Delta DVP01HC-H2
Delta DVP01HC-H2 Single-Channel High-Speed Counter Module
Delta DVP01HC-H2 is a single-channel hardware high-speed counter for DVP-EH2 and compatible EH3 PLC systems. It counts pulses from an encoder or suitable pulse source for length, position, revolution and production-count applications. A and B belong to the same counting channel; they are not two independent counters.
CPU compatibility and module function
The 2007 module sheet describes DVP-EH2 operation. Delta’s 2023 DVP catalogue also lists DVP01HC-H2 among DVP-EH3 expansion modules. Do not infer compatibility with other DVP CPU families from the H2 suffix alone. Check the exact CPU, expansion interface and software support. The module does not run a separate PLC user program; its hardware performs the configured counting and comparison functions.
Counting modes and frequency limits
The module supports A/B quadrature counting, separate forward/reverse pulses and pulse/direction operation. A/B input limits are 200 kHz at ×1, 100 kHz at ×2 and 50 kHz at ×4. Single-phase one-input or two-input modes are specified at 200 kHz. The headline 200 kHz rating therefore does not mean the same encoder frequency is accepted at every multiplier.
If PPR means A-phase periods per revolution, input frequency = PPR × rpm ÷ 60. At 1000 PPR and 3000 rpm, A phase is 50 kHz and ×4 evaluation produces 200,000 counts/s. This reaches the ×4 input limit; allow operating margin when selecting equipment. The manufacturer specifies a maximum 0.8 µs rise/fall time and minimum 2.5 µs ON/OFF pulse durations.
Input levels and encoder cable
A/B inputs provide separate terminals for 5 V, 12 V or 24 V: A5+/A12+/A24+ and B5+/B12+/B24+. Select only the correct voltage terminal for each signal; do not bridge these terminals together. Match the encoder output type and NPN/PNP wiring polarity. Never apply a 24 V signal to a 5 V input.
A TTL/HTL label or line-driver designation alone does not establish the correct connection; match signal levels, output circuitry and the module wiring diagram. The module counts pulses and does not directly decode an absolute encoder’s serial position word. For a linear encoder with suitable incremental pulse outputs, verify its output interface as well.
PRESET loads the preset value and DISABLE stops counting. Both require a minimum 50 µs pulse width. If using an encoder Z pulse for PRESET, check this condition and the enable setting. Route shielded signal cable away from motor/power wiring, considering electromagnetic interference and grounding together.
Power supply and YH0/YH1 comparison outputs
The module requires external 24 V DC; the manufacturer label states 3 W. The CPU expansion connection does not replace this supply. Measure DC voltage at the module, especially during startup. YH0 and YH1 are two hardware comparison outputs that operate at configured counts. They are transistor outputs, with a specified load rating of 5–30 V DC, 0.5 A.
YH0+/YH1+ are collectors and YH0−/YH1− are emitters; observe polarity. Comparison occurs as an input pulse changes the count. Loading the comparison value through PRESET or a register write does not necessarily activate an output. Configure output enable, latching and reset behaviour through CR#4.
Programming software and programming cable
PLC programming is performed through the host CPU using WPLSoft or a supported release of ISPSoft, according to the CPU model. The ladder program accesses module registers with FROM/TO and DFROM/DTO for 32-bit transfers where required. Configure COMMGR when needed for an ISPSoft connection.
For a CPU with an 8-pin mini-DIN RS-232 port, use a UC-PRG020-12A USB-to-RS-232 programming cable, or a UC-MS020-01A serial cable and suitable USB-to-RS-232 converter. Verify the exact CPU port, cable driver and COM number. The programming cable connects to the CPU; encoder wiring connects to the module’s A/B/PRESET inputs.
Control registers and reading a 32-bit count
CR#0 is model ID H’6120; CR#4 controls enable/functions; CR#5 selects the counting mode; CR#10–#11 hold the preset; CR#12–#13 the YH0 comparison value; CR#14–#15 the YH1 comparison value; and CR#20–#21 the current count. CR#29 reports errors and CR#30 firmware. A 32-bit value occupies two consecutive 16-bit registers; reading one register does not retrieve the complete count.
If the module is genuinely the first special module, DFROM K0 K20 D100 K1 reads CR#20–#21 into D100–D101. Evaluate D100 as the low word and D101 as the high word; K1 here means one 32-bit transfer. Change K0 to the actual special-module index. Special modules are indexed 0–7 from the closest to the CPU; this is not a digital X/Y address.
Disable counting before changing the mode in CR#5. A mode change can initialise count, preset and comparison registers. In 16-bit ring mode, CR#2–#3 define the ring length: a length of 200 gives counts 0–199. The signed 32-bit counting range is −2,147,483,648…+2,147,483,647.
RS-485 and Modbus access
For the module’s RS-485, Modbus ASCII and Modbus RTU access, CR#31 sets the address and CR#32 the communication format. The 2007 sheet lists 4800–57,600 bit/s options. Serial communication speed differs from the 200 kHz counter input rating. Hardware counts the pulses; communication retrieves count and status registers. Do not confuse CR numbers with Modbus parameter addresses.
Editor’s Note
Seeing the A and B indicators light is only a partial test of a used module. Apply a known number of pulses, then test both directions. Confusing ×1, ×2 and ×4 can make a healthy unit appear to count incorrectly.
Verify operation at low frequency before approaching the application’s real speed. If counts are lost at higher speeds, check amplitude, pulse width and edges at the module terminals with an oscilloscope. A clean signal at the source may deteriorate over a long cable.
Test PRESET and DISABLE separately. When counting stops, inspect the DIS state and CR#4 before assuming an input failure. If the count must survive power loss, define the retention or backup strategy explicitly in the project.
Test YH0 and YH1 individually with a suitable low-power DC load. Check output polarity and protection components. Do not test only by writing the threshold; verify comparison during actual pulse counting.
For machines stopped according to a count, provide the appropriate emergency-stop and safety-relay arrangement. Working communication or a switching YH output alone does not establish a safety-rated stop function.
During repair, inspect input protection, optocoupler circuitry, terminal solder joints and the external supply path. Find the cause of damage, such as 24 V applied to a 5 V input, before replacing parts. Retest PRESET, DISABLE and both comparison outputs as well as the counting inputs.
PDF files
Use our Delta DVP PLC files page for documentation. The 2007 DVP01HC-H2 sheet covers wiring, mode selection and the CR map; the 2023 DVP catalogue lists its place in the EH3 family. Also consult the cable selection guide for CPU connections.
Related topics and navigation
DVP01PU-H2 performs single-axis positioning/pulse output, while DVP01HC-H2 counts incoming pulses. When replacing the older DVP01HC-H, check the CPU generation and model identifier. Related groups are DVP H2 modules and DVP expansion modules.
Delta main page | Delta PLC | DVP PLC series | DVP-EH2 | DVP H2 modules | DVP01HC-H2 models