Delta DVP48HP00T

Delta DVP48HP00T — Expansion Unit with 24 Inputs and 24 Transistor Outputs

Delta DVP48HP00T is a mixed digital I/O expansion unit with 24 inputs and 24 transistor outputs for DVP-EH family PLC systems. It adds 48 field I/O points. The main supply is 100–240 V AC and the input signals are 24 V DC. It has no CPU and does not run an independent PLC program. T identifies transistor outputs; do not confuse it with the relay-output DVP48HP00R.

Main power and 24 V service output

Connect the AC supply to L/N. The nominal rating is 100–240 V AC, 50/60 Hz, with the sheet specifying −15%/+10% voltage tolerance. Power consumption is 30 VA. Keep mains wiring separate from X/Y and service-supply terminals. This 00 unit does not use the same main supply as the smaller 24 V DC powered HP11 modules.

The +24V/24G service output is rated at a maximum of 500 mA. This is the auxiliary DC supply budget, not the current rating of each Y output. Account for input circuits and connected sensors. Do not parallel an external power supply with the internal +24V output. Follow the manufacturer power sequence for the CPU and powered extensions, and complete protective grounding.

24 V DC inputs and NPN/PNP wiring

The 24 inputs support sink/source wiring. The sheet specifies 5 mA at 24 V DC and an approximate 20 ms input response. The ON threshold is above 16.5 V and the OFF threshold below 8 V. Select NPN/PNP wiring together with the S/S common: an NPN open-collector sensor normally uses S/S at +24 V, while a PNP sensor uses S/S at 0 V. Verify the actual output type of an inductive sensor or photoelectric sensor.

These inputs are not interchangeable with the CPU’s high-speed counter inputs. Approximately 20 ms response can cause fast encoder pulses to be missed. Use the CPU’s specified fast inputs or an appropriate counter module for encoder counting.

Transistor outputs, load and temperature limits

The 24 outputs are NPN open-collector/sinking outputs. Connect the DC load between the positive supply and Y, with the corresponding C common connected to the circuit 0 V. The load voltage range is 5–30 V DC. These are not dry relay contacts; do not switch an AC load directly through a Y terminal.

Per-point resistive-load limits: 0.3 A at 40°C, 0.2 A at 45°C, 0.15 A at 50°C and 0.1 A at 55°C. A separate 2 A total limit per common group also applies. A 0.3 A point rating does not mean every output can carry that current at every ambient temperature.

Local terminal groups: C0 → Y0–Y3; C1 → Y4–Y7; C2 → Y10–Y13; C3 → Y14–Y17; C4 → Y20–Y27. Check total current particularly for the eight-output C4 group. These are the labels printed on the unit; actual CPU Y addresses depend on expansion order.

The sheet specifies transistor switching times of 15 µs ON and 25 µs OFF. These electrical timings do not guarantee a particular servo pulse frequency or hardware positioning function. Use suitable suppression for inductive loads, load-appropriate fuses and an intermediate driver where required. Do not connect motors or high-power loads directly.

CPU compatibility and X/Y addressing

The unit belongs to the DVP-EH/DVP-EH2 hardware group; the manufacturer’s EH3 module table also lists DVP48HP00T. For DVP-EH3 and other replacement projects, check the exact CPU, expansion connection, hardware revision and total I/O capacity. Do not assume the same interface as E2 or Slim modules.

X and Y addresses use octal numbering: X10 follows X7; X8/X9 are not used. Local labels are X0–X27 for inputs and Y0–Y27 for outputs. For example, when this is the first digital extension after an EH main CPU with 16 inputs and 16 outputs, its 24 inputs normally occupy X20–X47 and its 24 outputs Y20–Y47. Earlier modules and CPU address-allocation rules determine the actual starting points.

Programming software and cable

DVP48HP00T does not receive a separate program. Use its inputs and outputs in the host CPU’s PLC programming project. For EH2/EH3, use WPLSoft or an ISPSoft release supporting the exact CPU; verify software support separately for legacy EH CPUs. Use the actual X/Y addresses in the ladder program. Do not apply an analog module FROM/TO and CR-register template to this digital unit.

For a host CPU with an 8-pin mini-DIN RS-232 port, use UC-PRG020-12A for USB programming access. Alternatively, connect a UC-MS020-01A serial cable to a PC RS-232 port or suitable USB-to-RS-232 converter. Install the USB driver, select the assigned COM port and configure COMMGR where required. The PC cable connects to the CPU; the expansion cable connects the CPU and DVP48HP00T.

Communication and panel installation

DVP48HP00T is not an independent RS-485 or Modbus RTU station; monitor its states through the CPU communication interface. Separate supply/output power conductors from sensor wiring and apply electromagnetic interference measures. Install it in an enclosure using 35 mm DIN rail or suitable screw mounting. Transistor current derating still applies within the 0–55°C operating range.

Editor’s Note

Check the 48HP00T label and L/N terminals first. This is not a small extension with a 24 V DC main supply. Check T versus R as well: do not transfer a relay-unit load circuit directly to the transistor model.

Inspect the expansion cable, connectors, terminals and DIN clip before applying power. Follow the correct power sequence for the CPU and powered extension. Do not connect or disconnect expansion cables while energised.

Test all 24 inputs individually and verify both their LEDs and the expected CPU X addresses. If the wrong address changes, correct the module order/addressing first. Check S/S against the sensor’s NPN/PNP output type.

Test all 24 outputs individually with a suitable fused DC load. A Y LED alone does not prove that the transistor can carry load current. For a failed group, first check its C common, 0 V return and load supply.

For a fault appearing as the panel warms up, measure load current and ambient temperature together. A shorted output transistor may energise a load even when Y is OFF in the program. Retest every channel and common group after repair.

The machine’s emergency-stop and safety-relay arrangement must remove hazardous energy as required. Check external interlocking for opposing commands such as forward/reverse; do not rely only on mutual conditions in PLC code.

PDF files

Use our Delta DVP PLC files page for documentation. The DVP-EH DIDO sheet covers power, I/O, terminals and expansion addressing. The cable guide is a supplementary host-CPU-to-PC connection reference. Compare legacy and newer document editions against the exact unit and hardware.

Related topics and navigation

DVP48HP00R has 24 inputs/24 relay outputs; DVP32HP00T has 16 inputs/16 transistor outputs; DVP32HN00T provides 32 transistor outputs. DVP16HP11T provides 8 inputs/8 transistor outputs and uses a 24 V DC main supply. Check terminal, supply and output differences before substituting any unit.

Delta main page | Delta PLC | DVP PLC series | DVP expansion modules | DVP EH modules | DVP48HP00T model page

External manufacturer documents and archive references

Delta DVP-EH DIDO — online archive of the manufacturer’s 2024-02-21 sheet | DVP-EH DIDO — legacy 2008-04-25 edition | Delta PLC/HMI Cable Selection Guide — DigiKey archive