Delta DVP32HP00T

Delta DVP32HP00T – 16-Input, 16-Transistor-Output Expansion Module

Delta DVP32HP00T is an I/O expansion unit in the DVP EH module family, providing 16 digital inputs and 16 NPN transistor outputs. Its unit supply is 100–240 V AC, while its inputs use 24 V DC signals. It extends a host PLC rather than running a separate user program.

Typical tasks include collecting pushbutton, limit-switch and sensor signals and switching suitable DC loads. When comparing Delta DVP expansion modules, check the output circuit as well as the I/O count. In this model designation, 32 denotes total I/O points and T identifies transistor outputs.

Electrical specifications

Supply: 100–240 V AC, 50/60 Hz. Inputs: 16 × 24 V DC, sink/source wiring using the S/S common. Outputs: 16 × NPN open collector; 5–30 V DC load circuit.

Current per output: 0.3 A at 40°C; 0.2 A at 45°C; 0.15 A at 50°C; 0.1 A at 55°C. Common-terminal limit: 2 A/COM. Both limits apply; individual channel ratings do not permit every output to carry its maximum current simultaneously.

Input response: approximately 20 ms. Transistor switching: 15 µs turn-on and 25 µs turn-off. These figures alone do not establish a high-speed counter function or a guaranteed pulse-output frequency.

Input and output wiring

For PNP sensors, connect S/S to 0 V; for NPN sensors, connect S/S to +24 V. Devices sharing an input common must use a compatible wiring arrangement. For the NPN outputs, connect the load between positive DC and the Y terminal, with the corresponding C common connected to DC 0 V. Match each terminal group to the diagram on the unit.

An AC-powered unit does not provide AC-switching transistor outputs. Provide suitable transient suppression for inductive DC loads and appropriate load protection. Apply mains power only to L/N, never to X/Y or S/S. Disconnect power before changing the installation or wiring.

Host PLC and expansion connection

The module appears in DVP-EH digital expansion documentation and in Delta’s DVP-EH3 catalogue. For an existing DVP-EH2 or other EH installation, check the exact CPU, revision, expansion arrangement and power budget. Do not assume compatibility with every DVP series controller.

The unit connects through the PLC expansion connection, which is separate from the computer programming cable. Changing the module order requires checking the X/Y addresses used in the existing project.

X/Y addressing

Delta DVP X/Y addresses use octal numbering: X27 is followed by X30. In the manual’s example with a 32-point EH host containing 16 inputs and 16 outputs, the first DVP32HP00T occupies X20–X37 and Y20–Y37. Other preceding modules or a different CPU I/O arrangement can change these starting addresses; this range is not universal.

A commissioning test can monitor X20 through the host CPU and operate Y20 into a suitable test load. Confirm the actual module order and CPU I/O map before using those example addresses.

Programming software and cable

No separate program is downloaded to DVP32HP00T. Its I/O is used in the host PLC program. WPLSoft can edit a suitable DVP CPU project; ISPSoft is an option when it supports the selected host CPU and version. Do not select DVP32HP00T as the project’s CPU. See Delta PLC software for related tools.

For a suitable EH CPU with an RS-232 programming port, a connection can use PC RS-232 → UC-PRG020-12A → CPU. UC-MS020-01A is another cable used for appropriate RS-232 connections. A computer without a serial port needs a suitable USB-to-RS-232 adapter and driver. Verify the CPU port, pinout and communication settings; the programming cable connects to the CPU, not this expansion unit.

Differences from related models

DVP32HP00R provides the same 16-input/16-output arrangement with relay outputs; its output wiring must not be treated as identical. DVP32HN00T provides 32 transistor outputs without inputs.

For fewer points, DVP16HP11T provides 8 inputs/8 outputs and DVP08HP11T provides 4 inputs/4 outputs. DVP48HP00T offers 24 inputs/24 outputs. Check the supply and terminal arrangement of each candidate; these are comparison models rather than guaranteed direct replacements.

Editor’s Note – Workshop checks and used equipment

Read the complete 00T model suffix before making a replacement. Check how the field loads are powered before substituting a transistor unit for a relay version.

An illuminated output LED is not a complete test. Use a suitable low-current load and measure switching, on-state voltage drop and off-state behaviour.

If several outputs sharing a common fail together, check the C connection, field supply and fuse before concluding that the module is faulty.

If an input LED changes but a different program address responds, photograph the module order and establish the actual I/O map instead of trusting an old project.

For temperature-related faults, measure load current and cabinet temperature together. Include simultaneous loads sharing each common terminal.

When buying used equipment, request clear views of the label, terminals and expansion connection and, where possible, a test of every I/O point. For repaired units, loaded operation matters alongside component identification.

PDF documents

Visit our Delta DVP PLC PDF files page for documentation. The archive record associates this model with the DVP-EH DIDO instruction sheet and the DVP series catalogue. Document language is recorded separately from webpage language; the multilingual sheet is not presented as a Turkish translation.

Related topics

For input-only expansion, see DVP08HM11N, DVP16HM11N and DVP32HM11N. Smaller mixed relay-output modules include DVP08HP11R and DVP16HP11R.

Navigation: Delta main page · Delta PLC · EH expansion modules · DVP PDF archive

External references

Delta DVP manufacturer catalogue (printed pp. 43 and 48). Delta DVP-EH DIDO instruction sheet, 25 April 2008 edition (archived copy of the manufacturer document). Read older specifications together with the equipment label and revision.