Delta DVP06XA-H2
Delta DVP06XA-H2 4 Analog Input / 2 Analog Output Module
The Delta DVP06XA-H2 adds four analog inputs and two analog outputs to a compatible DVP PLC main unit. CH1–CH4 are inputs and CH5–CH6 are outputs. The “06” designation does not mean six analog inputs. Select voltage or current operation through both the channel mode and terminal wiring.
Use our Delta DVP PLC files page for wiring, conversion curves and control-register information. Keep DVP06XA-H, DVP06XA-H2 and DVP06XA-H3 generations distinct, particularly their raw-value scaling and resolution.
Four analog inputs: range and resolution
The basic voltage input range is −10 to +10 V, converted to −2000 to +2000 with 12-bit / 5 mV resolution. Current input uses −20 to +20 mA, converted to −1000 to +1000 with 11-bit / 20 µA resolution. Do not copy DVP04AD-H2 scaling into this module's program.
Interpret analog signals using the selected mode and calibration curve. The 0–10 V / 4–20 mA label alone is insufficient. On the standard voltage Mode 0 curve, 5 V is approximately 1000 and 10 V is 2000. On current Mode 3, 4 mA is approximately 200 and 20 mA is 1000; the standard zero point in Mode 2 is 4 mA.
Input impedance is approximately 200 kΩ for voltage and 250 Ω for current. Configure input averaging through CR#2–CR#5. More averaging may smooth fluctuations but also slows the measurement response. The analog and digital sections are isolated, but analog channels are not isolated from one another.
Two analog outputs: range and load limits
CH5 and CH6 use command values of 0–4000. Basic voltage output is 0–10 V, 12-bit / 2.5 mV; basic current output is 0–20 mA, 12-bit / 5 µA. Selectable modes also include 2–10 V and 4–20 mA. Match the output mode to the input configuration of the connected variable frequency drive or analog controller.
Voltage output requires a load impedance of at least 1 kΩ; current output requires 500 Ω or less. In standard 0–10 V mode, K2000 produces approximately 5 V. In 4–20 mA output Mode 2, K0 = 4 mA, K2000 = 12 mA and K4000 = 20 mA. A zero command does not mean zero voltage or current in every mode.
CPU compatibility and power supply
DVP06XA-H2 is used in the DVP-EH2 expansion system and is also listed in Delta's DVP-EH3 catalogue table. Check the exact CPU, firmware and supported DVP -H2 module arrangement. DVP expansion modules are not universally interchangeable across CPU families.
The module requires an external 24 V DC supply, with an operating range of 20.4–28.8 V DC. The H2 instruction sheet specifies a maximum consumption of 3.5 W. When selecting a power supply or DIN rail supply, account separately for field transmitters and the connected output equipment.
Distinguishing input and output wiring
For voltage input, connect the signal between V+ and the appropriate COM. For current input, bridge V+ and I+ and complete the loop through the input and COM as shown in the wiring diagram. For pressure sensors and temperature transmitters, also verify the two/three/four-wire arrangement and external loop supply.
Voltage outputs use V+ and COM; current outputs use I+ and COM. Do not automatically apply the input's V+–I+ bridge to output channels. These outputs provide analog commands to suitable equipment; they are not power outputs for directly driving motors, coils or valve windings.
A conventional switching-output inductive sensor or photoelectric sensor is not an analog input source. Separate shielded analog wiring appropriately from contactor and relay load wiring. Consider control panel components, shield connections and suitable supply fuse protection together.
Programming software and cable
No independent PLC program is downloaded to the module. Use CPU-compatible WPLSoft or ISPSoft; exchange data through FROM/TO instructions in the CPU program. ISPSoft's extension-module wizard can inspect and edit control registers. Configure the COMMGR connection for the CPU port.
A suitable DVP CPU's RS232 programming port can use DVPACAB2A30. If the PC has no RS232 interface, use a suitable USB-to-RS232 converter, its driver and the correct COM port. The Delta PLC programming cable connects to the CPU; analog terminals and the module's D+/D− terminals do not replace this programming connection.
Control registers and FROM/TO example
CR#0 = H6604 identifies the model. CR#1 configures all six channels: three bits per input channel and two bits per output channel. Input modes are 0: −10 to +10 V, 1: −6 to +10 V, 2: −12 to +20 mA, 3: −20 to +20 mA. Output modes are 0: 0–10 V, 1: 2–10 V, 2: 4–20 mA, 3: 0–20 mA.
CR#6–CR#9 hold averaged inputs; CR#12–CR#15 hold present inputs. CR#10 commands CH5 and CR#11 commands CH6. CR#30 reports errors. Convert measurements into the correct engineering units for an HMI panel or SCADA.
For a module at K0, FROM K0 K6 D100 K4 reads four averaged inputs into D100–D103. TO K0 K10 D200 K2 writes D200 and D201 to the two outputs. Keep output commands within the selected mode's 0–4000 range.
As a bench example only, TO K0 K1 HA000 K1 sets CH1–CH4 to voltage Mode 0 and CH5–CH6 to 4–20 mA Mode 2. Apply mode settings deliberately during initialization rather than copying the example directly into a running machine. Back up parameters first because changing CR#1 can affect OFFSET/GAIN settings.
RS485 access and generation differences
Independent serial access supports Modbus ASCII or Modbus RTU. However, the manufacturer states that the module's RS485 connection cannot be used while connected to the CPU expansion bus. Do not assume simultaneous CPU FROM/TO access and independent serial access. CR numbers and serial register addresses are different references; see our Modbus communication guide for the addressing concepts.
The DVP04AD-H2 provides analog inputs, while DVP04DA-H2 provides analog outputs. The DVP06XA-H3 is a different-resolution generation. Matching four-input/two-output counts does not establish unchanged program scaling.
Editor's Note
Check the complete -H2 suffix when buying a used module. Do not confuse it with H or H3. Review the CPU model, module order and existing raw-value calculations together.
Start an input test with one channel. Apply known 0, 5 and 10 V values, or 4, 12 and 20 mA according to the selected mode. Calculate expected readings from this module's curve rather than DVP04AD scaling.
Initially disconnect actuator loads for output tests. Use a suitable voltmeter for voltage and a correctly arranged current measurement for current. Verify that K2000 gives 5 V in 0–10 V mode or 12 mA in 4–20 mA mode.
Distinguish a missing current-input bridge from an incorrectly wired current output. A connection appropriate for an input is not automatically appropriate for an output; CH1–CH4 and CH5–CH6 perform different duties.
For shifted readings, check mode, OFFSET/GAIN, signal common and load impedance first. Remember the lack of channel-to-channel isolation if one channel affects another. Eliminate cable and supply faults before attempting board repair.
Do not repeatedly rewrite CR#1 on every scan. Back up the parameters and test output behaviour during CPU STOP, restart and communication loss using the actual CPU/module settings.
Related topics and files
Delta DVP PLC series · DVP -H2 modules · DVP expansion modules · Delta DVP PLC manuals and PDF files.
External references
Delta DVP06XA-H2 2023 sheet, manufacturer download page · Delta DVP-EH2 expansion information · Delta DVP catalogue, EH3 module table.