP− and RP+/RP− are 5 V differential line-driver outputs. Select FP/RP (CW/CCW), pulse + direction or A/B phase output. Both terminal pairs serve one axis. Match the selected format and electrical interface to the drive's pulse input.
Parameters support single-speed and two-speed positioning, interrupt positioning, variable speed, JOG, homing and manual pulse generator operation. Acceleration curves and acceleration/deceleration times can be configured. Connecting multiple independent modules does not by itself provide coordinated multi-axis interpolation.
Distance, speed and electronic gearing
Position values use 32-bit data, expressed in pulses or the selected machine unit. Parameter A represents command pulses per motor revolution; B represents mechanical travel per revolution. Electronic gearing in the drive means A need not equal the motor encoder's nameplate resolution.
For example, 2000 command pulses/revolution with 5 mm travel/revolution requires 4000 pulses for 10 mm travel. This is a calculation example only. Include the actual gearbox ratio, screw lead and coupling arrangement. The module's CP value represents command-pulse-based position; it does not independently prove physical axis position. Assess any separate linear measurement system accordingly.
START, STOP, limits, DOG and PG0 wiring
START initiates operation, STOP stops it, LSP/LSN provide travel limits, and DOG serves as a homing approach or interrupt input according to the mode. Wire these inputs through S/S using the specified sink/source arrangement. Check output type, voltage and input polarity when selecting limit switches, inductive sensors or photoelectric sensors.
ΦA+/ΦA− and ΦB+/ΦB− accept manual pulse generator inputs up to 200 kHz. PG0+/PG0− accepts the zero/index signal used in homing. Check the specified 5–24 V DC interface conditions for A/B and PG0. Do not treat PG0 as another A/B high-frequency input.
CLR+/CLR− clears the servo drive's error counter. It is an NPN open-collector output, specified for 5–24 V DC and less than 20 mA. Do not use it to power a motor brake or power coil. The module's STOP input must not replace an independent emergency-stop circuit.
CPU compatibility and supply
The instruction sheet specifies the DVP-EH2 main unit; Delta's DVP-EH3 catalogue table also lists DVP01PU-H2. Match DVP -H2 modules to the exact CPU and hardware generation. The EH2 sheet specifies a total of eight special extension modules, including other installed modules. Eight independent axes require eight PU modules.
The supply is 24 V DC, with a 20.4–28.8 V DC tolerance range. The H2 sheet's general specifications table gives 140 ± 30 mA consumption. Include the other modules when sizing a power supply or DIN rail supply. Provide appropriate fuse protection and separate pulse wiring from contactor, relay and motor power circuits. Control panel layout and shielding affect pulse reliability.
Programming software and cable
No separate PLC application is downloaded to this module. Program the host CPU using its supported WPLSoft or ISPSoft. Exchange parameters and status through FROM/TO, using appropriate DFROM/DTO instructions for 32-bit values. Configure COMMGR for the CPU port when connecting through ISPSoft.
A compatible DVP CPU's RS232 programming port can use DVPACAB2A30. If the PC lacks RS232, use a suitable USB-to-RS232 converter, its driver and the correct COM port. Connect the Delta PLC cable to the CPU. A PLC programming cable and the shielded differential pulse cable between the module and servo drive perform different duties. Verify the servo cable pinout against the actual drive model.
Control registers and 32-bit transfers
The module contains 54 sixteen-bit registers, CR#0–CR#53. CR#0 = H6110 identifies the model. CR#1–CR#2 hold A, CR#3–CR#4 hold B, and CR#5 selects units, pulse format and input polarities. CR#21/CR#22 set acceleration/deceleration times.
CR#23–CR#24 hold the first target position and CR#25–CR#26 its operating speed. CR#31 contains operation commands, CR#32 the operating mode, CR#33–CR#34 CP position in pulses, and CR#35–CR#36 speed in pulses/second. CR#43 reports execution status, CR#44 errors, CR#52 terminal status and CR#53 firmware.
For a module at K0, FROM K0 K0 D90 K1 reads the model ID. DFROM K0 K33 D100 K1 reads CR#33–CR#34 into D100–D101 as one 32-bit value. FROM K0 K44 D120 K1 reads the error code. DTO K0 K23 D200 K1 writes D200–D201 to the target-position pair; it does not by itself initiate movement.
For these double-word transfers, K1 represents one two-word value. Preserve low/high-word order and signed-number interpretation. Displaying only the low word on an HMI panel or SCADA screen causes incorrect readings, particularly for positions above 32767.
RS485 access and parameter retention
Independent RS485 access supports Modbus ASCII/RTU. The manufacturer instructs users to disconnect the module from the CPU before using RS485; do not assume simultaneous expansion-bus and independent serial access. A CR number is not its Modbus register address.
The sheet explains that writing latched registers through CPU TO/DTO instructions does not make those settings retentive. Implement controlled initialization in the CPU program, back up parameters and verify behaviour through a power cycle.
Editor's Note
Check the complete -H2 label and terminal set on a used module. Establish the exact host CPU before accepting a module merely because its connector fits.
Make the axis safe before initial tests and start at low JOG speed. Verify direction and both travel limits before performing a homing operation.
If FP/RP LEDs operate but the motor does not move, check servo enable, pulse-input mode, differential wiring and electronic gearing before condemning the module.
A basic multimeter cannot adequately assess pulse quality. Use a suitable differential measurement method; do not short a pulse-minus terminal through an earth-referenced oscilloscope ground clip.
Distinguish DOG from PG0 when troubleshooting homing. An increasing position display does not prove correct mechanical travel; check couplings, backlash and lost pulses.
CR#44 code H0030 indicates low supply; H0020/H0021 indicate inhibited directional pulse output. Check supply and limit/polarity settings first. Back up parameters before any factory reset.
Related topics and files
Delta DVP PLC series · DVP -H2 modules · DVP expansion modules · Delta DVP PLC manuals and PDF files.
External references
Delta DVP01PU-H2 instruction sheet, manufacturer download page · Delta DVP-EH2 expansion information · Delta DVP catalogue, EH3 module table.