Delta DVP04TC-H2

Delta DVP04TC-H2 Four-Channel Thermocouple Temperature Measurement Module

Delta DVP04TC-H2 is a PLC expansion module with four thermocouple inputs. It sends furnace, extruder, packaging and heating-zone measurements to the host CPU. This is a specialised analog input module: it is not a Pt100/RTD module or a heater power output. Consider the difference between Pt100 and thermocouples when selecting the sensor and module.

Document revision and supported sensors

The DVP-0070630-03 instruction sheet dated 10 April 2023 specifies J, K, R, S, T, E and N thermocouples plus 0–150 mV input, describing 24-bit conversion. The 2007 sheet and 2013 special-modules manual describe five types and 14-bit conversion. The 2010 DVP-1070630-02 sheet also describes 24-bit conversion and seven types; publication year alone does not identify a hardware generation. Keep these document specifications separate and compare the actual unit’s firmware with the applicable documentation.

Temperature ranges in the 2023 sheet: J: −100…+1150°C; K type: −100…+1350°C; R and S: 0…+1750°C; T: −150…+390°C; E: −150…+980°C; N: −150…+1280°C. These are module conversion ranges; the probe sheath, cable and operating environment impose their own limits. Follow the relevant thermocouple standards and select matching extension or compensation cable.

Resolution, digital scaling and response time

Celsius registers use 0.1°C units: for example, 253 represents 25.3°C. Handle negative readings as signed data. ADC conversion bits, the CPU temperature register width and measurement accuracy are different specifications. A 0.1°C display increment does not guarantee ±0.1°C accuracy.

The 2023 sheet specifies ±0.6% of full scale over 0–55°C ambient and a response time of 200 ms × channel count. Four channels therefore give a nominal value of approximately 800 ms; averaging can further delay the response to process changes. CR#2–CR#5 averaging settings span 1–100 in the 2023 sheet, compared with 1–20 in the older documents.

Power supply and sensor wiring

The module needs external 24 V DC, with an allowed range of 20.4–28.8 V DC and specified consumption of 2.5 W. Check DC voltage at its 24V/0V terminals. Connect each sensor’s positive wire to L+ and negative wire to L−; SLD is for the shield. Keep power and sensor terminals clearly identified.

The thermocouple’s low-level analog voltage requires extension or compensation cable suitable for that thermocouple type. Preserve polarity and check wire colours against the applicable standard. Internal cold-junction compensation cannot correct the wrong cable or reversed polarity. Cable routing away from electromagnetic interference, proper shielding and grounding affect stability. The 2023 sheet specifies floating thermocouple sensors.

CPU compatibility, software and programming cable

The manufacturer sheet describes FROM/TO access through a DVP-EH2 CPU. For another CPU family, verify the exact CPU and expansion compatibility separately. Special modules are numbered 0–7, starting with the closest to the CPU; this is not a digital X/Y address. Remove power before connecting the module.

PLC programming is performed through the host CPU. Use WPLSoft for EH2 projects, or ISPSoft when supported by the exact CPU and software release. The 2023 sheet also mentions the ISPSoft extension-module wizard for finding or modifying control registers. The ladder program reads measurements; configure COMMGR where required for the connection.

For a CPU with an 8-pin mini-DIN RS-232 port, use a UC-PRG020-12A USB-to-RS-232 programming cable, or a UC-MS020-01A serial cable with a suitable USB-to-RS-232 converter. Check the exact CPU port, pinout, cable driver and COM number. The programming cable connects to the CPU; thermocouple wiring connects to L+/L−.

Control registers and a reading example

CR#0 is model ID H’6403; CR#1 selects channel/sensor modes; CR#6–CR#9 hold averaged Celsius readings; CR#14–CR#17 hold present Celsius readings; CR#30 reports errors; and CR#34 reports firmware. Each channel has a three-bit sensor-type field in CR#1. In the 2023 sheet, b12–b15 enable/disable channels: 0 enabled, 1 disabled. Older documents mark these upper bits as reserved.

If this is genuinely the first special module, FROM K0 K6 D100 K4 reads the four averaged Celsius values into D100–D103. Change K0 to the actual special-module index. A D100 value of 253 means 25.3°C. Avoid unnecessarily rewriting sensor modes and averaging settings every scan; manage initialisation and error checks separately.

RS-485, Modbus and temperature control

In independent operation the module supports RS-485/Modbus communication using ASCII or Modbus RTU. The module’s RS-485 connection cannot be used while it is attached to the CPU expansion bus. CR numbers differ from Modbus parameter addresses; for example, the documented address of CR#6 is H’409C. Select CR#32 communication settings for the actual firmware.

Temperature readings can provide feedback for PID control with a PLC. When implementing PID temperature control, coordinate measurement/filter timing with the control cycle. Heater power must be switched by suitable external output and power devices.

Editor’s Note

Record the label and firmware before buying or replacing a used unit. Documents from different periods describe different capabilities under the same model name. A successful K-type reading alone does not establish support for every sensor mode, extended range or newer register function.

Test all four channels individually with a known-good probe or thermocouple calibrator. Check a second point suitable for the application as well as a near-ambient reading. Match the calibrator’s thermocouple type and cold-junction compensation settings.

If all channels show a similar offset, inspect terminal-area temperature differences, cold-junction compensation and extension cable. For a single-channel fault, swap the probe and cable with a healthy channel to separate a sensor problem from a module problem.

Do not immediately increase averaging to its maximum when readings fluctuate. First inspect loose terminals, shield connections, supply ripple and interference from drive cables. Heavy filtering also delays indication of a real temperature rise.

Monitor sensor breaks through CR#30 and channel status, and apply plausible temperature limits in the program. Address independent overtemperature protection and the emergency-stop arrangement when controlling heaters. A plausible number on the display is insufficient evidence of safe control.

With power removed, inspect corrosion, cracked solder joints and input-protection components. If 24 V reached a sensor input, replacing the visibly damaged part may be insufficient. After repair, retest every channel, polarity and temperature tracking.

PDF files, related models and navigation

Use our Delta DVP PLC files page for documentation. The 2023 DVP-0070630-03 sheet and the older special-modules manual are different editions; apply sensor types, ranges and CR settings according to the appropriate document revision.

DVP04PT-H2 is a related RTD model and does not have the same input type as DVP04TC-H2. Within the DVP H2 module range, match the sensor type to the expansion module function.

Delta main page | Delta PLC | DVP PLC series | DVP-EH2 | DVP H2 modules | DVP04TC-H2 models

External references

Delta DVP04TC-H2 manufacturer instruction sheet, 2023 | Delta special-modules application manual — older edition