Delta DVP01HC-H is a single-channel high-speed counter module from the original -H generation for the DVP-EH family. It counts signals from an encoder or a suitable pulse source in PLC applications. A and B are inputs for the same counting channel, not two independent counters. Two hardware comparison outputs, YH0 and YH1, provide separate thresholds.
The high-speed counter is used for measuring-wheel length tracking, position monitoring and product counting. Scale the incremental encoder's pulses per revolution together with the selected ×1/×2/×4 mode. Unlike the DVP01PU-H pulse output module, this device receives and counts pulses.
Counting modes and frequency limits
Pulse plus direction and separate up/down pulse modes support up to 200 kHz. For A/B phase inputs, the limits are ×1: 200 kHz, ×2: 100 kHz and ×4: 50 kHz. Check the selected mode when assessing frequency; selecting ×4 does not permit a 200 kHz input.
Select 16-bit ring counting or signed 32-bit counting. The 32-bit range is −2,147,483,648…+2,147,483,647. For example, a 1000-pulse/revolution encoder produces 4000 counts per revolution in A/B ×4 mode. With an inductive sensor or photoelectric sensor, switching speed and pulse quality must also be adequate; the module's rating does not increase the sensor's speed.
Inputs, power supply and output wiring
The module requires 24 V DC, with a permitted range of 20.4–28.8 V DC. Size the DIN rail power supply for the encoder and other loads too. A/B terminals are A24+/B24+ for 24 V, A12+/B12+ for 12 V and A5+/B5+ for 5 V, with A− and B− returns. Select only one suitable voltage-level terminal for each signal; do not bridge the 5/12/24 V terminals.
PRESET uses P24+ (12–24 V) or P5+ (5 V); DISABLE uses D24+ (12–24 V) or D5+ (5 V), with PRE− and DIS− returns. Identify the encoder output type and follow the manufacturer's PNP/NPN wiring diagram. Do not assume a line-driver encoder is directly compatible merely because its connector or voltage appears similar.
YH0/YH1 are transistor outputs rated 5–30 V DC, 0.5 A. The “+” terminal is the collector and “−” the emitter; these are neither relay contacts nor differential line-driver outputs. Comparison outputs must also be enabled. Cable shielding and grounding are particularly important on long encoder runs.
CPU compatibility and module addressing
DVP01HC-H and DVP01HC-H2 are different generations. The original -H CR#0 identification code is H0120, while H2 uses H6120. DVP02HC-H has two channels and a different CR map. Before moving to EH3 or another CPU, verify support for the complete module code rather than relying on physical fit.
Special expansion modules connected to the CPU are numbered 0–7 by their distance from it; intervening digital I/O modules do not count toward this number. DVP01HC-H occupies no standard X/Y points. The module number in FROM/TO instructions must match the actual arrangement.
Programming software and cable
Configure and read the module through the connected CPU's ladder program. Use a version of WPLSoft or ISPSoft supporting that CPU; COMMGR manages the communication channel for ISPSoft. The module does not use a separate USB programming cable.
For the DVP-EH CPU's COM1 RS-232 port, use the DVPACAB2A30 programming cable: approximately 3 m, with a 9-pin female D-sub PC connector and an 8-pin mini-DIN PLC connector. Without a PC serial port, add a USB-to-RS-232 converter with its driver installed and select the assigned COM number. Observe the differences between RS-232, RS-422 and RS-485 when selecting Delta programming cables.
CR registers and 32-bit reading example
In the CR#4 control word, b0 enables counting, b1 enables YH0, b2 enables YH1 and b4 enables PRESET. CR#5 selects the counting mode. CR#10–11 hold the preset, CR#12–13 the YH0 threshold, CR#14–15 the YH1 threshold and CR#20–21 the current count. The first register in each pair is the low word. CR#29 contains errors and CR#30 the firmware version.
Counting example for special-module number 0 only: under a first-scan condition, disable counting with TO K0 K4 K0 K1, then select 32-bit A/B ×1 with TO K0 K5 K0 K1. Under an appropriate start condition, TO K0 K4 K1 K1 enables counting. This control-word example leaves both threshold outputs and PRESET disabled. It writes the entire control word, so design any other required bits separately.
Cyclic DFROM K0 K20 D100 K1 reads the 32-bit count into D100–D101. FROM K0 K29 D200 K1 reads error information into D200. Display the pair as a signed 32-bit value on the HMI panel. Clear CR#4 b0 before changing mode. Since writing the mode can reinitialize some registers, load presets and thresholds after mode selection.
RS-485 and motion applications
In standalone use, the module supports Modbus RS-485 with ASCII or RTU. RS-485 cannot be used simultaneously with the CPU expansion connection. Standalone PC access requires a USB-to-RS-485 converter with its driver installed. CR#31 sets the address and CR#32 the serial configuration.
In servo or stepper motor mechanisms, encoder feedback measures motion; this module is not itself a servo drive. Design home referencing and limit switch functions together with the machine's reference and travel-limit logic.
Editor's Note
For a used module, inspect the complete label and terminal block first. Do not treat -H and -H2 as identical. Record the CPU model, module order and CR#0 identification.
Perform initial tests with drive outputs safely disconnected. Measure the supply at the terminals under load, then turn the encoder slowly in both directions to check direction and counts per revolution.
A fourfold result in ×4 mode is not automatically a fault; check scaling first. If counts are lost or direction changes unexpectedly, inspect A/B wiring, selected mode and pulse waveforms with an oscilloscope.
Do not test a threshold output merely by writing a count value. According to the manual, comparison operates when an actual count change reaches equality; loading a preset equal to the threshold does not itself trigger the output. Test output enabling and reset logic too.
If extra counts appear when contactors operate, first inspect shielding, commons, cable routing and supply dips. Replacing the module may not solve worn terminals or an incorrect voltage-level connection.
Back up mode, preset, threshold and serial settings before changing them. Saving the PLC project does not guarantee that every current module register value is also preserved. Verify initialization and output behaviour after power restoration.
PDF manuals and related topics
Use our Delta DVP PLC files page for wiring diagrams and CR tables. Chapter 7 of the special-modules manual covers DVP01HC-H and DVP02HC-H together; use the table specifically headed DVP01HC-H. Both archived manufacturer manuals are in English.
DVP -H modules · DVP01HC-H2 · DVP02HC-H · DVP expansion modules · DVP PLC series · Delta PLC · Second-hand Delta equipment
External references
Delta DVP-PLC Special Modules, 2013, chapter 7 · Delta DVP-PLC Programming manufacturer manual download page