Delta DVP16HM11N

Delta DVP16HM11N – 16 Digital Input EH Expansion Module

Delta DVP16HM11N is a 16-point, 24 V DC digital input expansion module in the DVP EH module family. It passes field sensor and contact states to the host CPU. It has no output channels or independent user program. When selecting a Delta PLC system, distinguish the host controller from its input expansion units.

Typical applications include additional pushbuttons, limit switches, photoelectric sensors and inductive sensors. It reads discrete on/off states. The distinction between analog and digital inputs matters: a suitable analog module is required to measure a 0–10 V or 4–20 mA value.

Technical characteristics and input response

I/O: 16 DI / 0 DO. Input type: 24 V DC, Sink/Source. The legacy EH DIDO manufacturer sheet specifies 5 mA nominal input current and an input response of approximately 20 ms. Check pulse duration when selecting inputs for fast signals; the CPU scan adds to the overall response.

The same sheet specifies a 24 V DC operating supply class, 20.4–28.8 V, and 1.5 W module consumption. Overall dimensions are approximately 55 mm wide × 90 mm high × 82 mm deep. Follow the actual unit’s supply and expansion diagram. Never apply mains voltage to X or S/S terminals.

PNP / NPN sensors and the S/S common

For a three-wire PNP sensor, connect the relevant S/S common to 0 V and the sensor output to the selected X input. For an NPN sensor, connect S/S to +24 V; the sensor output then pulls the input toward 0 V. Check sensor power, signal and reference together. Use the manufacturer wiring diagram and actual current path when interpreting Sink/Source terminology.

For a dry-contact test, switch +24 V to X in the PNP arrangement, or switch 0 V to X in the NPN arrangement. Set the common arrangement with power removed. Avoid mixing incompatible PNP/NPN circuits within a common group. Two physical S/S labels alone do not establish two independently isolated input groups.

Host CPU compatibility and model differences

DVP16HM11N appears in the original DVP-EH extension sheet. Delta’s EH2 announcement lists it among DVP-EH2 extensions, while the 2023 DVP catalogue lists it under DVP-EH3 digital modules. Check the exact host CPU, expansion order, total I/O and supply budget. Compatibility with another DVP family must be established separately.

Compare DVP08HM11N for 8 inputs and DVP32HM11N for 32 inputs. DVP16HP11R and DVP16HP11T combine inputs and outputs and serve a different purpose. Preserve the HM, HN or HP designation and complete suffix when ordering; the total point count alone does not identify a replacement.

Programming software and connection cable

No separate program is downloaded to DVP16HM11N. Its inputs are processed as X contacts in the host CPU project using the supported WPLSoft or ISPSoft version. For an ISPSoft connection, select the appropriate driver and COM port in COMMGR. The project CPU selection must match the actual host controller.

Connect the programming cable to the host CPU, not to the input module. For EH3 CPUs, Delta’s cable guide shows UC-PRG020-12A for the COM1 RS-232, 8-pin mini-DIN programming connection. UC-MS020-01A is an alternative with a computer RS-232 port or a suitable USB-to-RS-232 converter. Install the UC-PRG USB driver and select its assigned COM port. A standard USB lead or a cable with a similar plug is not sufficient.

X addressing and commissioning

Local terminal labels are X0–X7 and X10–X17. DVP uses octal X addressing, so X8 and X9 do not occur. Local terminal labels do not necessarily equal the final X addresses in the host program.

Example: after a CPU with 16 inputs, as the first digital input expansion and with no preceding input module, this unit may occupy X20–X37. In this example, local X0 maps to program X20; X7 to X27; X10 to X30; and X17 to X37. Confirm the real allocation from the host I/O sequence and online monitoring. Compare the field signal, input LED and monitored X bit together. The module itself does not require a Modbus station address.

Editor’s Note

Start with a clear photograph of the DVP16HM11N label. A similar-looking Delta unit with 16 points may have a different role. Ask for the host CPU label and expansion connector photographs together.

With power removed, inspect the terminals, DIN rail latch and expansion connection. Corrosion, a broken plug, loose screws or heat damage deserve closer inspection; a clean housing does not prove an electrically sound module.

Test with a compatible CPU while machine movement is disabled. Apply a test signal to all 16 channels in turn. One working input LED is insufficient evidence that the entire unit works.

If the sensor LED operates but the PLC does not see the input, check S/S, the 0 V reference, field wiring and program address first. These checks can prevent an unnecessary module purchase.

For a single faulty channel, remove power before transferring the same test signal to a known-good channel to separate wiring faults from input-circuit faults. If a whole group is affected, investigate the common connection and expansion plug. Electronic repair requires suitable measurements and circuit knowledge.

For a used unit, request a written record of the CPU, channels tested and results. This technical page does not certify that any particular unit has been tested. See used digital input modules for related stock categories.

PDF documents and related topics

Use the Delta DVP PLC PDF files page for the model instruction sheet, series catalogue and host CPU cable selection documents. The original PDFs may be English or multilingual English/Chinese documents; the page language does not change the PDF language.

What is a PLC? · Grounding · DVP expansion modules · DVP PLC series

Navigation: Delta home · Delta PLC · EH modules · DVP files

External references

Delta DVP-EH DIDO manufacturer sheet – legacy edition, English/Chinese · Delta EH2 expansion list · Delta WPLSoft / ISPSoft explanation