Delta DVP04PT-H2
Delta DVP04PT-H2 RTD temperature input module
Delta DVP04PT-H2 is a four-channel RTD temperature input module developed for the DVP-EH2 family and also listed in the DVP-EH3 product catalogue. It converts measurements from resistive temperature sensors into digital data for the PLC program. The manufacturer's multi-sensor instruction sheets specify PT100, PT1000, NI100 and NI1000, plus resistance measurement modes.
The selected channel mode must match the PT100 or PT1000 sensor. The difference between PT100 and thermocouples matters here: this is an RTD input module. J/K-type thermocouples require suitable hardware such as DVP04TC-H2. DVP04PT-H2 sensor terminals are not general-purpose analog voltage/current inputs.
Sensor ranges, scaling and response time
The multi-sensor instruction sheet specifies −180…+800 °C for PT100/PT1000 and −80…+170 °C for NI100/NI1000. These are module measurement limits; the probe sheath, cable and sensing element may impose a narrower range. Celsius data uses 0.1 °C units: 253 = 25.3 °C; −125 = −12.5 °C.
The sheet specifies 16-bit digital data and 0.1 °C resolution. Resolution is different from overall accuracy; the manufacturer gives ±0.6% of full scale at an ambient temperature of 0–55 °C. Response time is specified as 400 ms × number of channels, approximately 1.6 seconds for four channels. This is not the PLC scan time; averaging and the probe's thermal lag must also be considered.
Supported 0–300 Ω and 0–3000 Ω resistance modes use a digital range of 0–30000. Do not interpret these values using the temperature mode's 0.1 °C scale. Record the analog signal type and selected channel mode clearly in the project.
Older documents and hardware revision
DVP04PT-H2 document editions differ. Older PT100-focused sheets show CR#1 as reserved, while the 2010 and 2023 multi-sensor sheets define it as the channel-mode register. Before applying the newer table to an older module, check its label and CR#34 firmware version. The CR#0 model code is H6402; this code alone does not establish every revision-specific feature.
DVP04PT-H, DVP04PT-H2 and DVP04PT-S are separate products. Match the CPU, expansion connection and document to the complete model. Special expansion modules are numbered 0–7 by their distance from the CPU; intervening digital modules do not count toward this number. The module occupies no standard digital X/Y points.
Power supply and RTD wiring
The supply is 24 V DC, with a permitted range of 20.4–28.8 V DC and specified consumption of 2.5 W. Size the DIN rail power supply together with the other loads. Wire sensors with power disconnected; do not apply 24 V supply or mains voltage to RTD inputs.
For a three-wire RTD, connect one sensor end to L+ and the two matched conductors from the other sensor end to L− and I−. Connect the shield according to the FG arrangement. The manufacturer shows a bridge between L− and I− for two-wire operation, where cable resistance adds to the measurement. Three-wire wiring is preferred to reduce lead-resistance effects; conductor construction and resistance should be closely matched.
Separate sensor wiring from motor, drive and power cables. Follow the manufacturer's grounding and shielding diagram. If a PT100 converter produces 4–20 mA or 0–10 V, connect its output to an appropriate current/voltage input module.
Programming software and cable
Configure and read the module through FROM/TO instructions in the connected CPU's ladder program. Use a version of WPLSoft or ISPSoft supporting that CPU; COMMGR manages the appropriate communication channel for ISPSoft. The module does not run a separate USB programming project.
A common connection to the EH2/EH3 CPU's COM1 RS-232 port uses DVPACAB2A30: approximately 3 m, with a 9-pin female D-sub PC connector and an 8-pin mini-DIN PLC connector. Without a PC serial port, add a USB-to-RS-232 converter with its driver installed and select the assigned COM number. Observe the differences between RS-232, RS-422 and RS-485 when choosing Delta PLC cables. The module's D+/D− terminals are not the CPU's RS-232 programming port.
CR registers and temperature reading example
In the multi-sensor sheet, CR#1 uses b0–b3 for CH1, b4–b7 for CH2, b8–b11 for CH3 and b12–b15 for CH4. Channel codes are 0: PT100; 1: NI100; 2: PT1000; 3: NI1000; 4: 0–300 Ω; 5: 0–3000 Ω; F: disabled. For example, HFFF2 enables CH1 as PT1000 and disables the other channels. This write affects all four channel-mode fields.
CR#2–5 set the CH1–CH4 averaging counts; the corresponding sheet specifies 1–100, default 10. CR#6–9 contain averaged °C, CR#18–21 current °C, CR#30 error status and CR#34 the firmware version. Do not transfer an older sheet's averaging limit to a different revision.
For special-module number 0 and hardware verified against this CR#1 table only: select four PT100 channels under a first-scan condition with TO K0 K1 H0000 K1. Cyclic FROM K0 K6 D100 K4 reads the four averaged Celsius values into D100–D103. FROM K0 K30 D200 K1 reads error status. On the HMI panel, use signed 16-bit data with one decimal place; do not display negative temperatures as unsigned values. Avoid continuously rewriting channel and averaging settings.
RS-485 and temperature control
Standalone operation supports Modbus RS-485 using ASCII or RTU. RS-485 cannot be used simultaneously with the CPU expansion connection. For standalone PC access, use a USB-to-RS-485 converter with its driver installed. CR#31 sets the station address and CR#32 the communication format; the default is 9600 bps, ASCII, 7E1. Do not apply newer serial-format options directly to older firmware.
Supported revisions also provide per-channel PID registers. When designing PID control with a PLC, handle measurement, calculated output and physical power switching separately. DVP04PT-H2 has no power output for driving a heater. Select an SSR or other suitable output hardware according to the load and control cycle.
Editor's Note
For a used module, record its complete label, terminal block, CPU model and firmware value. Do not configure every device carrying the DVP04PT-H2 name solely from the newest sheet found online.
Before adjusting calibration for a drifting reading, check sensor type and L+/L−/I− wiring. Wiring a two-wire probe as though it were three-wire, or using extension leads with unequal resistance, can create a persistent error.
With control outputs disconnected, test each channel at low, middle and high temperature points using a suitable RTD simulator. Moving the same simulator between all four channels helps distinguish a sensor fault from a channel fault.
An unused channel can affect the ERROR indication. Read CR#30 as a bit field first; several errors may coexist. Disable unused channels using the table supported by the device. Do not perform a general reset merely to extinguish the error light.
If temperature jumps when contactors operate, check shielding, terminals and the 24 V supply under load. Increasing averaging can smooth fluctuations, but it does not repair wiring and delays the reading.
Back up settings before changes and test power restoration. Do not assume values written through CPU TO instructions remain stored. Verify how heating stops on a broken sensor, and provide independent overtemperature protection.
PDF manuals and related topics
Use our Delta DVP PLC files page for RTD wiring, CR tables and CPU programming documents. The archived 2010 model sheet contains English and Chinese sections; the 2013 special-modules and 2020 programming manuals are in English. Compare older family-manual tables with the model sheet and actual device revision.