Delta DVP16HP11R
Delta DVP16HP11R – 8 Digital Input / 8 Relay Output Extension Module
Delta DVP16HP11R belongs to the Delta DVP-EH extension family and provides 8 digital inputs plus 8 relay outputs. Its 16-point designation means 16 combined I/O points. It is an extension module; the PLC control program runs in the connected main CPU.
The exact model is listed in the DVP-EH3 catalogue. For an existing DVP-EH or DVP-EH2 installation, check the CPU model, extension order and power budget together. Typical uses include expanding digital I/O for pushbuttons, limit switches, inductive sensors and photoelectric sensors, with relay switching for suitable control loads.
Main technical characteristics
Operating supply class: 24 V DC, with a specified range of 20.4–28.8 V DC and consumption of 2 W. Approximate dimensions are 55 mm wide × 90 mm high × 82 mm deep; operating temperature is 0–55 °C. Consider DIN rail mounting and grounding when planning the cabinet.
Inputs: 8 sink/source 24 V DC digital inputs, approximately 5 mA nominal input current and 20 ms response. Input circuits use optocoupler isolation and status LEDs. These digital inputs serve ordinary on/off signals rather than analog measurements or high-speed encoder counting.
Outputs: 8 relay outputs. The sheet specifies switching voltage limits of 250 V AC / 30 V DC and approximately 10 ms relay response. Mechanical contacts are unsuitable for the high-speed pulse outputs required by pulse-commanded servo or stepper systems.
S/S, C0 and load wiring
Local terminal labels are X0–X7 for inputs and Y0–Y7 for outputs. S/S is the input common; C0 is shared by all eight relay outputs. Neither is a separate module operating-power terminal. Match the terminal plan on the actual unit to the main CPU’s extension instructions.
PNP/NPN selection determines the input-common connection: connect S/S to 0 V for PNP-output sensors, or to +24 V for NPN-output sensors. Check the sensor supply and complete signal return path. Relay C0–Y contacts switch the external load circuit; an output does not generate 24 V. Different voltage sources must not be connected to outputs sharing C0.
Understanding the 2 A and 1.5 A relay figures
The manufacturer’s model-selection table states 2 A per point, while its detailed electrical table specifies 1.5 A per point and 5 A per common for resistive loads. Treat 2 A as requiring clarification for the actual revision and load. Eight outputs at 1.5 A each would total 12 A, exceeding the 5 A C0 limit. Inductive-load inrush and contact life require separate assessment.
Suitable reverse-parallel diode suppression for DC coils, appropriate suppression for AC coils, and correctly selected load-circuit fuses help protect the contacts. Select an appropriate intermediate switching device for motors or loads with substantial inrush.
CPU compatibility and addressing
Printed X0/Y0 terminal labels do not determine the final program addresses. As an illustrative first digital extension after a 32EH CPU with 16 inputs and 16 outputs, DVP16HP11R can occupy X20–X27 and Y20–Y27. Other installed extensions change the allocation. DVP X/Y addresses use octal numbering: 10 follows 7. Confirm the actual allocation from the installed hardware order.
Programming software and connection cable
No separate program is downloaded to DVP16HP11R. PLC programming takes place in the main CPU. For EH-family systems, use WPLSoft or ISPSoft with support for the actual CPU and revision. Select the correct CPU type when opening the project. The programming language and software version follow the CPU and existing project.
For an EH3 COM1 RS-232 connection: the manufacturer’s cable guide shows UC-PRG020-12A, a 2 m active USB programming cable for the CPU’s 8-pin mini-DIN RS-232 interface. Install the appropriate USB driver and select the resulting COM port; also check the COMMGR communication channel used with ISPSoft.
For a computer with a real RS-232 port, UC-MS020-01A is the serial-cable option. A USB-only computer additionally requires a suitable USB-to-RS-232 converter. Connect to the main CPU. The extension module has no independent RS-485/Modbus station address.
Differences between nearby model codes
DVP16HP11T also has 8 inputs and 8 outputs, but uses transistor outputs and requires the corresponding load wiring. DVP08HP11R provides 4 inputs/4 relay outputs; DVP16HM11N provides 16 inputs only; DVP08HN11R provides 8 relay outputs only. Similar codes require a function and wiring check before replacement.
Editor’s Note
Start by checking that the nameplate actually says DVP16HP11R. The final letter matters: relay and transistor versions can look similar while requiring different load circuits.
A relay click or illuminated output LED does not prove that the contact carries a load correctly. Check each channel with a safe, low-voltage, current-limited test load.
If several outputs fail together, inspect C0, the terminal connections and the load supply before replacing every relay. A shared connection fault can make otherwise functional channels appear defective.
During fault finding, compare the sensor signal, S/S connection, input LED and monitored CPU bit in sequence. Establish where the signal disappears before changing components.
For relay replacement, check the coil rating, contact-load category, pin arrangement and board condition. A replacement relay will not remove the cause of an earlier overload.
Back up the CPU program, isolate machine movements and remove all forced states after testing. Provide the required emergency-stop and interlocking circuits as part of the machine safety design.
Manuals and PDF documents
Use our Delta DVP PLC PDF files page for the installation sheet, EH3 module-selection catalogue and main-CPU cable guide. Match the full model and document edition. Page language and PDF language are separate: the English page may link to a multilingual original document.
Related topics
For module selection, see Delta DVP extension modules and EH modules. For system planning, browse Delta DVP PLC series.
Delta home | Delta PLC models | DVP series | EH extension modules | DVP PDF files
External references
Delta DVP-EH DIDO manufacturer sheet – legacy 2008 edition; Delta DVP/TP manufacturer catalogue – EH3 ordering table; Delta PLC/HMI Cable Selection Guide; Delta’s WPLSoft/ISPSoft explanation. PDFs are in English; the installation sheet also contains Chinese sections.