Delta DVP16HP11T
Delta DVP16HP11T – 8-Input / 8-Transistor-Output Digital Expansion Module
Delta DVP16HP11T is a 24 V DC mixed digital expansion module adding 8 digital inputs and 8 NPN/sinking transistor outputs to a compatible DVP-EH host. It does not execute an independent PLC program; its input and output circuits exchange field signals with the host CPU. Delta lists the exact model in its DVP-EH3 ordering table.
Typical duties include pushbutton, limit switch, inductive sensor and photoelectric sensor signals, together with small DC control loads. The DVP16HP11R relay version requires different output wiring. DVP16HP11T outputs switch DC loads; AC power and motor supply circuits must not be connected directly to them.
Power, dimensions and host compatibility
Module supply: 24 V DC, permitted range 20.4–28.8 V DC. The instruction sheet specifies 2 W consumption for the 16HP11R/T group; this does not include the total field-load power. Size the 24 V DC power supply for the module, sensors and output loads together. This model does not provide the 500 mA service supply specified for the larger AC-powered HP00 units.
Dimensions: approximately 55 × 90 × 82 mm (width × height × depth), with 35 mm DIN rail or screw mounting. Operating temperature is 0–55°C. Connect the side expansion interface with power removed. For DVP-EH, DVP-EH2 and DVP-EH3 installations, check the exact CPU, expansion order and system limits. The EH3 catalogue listing does not establish compatibility with every Delta PLC family.
Digital inputs and PNP/NPN wiring
8 inputs, 24 V DC, approximately 5 mA per input, with optical isolation and LED indication. ON threshold: above 16.5 V; OFF threshold: below 8 V; response time: approximately 20 ms. These are switching inputs, not analog measurement inputs or high-speed encoder inputs. Optocoupler isolation does not establish individual isolation between channels.
For PNP sensors, connect S/S to 0 V; for NPN sensors, connect S/S to +24 V. Connect the sensor output to the required X terminal. Check NPN versus PNP and sink/source behaviour before transferring wiring. Inputs sharing an S/S group use the same reference; do not mix PNP and NPN sensors indiscriminately on that common connection.
Transistor outputs, C0 and load limits
The 8 outputs are NPN/sinking, open collector. In the terminal layout, Y0–Y7 share C0. Connect C0 to the load supply’s 0 V reference, and connect each load between +DC and its Y terminal. Arrange module and field-circuit references according to the manufacturer’s diagram. These outputs are not relay dry contacts.
DC load voltage: 5–30 V DC in the selection table. Resistive-load limits per output are 0.3 A at 40°C, 0.2 A at 45°C, 0.15 A at 50°C and 0.1 A at 55°C. The C0 total must also remain within 2 A; eight simultaneous 0.3 A loads would exceed it. Check inductive loads and inrush separately. Use a suitable interface driver for contactors and larger loads.
Electrical switching times are approximately 15 µs ON and 25 µs OFF. These figures do not establish support for the CPU’s high-speed pulse instructions on expansion outputs. Fit a suitable reverse-parallel diode or other appropriate suppression to DC coils. Select fuses and wire sizes for the load circuit and prospective short-circuit current.
Addressing and an example
Local terminal labels are X0–X7 and Y0–Y7; addresses used by the CPU depend on the expansion order. DVP X/Y numbering is octal. For example, as the first digital expansion after a compatible EH CPU with 16 inputs and 16 outputs, a suitable system arrangement assigns X20–X27 and Y20–Y27. A different CPU or preceding modules changes the allocation.
In a test project with this allocation confirmed, LD X20 followed by OUT Y20 makes the first input operate the first output. Add the machine’s permissives and interlocks to the ladder program. DVP16HP11T uses digital X/Y addresses, rather than analog-module CR setup or a FROM/TO template.
Programming software and cable
DVP16HP11T has no separately downloadable user program. Develop the host CPU project with WPLSoft or ISPSoft as supported by the exact CPU and software release. Configure COMMGR when required for ISPSoft communication. Select the actual host CPU as the project target, rather than DVP16HP11T, and back up an existing project before conversion.
For example, an EH3 CPU’s 8-pin mini-DIN RS-232 COM1 port can use the UC-PRG020-12A USB-to-RS-232 programming cable. Alternatively, use a UC-MS020-01A serial cable with a suitable PC RS-232 port or USB-to-RS-232 converter. The programming cable connects to the CPU, not to this module’s X/Y terminals. Check the cable driver, COM number, CPU port settings and pinout.
Editor’s Note
Start with the complete 16HP11T label. A similar enclosure is no reason to reuse the relay version’s wiring unchanged. Check C0 and the load supply before connecting the replacement.
If an input LED stays off, check S/S, sensor type and the voltage between X and the common reference while the sensor operates. An incorrect PNP/NPN common connection can make a healthy input appear faulty.
If an output LED is on but its load does not operate, check the C0 return, field supply and cable. Interpret multimeter readings together with a suitable small test load; an LED alone does not prove the transistor works under load.
Test every input and output on a used module, one at a time, with a current-limited DC supply and a low-current load. Look for discoloured terminals, loose screws, corrosion and bent expansion contacts.
After an output failure, inspect the coil, suppression device and field wiring before fitting another module. Otherwise the replacement may fail for the same reason. Keep protective grounding and signal 0 V functions clear, following the cabinet schematic.
Disconnect loads that could cause movement during online monitoring or output-forcing tests. Preserve the program and address backup, and retain the necessary hardware interlocks when returning the machine to operation.
PDF documents
Use the Delta DVP PLC files page for installation, terminal layouts, power and output limits. The archived documents for this article are the DVP-EH DIDO instruction sheet, DVP catalogue and PLC/HMI cable selection guide. PDFs retain their original languages; the TR/EN articles do not imply translated manufacturer PDFs.
Related topics and navigation
Related models: DVP16HP11R provides 8 inputs and 8 relay outputs; DVP08HP11T provides 4 inputs and 4 transistor outputs; DVP16HM11N provides 16 inputs; DVP08HN11T provides 8 transistor outputs. Their duties and wiring differ, so they are not direct equivalents.
Delta main page | Delta PLC | DVP PLC series | DVP expansion modules | DVP EH modules | DVP16HP11T model page | DVP PDF files
External references
Delta DVP-EH DIDO instruction sheet – archived 2008-04-25 edition; DVP-EH DIDO – DVP-0061130-01, 2024-02-21 edition, online review; Delta DVP catalogue – DVP16HP11T ordering row, printed page 43; Delta PLC/HMI Cable Selection Guide – 2019-08-15; Delta WPLSoft / ISPSoft explanation. Delta Electronics is the manufacturer; check the edition and equipment label when using copies hosted by external archives.