Delta DVP32HN00T – 32-point transistor output expansion unit
Delta DVP32HN00T is a digital expansion unit with 0 inputs and 32 transistor outputs, used to add outputs to DVP-EH control systems. The host PLC executes the machine program. Typical selection work involves panels with numerous DC control loads.
The unit supply is 100–240 V AC, 50/60 Hz; the transistor load voltage is 5–30 V DC. Keep these supplies distinct. For replacement in a DVP-EH2 or DVP-EH3 installation, check the exact host CPU, expansion connection and hardware revision together. A shared DVP family name does not establish interchangeability.
Output capacity and load selection
Per-point output current: 0.3 A at 40 °C, 0.2 A at 45 °C, 0.15 A at 50 °C and 0.1 A at 55 °C. The instruction sheet specifies 2 A per common terminal. Include group totals and starting currents in the load calculation. Listed unit consumption is 30 VA.
The outputs use an NPN open-collector, sinking arrangement. Connect a suitable DC load between the positive supply and its Y output, with the relevant output common connected to the DC return as shown in the wiring diagram. Check the actual terminal groups. Use a suitable interposing relay or driver for AC or higher-current loads; never connect a 230 V AC load directly to these transistor outputs.
For DC valves, interposing relays and indicator lamps, assess switching surges, leakage and release behaviour alongside rated current. Fit suitable suppression to inductive loads. An illuminated output LED alone does not establish that the connected load receives the correct voltage and current.
Addressing and commissioning
DVP X/Y addresses follow octal numbering. The assigned Y start depends on the host CPU and preceding digital expansion units. If this unit is assigned Y20, its 32 outputs occupy Y20–Y57. This is an example, not a universal starting address; verify the installed project.
Install the unit with power isolated, then check the expansion connector, commons and grounding. Prevent machine movement during testing and begin with a small test load. Confirm that each forced software address operates the intended physical channel, and remove every force after testing. A transistor output designation alone does not qualify this unit for high-speed servo pulse commands.
Programming software and connection cable
No separate program is downloaded to DVP32HN00T. The host CPU program controls its Y addresses. Select a version of WPLSoft or ISPSoft that supports the actual CPU, and select the correct CPU type in the project. Back up the existing program before changing the CPU selection or downloading a project.
Connect the computer to the host PLC programming port. For an appropriate DVP CPU RS-232 port, the UC-PRG020-12A USB programming cable is an option; match the connector and pinout to the CPU manual. Install its USB driver and select the correct COM port. This expansion unit has no separate USB, RS-232 or Ethernet programming connection.
Differences from related models
DVP32HN00R provides the same output count with relay switching, requiring a separate load-wiring assessment. For fewer outputs, compare DVP08HN11T and the relay version DVP08HN11R. Where inputs are also needed, DVP32HP00T offers 16 inputs / 16 transistor outputs, while DVP48HP00T provides 24 inputs / 24 transistor outputs.
Smaller mixed I/O options include DVP08HP11T and DVP16HP11T. Relay mixed I/O alternatives include DVP08HP11R, DVP16HP11R, DVP32HP00R and DVP48HP00R. These are selection comparisons; verify point counts, supply and terminal differences before considering a replacement.
Related topics
For additional sensor inputs, see DVP08HM11N, DVP16HM11N and DVP32HM11N. Analog measurement, analog control and mixed analog tasks belong to different module classes, represented by DVP04AD-H2, DVP04DA-H2 and DVP06XA-H2. DVP32HN00T does not perform these analog functions.
Editor’s Note
When buying a used unit, first read HN00T on its label. An HN00R or HP model needs a different assessment; a small code difference can change the load wiring.
Do not accept “the LEDs work” as a complete test. Ask for all 32 outputs to be checked with a suitable load, including every common-terminal group.
If an entire group fails, check the DC load supply, return, fuse and expansion connection first. A single channel that remains conducting can indicate a failed output transistor.
Inspect burnt terminals, loose screws, corrosion and the expansion connector carefully. A clean photograph gives little evidence of operation under load.
Record the CPU program and wiring before repair. Begin with power isolated, and never apply an insulation tester to connected electronic circuits. Test a repaired channel with a current-limited load before returning it to service.
PDF documents and navigation
See the Delta DVP PLC PDF files page for documentation. DVP32HN00T model page · Delta main page.
External reference: Delta DVP-EH DIDO manufacturer instruction sheet — 25 April 2008 edition, English and Chinese, hosted in a distributor archive. Check against the installed hardware revision.