Delta DVP04DA-H2 is a four-channel, 12-bit analog output module for compatible DVP-EH2 PLC systems. It converts values from the host CPU into voltage or current commands. Within an analog I/O system, it generates outputs; the DVP04AD-H2 performs the different task of reading inputs. It is a special expansion unit among PLC input and output modules.
Output modes and digital scaling
Configure each channel separately: Mode 0: 0–10 V; Mode 1: 2–10 V; Mode 2: 4–20 mA; Mode 3: 0–20 mA. The analog signal type must match the receiver setting and terminal wiring. The normal digital-to-analog conversion command range is K0–K4000. Specified resolution is 2.5 mV/LSB for 0–10 V and 5 µA/LSB for 0–20 mA.
With standard conversion curves, 0/2000/4000 produces 0/5/10 V in 0–10 V mode and 4/12/20 mA in 4–20 mA mode. Analog voltage and analog current use different output terminals. When selecting 0–10 V or 4–20 mA, remember that a zero command produces 4 mA in 4–20 mA mode. Interpret this together with the receiver’s stopping logic.
Wiring, load and isolation
Take voltage output from V+–COM and current output from I+–COM. Do not join V+ and I+; follow the selected output diagram. In analog signal applications, match the drive, recorder or controller analog input to the same range.
The model-specific sheet specifies 1 kΩ–2 MΩ load and 10 mA maximum for voltage output, and 0–500 Ω load for current output. Include cable and receiver resistance in the current-loop load. Optical isolation separates the internal digital circuit from the analog section; analog channels are not isolated from one another. Consider external signal isolation where receivers have different ground potentials.
Supply, expansion and response
External power is 24 VDC, permitted range 20.4–28.8 VDC, with 4.5 W maximum consumption. Select the power supply for the combined load. The module uses the compatible CPU’s right-side expansion bus. Special modules are numbered 0–7 by distance from the CPU; the eight-module allowance is shared, and no digital X/Y points are occupied.
Response is specified as 3 ms × channel count, giving a 12 ms basic conversion time for four channels. PLC scan and receiver filtering add to total response. Control-loop timing depends on the whole system. Accuracy is specified as ±0.5% of full scale at 25 °C and ±1% at 0–55 °C ambient.
Programming software and cable
Prepare the host program with WPLSoft or ISPSoft. Use TO to write modes and output values, and FROM to read identity and error registers in the ladder diagram. ISPSoft’s extension-module wizard can inspect or configure CR settings on supported hardware. DVP04DA-H2 does not run a standalone user program.
Connect the computer to the host PLC. For DVP-EH2 COM1 RS-232, 8-pin mini-DIN, use an appropriate DVP cable such as DVPACAB230. A computer without a serial port requires a USB–RS-232 adapter and its driver. In ISPSoft, select and start the appropriate COM connection through COMMGR. Select cables for the actual CPU port when using a different controller.
CR registers and correct channel-mode setting
CR#0 = H6401 identifies the module. CR#1 contains mode fields: CH1 b0–b2; CH2 b3–b5; CH3 b6–b8; CH4 b9–b11. Each channel uses three bits; b12–b15 are reserved. Calculate CR#1 = Mode1 + 8×Mode2 + 64×Mode3 + 512×Mode4, where Mode1–Mode4 are the channel codes from 0 to 3.
For four 4–20 mA channels, CR#1 = H0492. For special module 0, TO K0 K1 H0492 K1 writes that selection. CR#6–#9 contain CH1–CH4 output values; TO K0 K6 D100 K4 transfers D100–D103 to all four outputs. These examples affect every channel: use a test setup disconnected from the process, with correct wiring and initial values. Replace K0 with the actual module number.
FROM K0 K30 D120 K1 reads the error register. In CR#30, check b0 for supply, b1 for data, b2 for mode, b3 for OFFSET/GAIN, b4 for hardware/memory and b7 for instruction errors. Multiple errors may coexist. CR#34 reports firmware. Check calibration effects after changing the mode, and avoid rewriting mode selection unnecessarily on every scan.
OFFSET/GAIN and process control
CR#18–#21 adjust OFFSET and CR#24–#27 adjust GAIN. Do not use them to conceal incorrect receiver scaling or wiring. Measure low, middle and full-scale outputs first, then calibrate against a reference if necessary. CR#33 includes calibration permissions and default-restoration functions; preserve existing settings before changing it.
In PLC-based PID control, the host PLC or relevant control system performs the PID calculation; DVP04DA-H2 converts the resulting command into an analog output. Feedback arrives through a separate measurement path. Displaying setpoint, measured value and output percentage together on an HMI helps distinguish scaling problems from process faults.
RS-485, cabling and technical files
The RS-485 interface supports Modbus ASCII and RTU. The module’s own RS-485 interface cannot be used while it is connected to the CPU expansion bus. For standalone communication, CR#31 sets the station and CR#32 communication settings. Match format options to firmware. Do not assume normal TO/DTO writes survive power loss; initialize required settings in the PLC startup program.
Reduce electromagnetic interference by separating shielded signal cables from motor and mains wiring. Follow the manufacturer’s COM, FG and grounding diagram. Use Delta DVP PLC files for wiring sheets, conversion curves and CR descriptions. When replacing H, H2 or H3 modules, compare the complete model, CPU support, terminals and program.
Editor's Note
Check the command and mode together. A value of 2000 does not always mean 10 mA; it means 12 mA in 4–20 mA mode. The receiver must use matching scaling.
Test all four channels at low, middle and high outputs on a used unit. Measure voltage in parallel and current using the correct series connection. Never place an ammeter directly across a voltage output.
In a suitable 4–20 mA test circuit, a precision 250 Ω resistor produces 1/3/5 V at 4/12/20 mA. Dissipation is 0.1 W at 20 mA: select a suitable resistor rated at least 0.25 W and stay within the total load limit.
If an output appears faulty, disconnect the field cable and test with a suitable dummy load. For one faulty channel inspect its terminals and output stage; for all channels inspect supply, COM wiring and program first.
Back up calibration before resetting. Check output behaviour after a power cycle, CPU STOP and communication loss in a controlled setup. A zero analog command alone does not prove that the machine stopped safely.