Delta DVP08TC-H2

Delta DVP08TC-H2 – 8-Channel Thermocouple Temperature Module

Delta DVP08TC-H2 is a special expansion module for eight thermocouple inputs. It supports J, K, R, S, T, E and N sensors, plus 0–150 mV and ±150 mV input modes. It collects temperatures for furnaces, extruders, moulds and multi-zone heating systems through a compatible PLC such as DVP-EH2. It is not a standalone programmable CPU.

Input design, resolution and power

Each analog input can use its own sensor-type setting. The instruction sheet specifies 24-bit conversion; temperature data transferred to the PLC uses a signed 16-bit word with a 0.1 °C unit. ADC conversion, register width and measurement accuracy describe different properties. Overall accuracy is specified as ±0.6% of full scale at 0–55 °C ambient; 0.1 °C resolution does not guarantee 0.1 °C accuracy.

The supply is 24 VDC, permitted range 20.4–28.8 VDC, with 2.5 W maximum external power consumption. The model-specific instruction sheet specifies analog/digital isolation and isolation between channels. Also observe its requirement for floating thermocouple sensors. Never apply mains voltage to the input terminals.

Supported sensors and temperature ranges

The module ranges for different thermocouple types are J: -100…+1150 °C; K: -100…+1350 °C; R and S: 0…+1750 °C; T: -150…+390 °C; E: -150…+980 °C; N: -150…+1280 °C. Type J thermocouples and Type K thermocouples require different input settings. Check thermocouple standards and the probe’s own rating; a module’s upper measurement limit is not a temperature rating for every connected probe.

The difference between Pt100 and thermocouples matters: DVP08TC-H2 accepts thermocouples. For resistance sensors, consider a suitable RTD module such as DVP04PT-H2. An analog signal in mV mode must be interpreted using that mode’s scaling. When comparing analog and digital inputs, remember these terminals are not 24 V switching-sensor inputs.

Sensor wiring and PLC expansion

Connect thermocouple positive to L+ and negative to L-. Use extension/compensation cable appropriate to the thermocouple type, with suitable shielding. SLD is the shield connection. The module provides cold-junction compensation; unsuitable cable and heat sources near the terminals can introduce errors. Reduce electromagnetic interference by separating sensor wiring from drive/motor power cables and following the manufacturer’s grounding diagram.

Install the module on the compatible controller’s right-side expansion bus. Special modules are numbered 0–7 by distance from the CPU and occupy no digital X/Y points. The eight-special-module limit is shared with other special modules; check CPU compatibility and power capacity. Do not assume that DVP04TC-H, DVP04TC-H2 and DVP08TC-H2 have the same channel count or CR layout.

Programming software and cable

Create the host program with WPLSoft or ISPSoft. Use FROM/TO instructions in the ladder diagram to access module registers. Connect the computer to the host PLC’s programming port. ISPSoft’s extension-module wizard can also inspect or configure CR settings on supported hardware.

For the DVP-EH2 COM1 RS-232, 8-pin mini-DIN port, use an appropriate DVP cable such as DVPACAB230. A computer without a serial port needs a USB–RS-232 adapter and its driver. For ISPSoft, select the correct COM port in COMMGR and start the connection. Select the cable for the actual host CPU; thermocouple wiring and programming cables serve different purposes.

CR registers, sensor selection and reading example

CR#0 = H6804 identifies the model and CR#1 reports firmware. CR#2–#9 select CH1–CH8 types: H0000 J; H0001 K; H0002 R; H0003 S; H0004 T; H0005 E; H0006 N; H0007 0–150 mV; H0008 ±150 mV; HFFFF channel disabled. The default is type J. CR#10–#17 set averaging from K1 to K100, default K10. CR#18: K0 Celsius, K1 Fahrenheit.

CR#19–#26 contain the eight averaged measurements. For special module 0, FROM K0 K19 D100 K8 reads them into D100–D107. In Celsius mode, 253 means 25.3 °C and -125 means -12.5 °C. FROM K0 K37 D120 K1 reads error status. Replace K0 with the actual module number. CR#27–#34 are channel offsets; the documented relationship is measurement − offset = displayed value. Do not use an offset to conceal an incorrect sensor or cable.

Response time is 200 ms × channel count, giving 1.6 seconds for eight channels before additional averaging effects. In CR#37, b0 indicates supply error, b1 module error, and b2–b9 CH1–CH8 measurement-range errors. Several bits may be active simultaneously. Reject invalid readings instead of treating them as valid temperatures.

PID functions and heater outputs

The module includes additional PID control registers. CH1 starts at CR#100; subsequent channel blocks are spaced by 15 registers. CR#220 selects run/stop, CR#221 auto-tuning, CR#222 heating/cooling and CR#223 preheating. Set PID coefficients and sampling time for the process. These functions do not provide eight physical heater outputs on the module.

For PLC-based PID control, apply the calculated output through a suitable PLC output and SSR/drive. PID temperature control needs valid feedback, sensor-failure handling and independent overtemperature protection. RS-485 access to CR#100–#223 PID registers is unsupported. Verify measurement settings before starting auto-tuning.

RS-485 and parameter retention

The RS-485 interface supports Modbus ASCII and RTU. The module’s RS-485 port cannot be used while it is connected to the CPU expansion bus. For standalone communication, CR#35 sets the station and CR#36 holds communication settings. CR numbers are not raw Modbus addresses; match format details to the firmware and document edition.

Do not assume normal measurement settings written through TO/DTO remain after power loss. Reapply the required sensor types, unit and averaging during PLC startup. Check PID retention separately against the applicable edition. Use Delta DVP PLC files for wiring and register documentation, and preserve the full model and firmware with the backup.

Editor's Note

Check the sensor type first. A type J sensor configured as type K can produce plausible but incorrect readings. Verify each of the eight CR#2–#9 settings independently.

For a drifting channel, move a known-good probe or appropriate thermocouple simulator between channels. A fault that follows the probe points to the probe/cable; one that stays on the channel calls for terminal, protection and input-circuit inspection.

If readings jump when a motor or contactor starts, inspect shielding, grounding and cable routing before replacing the card. Panel components heating the cold-junction area can also affect measurements.

Test all eight inputs on a used unit at more than one reference temperature. Check the error register and settings after a power cycle. A POWER indicator alone does not validate the measurement circuits.

If temperature is correct but heating does not operate, trace the PID run bit, calculated output, PLC output and SSR in sequence. Isolate power before removing the module, and ensure a sensor fault cannot leave heating enabled.

Related topics and navigation

DVP08TC-H2 main page · Delta DVP-H2 modules · DVP expansion modules · DVP PLC series · DVP PLC files

External manufacturer documents

Delta DVP08TC-H2 Instruction Sheet, 2017, TR/EN · WPLSoft / ISPSoft FAQ · ISPSoft / COMMGR