Delta DVP08HP11R
Delta DVP08HP11R - 4 Input / 4 Relay Output Digital Extension Module
Delta DVP08HP11R is a mixed I/O module in the DVP-EH extension family, providing 4 digital inputs and 4 relay outputs. Delta lists it in the 24 V DC operating class. It adds I/O controlled by the program in a compatible host PLC.
Check the CPU and hardware revision in DVP-EH and DVP-EH2 installations. Delta also lists the exact model among DVP-EH3 digital extensions. Apply the host CPU’s extension rules and power budget.
Operating voltage and terminal functions
Operating voltage: 24 V DC; the sheet specifies 20.4-28.8 V DC and 1.5 W consumption. The reviewed 08HP terminal drawing shows no separate L-N or +24V/0V operating-supply terminals. Follow the CPU installation instructions for the extension connection: S/S is the input common; C0 is the relay-output common.
Wire the field sensors’ 24 V power supply and the load supply according to their respective circuits. The relay contacts’ ability to switch AC loads does not make mains voltage suitable for the module’s operating supply.
Digital inputs and PNP/NPN wiring
Inputs: X0-X3, four channels; 24 V DC sink/source, nominal 5 mA, approximately 20 ms response. Signals may come from inductive sensors, photoelectric sensors, limit switches or pushbuttons. Connect S/S to 0 V for PNP sensors, or to +24 V for NPN sensors.
Inputs have optocoupler isolation and status LEDs. With approximately 20 ms response, fast encoder pulses or short counting pulses require a suitable high-speed CPU input or dedicated counter module.
Relay outputs and the C0 common
Outputs: Y0-Y3, four relay outputs sharing one C0 common. The detailed terminal table gives voltage limits of 250 V AC / 30 V DC, 1.5 A per output and 5 A per common, with approximately 10 ms response. The same sheet’s selection table states 2 A, so assess loads against the detailed table and the applicable hardware revision.
All four output currents pass through C0, so their total must remain within 5 A. Relay contacts do not generate load voltage; they switch the external supply connected through C0. For inductive loads such as contactor coils, assess inrush, suitable suppression and circuit protection. Relay outputs are intended for switching rather than high-speed pulse generation.
Addressing, software and programming cable
X0-X3 and Y0-Y3 are local terminal labels. Program addresses depend on extension order. For example, the first module after a compatible 16-input/16-output EH CPU may use X20-X23 and Y20-Y23. X/Y numbering is octal; confirm the actual allocation against the installed extension chain.
Which software? The host CPU program reads inputs and commands outputs. Use WPLSoft or ISPSoft where supported by the CPU and software version; Delta documents both tools for EH3. Configure COMMGR and the correct communication driver for ISPSoft. The module has no separate user-program download or independent Modbus station setting.
Which cable? Connect the computer to the host CPU’s programming port. For EH3 COM1 RS-232, examples are the UC-PRG020-12A USB programming cable and UC-MS020-01A serial cable. Check the USB-serial driver and COM port. Select the Delta PLC cable for the host port and pinout.
Related models and selection differences
DVP08HP11T provides 4 inputs/4 transistor outputs; DVP08HN11R provides 8 relay outputs; DVP08HM11N provides 8 digital inputs. DVP16HP11R has 8 inputs/8 relay outputs. The larger DVP32HP00R is a different AC-powered 16/16 unit. Recheck point count, output technology, supply and addressing when changing models.
Editor’s Note
For used equipment, request clear photographs of the DVP08HP11R label and extension connector. The R/T suffix and HP/HN/HM letters identify different functions.
All four relay outputs share C0. If every output fails, check the common supply, terminal and protection before assuming four failed relays.
A relay click is insufficient proof. Test each channel with a suitable controlled load and verify that the contact opens again when its command is removed.
Apply a controlled 24 V input signal with the correct S/S wiring. Compare the terminal LED with the actual CPU address to distinguish field wiring from module faults.
For welded contacts or overheated terminals, investigate load inrush and coil suppression. Check grounding and fuses as well; replacing a relay leaves the cause unresolved if the overload remains.
Back up the CPU program and photograph the extension order before removal. Disconnect power before handling extension connectors, and prevent machine movement during the first test.
PDF files and related topics
Use our Delta DVP PLC files page for the manufacturer sheet, catalogue and cable documentation. Identify the host CPU family before choosing the required DVP extension module.
Navigation: DVP08HP11R main page · DVP-EH modules · Delta PLC · Used Delta equipment · Used digital input modules.
External references
DVP-EH DIDO installation and wiring sheet - legacy 2008 edition · Delta DVP/TP catalogue - EH3 extension models · Delta PLC/HMI cable selection guide - host CPU connection