Delta DVPPF02-H2
Delta DVPPF02-H2 PROFIBUS DP Slave Communication Module
The Delta DVPPF02-H2 connects a compatible DVP main unit to a PROFIBUS DP network as a slave station. It is neither a standalone PLC nor a PROFIBUS master. It supports DPV0 cyclic data exchange, automatic baud-rate detection and communication up to 12 Mbit/s.
Use our Delta DVP PLC files page for the application manual, wiring and register information. Commissioning involves the CPU program, master network configuration and correct GSD file together; connecting the cable alone does not establish application data exchange.
CPU compatibility and power supply
The original manufacturer's manual describes DVPPF02-H2 for DVP-EH2. Delta's 2023 DVP catalogue also lists it under DVP-EH3 extension modules. Check the exact CPU model, firmware and supported DVP -H2 module arrangement rather than extending this compatibility to every DVP series.
The module connects to the CPU's right-side expansion bus and receives power from the main unit; a separate external supply is not connected to DVPPF02-H2. Consider the CPU's power supply, DIN rail supply arrangement and total expansion load together. Do not apply 24 V to the PROFIBUS connector.
GSD file, four slots and data capacity
The application manual specifies equipment ID 0AFE hexadecimal and device-description file DELT0AFE.GSD. Install this file in the PROFIBUS master's network configuration software. Delta GSD device-description files are not CPU programs or firmware. A GSD file is distinct from the GSDML files used for PROFINET.
The master configuration supports four logical slots. Across those four slots, the maximum is 100 input words and 100 output words, equivalent to 200 bytes in each direction. This is not a separate 100-word allowance for every slot. Input and output directions are defined from the PROFIBUS master's perspective.
Slot order and data length on the master must match the data areas used in the Delta CPU program. Correct display on an HMI panel or in SCADA also requires the proper word order, byte order, sign and scaling. A green NET indicator alone does not prove that every application value is correctly mapped.
Which programming and configuration software is used?
Create the Delta CPU program in a CPU-compatible version of WPLSoft or ISPSoft. Configure the COMMGR connection when using ISPSoft. Configure the PROFIBUS network using the master's engineering software; the manufacturer's application manual includes a Siemens STEP 7 / HW Config example. GSD installation, station address and slot selection belong to the master project.
For a suitable Delta CPU's RS232 programming port, use DVPACAB2A30 and, where required, a suitable USB-to-RS232 converter with its driver installed. Select the Delta PLC programming cable for the CPU's actual port. This connection is separate from the module's PROFIBUS DB9 field connection; identical connector shapes do not establish identical electrical interfaces.
DFROM/DTO instructions and data direction
Use DFROM/DTO rather than FROM/TO for this model. These are 32-bit instructions: a transfer quantity of K1 moves two 16-bit control registers. The special-module number follows its position relative to the CPU; K0 in the examples represents the first special module.
CR#3–CR#102 hold data sent from the Delta CPU to the PROFIBUS master; the CPU writes this area using DTO. CR#103–CR#202 hold data received from the master; the CPU reads this area using DFROM. The master's input area receives Delta data, while its output area sends data to Delta.
For a module at K0, DTO K0 K3 D100 K1 writes D100 and D101 to CR#3 and CR#4. DFROM K0 K103 D200 K1 reads CR#103 and CR#104 into D200 and D201. These examples transfer two words. Match the master's slot lengths and the actual module number before use.
CR#0 = H0250 identifies the model; CR#1 contains firmware version; CR#2 reports I/O data length; CR#251 reports errors. Do not write to system-reserved areas. An industrial communication data map should record each address, direction and engineering unit for later troubleshooting.
PROFIBUS cable and DB9 pin assignment
Use PROFIBUS DP-rated shielded twisted-pair cable and a standard DP connector. The principal pins are 3 = P/B, 8 = N/A, 5 = DGND and 6 = VP. VP is the defined connector supply reference and must not be treated as an external 24 V input. An RS485 physical layer does not make this a Modbus RS485 port.
Terminate the two physical ends of each segment according to the DP connector instructions. The manual specifies 100 m at 12 Mbit/s, 200 m at 1.5 Mbit/s, 400 m at 500 kbit/s and up to 1200 m at lower rates under the specified conditions. Maximum distance and maximum speed do not apply simultaneously.
Route the cable appropriately away from variable frequency drive, contactor and relay load wiring. Review control panel components, shield connections and appropriate CPU supply fuse protection together. Our PROFIBUS questions and answers provide further background.
Station address and field data
The two rotary switches select a hexadecimal station address. Valid settings are 01–7D hex, or 1–125 decimal. Decimal address 26 therefore requires switch digits 1 and A. Set the address with power isolated and restart the module; changing the switches during operation does not apply a new address. Avoid duplicate addresses on the same network.
Inductive sensor and photoelectric sensor states can be collected through suitable CPU inputs and transferred as bits. Analog signals, such as a pressure sensor measurement, must first be digitized by a suitable measurement module. A 0–10 V / 4–20 mA signal cannot connect directly to the PROFIBUS DB9 pins. DVPPF02-H2 transports data and does not perform analog measurement.
Editor's Note
Confirm the complete module code, CPU model and existing master project before buying a used unit. Back up the working GSD file, slot arrangement and Delta program together.
Begin with a two-word transfer in each direction. Use known test values to verify direction, word order and byte order. Remember that K1 in DFROM/DTO also transfers the adjacent 16-bit register.
If POWER is on but NET does not become green, check the running master, station address, GSD selection, slot lengths and both line-end terminations before condemning the module.
Read CR#251 when NET flashes red. Distinguish address errors, watchdog faults and supply faults. Eliminate simple mistakes such as setting 26 hex when the intended address is 26 decimal.
When checking DB9 wiring, inspect the connector's incoming/outgoing cable arrangement and termination switch as well. A loose shield connection or damaged cable may work at a low rate and fail at a higher one.
Define how long the last received command remains valid after communication fails. Use application timeouts and a process-appropriate fault response instead of relying solely on the NET indicator.