Delta DVP Slim analog modules add voltage and current channels to compatible DVP PLCs. AD modules read field signals, DA modules send analog commands, and XA modules combine both. Count the inputs and outputs separately, then match the 0–10 V or 4–20 mA signal range and the expansion side of the CPU.
Model selection and individual module pages
| Delta model | CPU side | Channels and selection criteria |
|---|---|---|
| DVP04AD-S | Right | 4 single-ended analog inputs |
| DVP04AD-S2 | Right | 4 differential analog inputs |
| DVP06AD-S | Right | 6 single-ended analog inputs |
| DVP02DA-S | Right | 2 analog outputs |
| DVP04DA-S | Right | 4 analog outputs |
| DVP04DA-S2 | Right | 4 analog outputs, S2 terminal and CR assignments |
| DVP06XA-S | Right | 4 single-ended analog inputs + 2 analog outputs |
| DVP06XA-S2 | Right | 4 differential analog inputs + 2 analog outputs |
| DVP04AD-SL | Left | 4 differential analog inputs, 250 µs/channel |
| DVP04DA-SL | Left | 4 analog outputs, 250 µs/channel, including ±10 V mode |
A single-ended input measures against a common reference. A differential input measures the voltage difference between its input terminals. Check the module’s isolation specifications if the application requires channel-to-channel isolation. Delta specifies 3 ms/channel for the DVP04AD-S2 and DVP06AD-S and 250 µs/channel for the SL models. Total response also depends on the channel count, averaging and the CPU scan.
Match the module to the application
Measurement. Read the device label to identify the analog signal. Use an analog input for a pressure transmitter or hydrostatic level measurement. When using a voltage-output potentiometer or analog encoder, match the supply, reference and operating range.
Command. An analog output can send a speed reference to a variable frequency drive or a position command to a proportional valve. In pump control, an XA module can save cabinet space when the system reads pressure and sends a speed command. For PID control, see PID control with PLCs. Display the process reading, setpoint and output percentage separately in SCADA.
Output range and load. For example, the DVP04DA-S2 requires a load of at least 1 kΩ in its 0–10 V and 2–10 V modes, and at most 500 Ω in its 0–20 mA and 4–20 mA modes. Match the programmed output mode to the downstream device’s input setting.
Scaling example. A 0–10 bar transmitter with a 4–20 mA output gives 0 bar at 4 mA, 5 bar at 12 mA and 10 bar at 20 mA. In the appropriate 4–20 mA input mode, the 2026 manual gives nominal raw ranges of 0–4000 for DVP04AD-S2, 0–1000 for DVP06XA-S2 and 0–32000 for DVP04AD-SL. At 5 bar the respective values are about 2000, 500 and 16000. Verify the channel mode and hardware revision, then test both endpoints. Handle low-current or open-loop alarms separately from the process reading.
CPU compatibility, software and cables
Check the complete PLC model number, the right or left expansion connector, the 24 V DC supply and the CPU’s expansion limit. Find individual CPU codes under DVP-SA2, DVP-SX2, DVP-SV2 and DVP-EH3-L. For an SL module, verify the left-side connector and CPU support for that specific module.
For PLC programming, use WPLSoft or ISPSoft as supported by the CPU. ISPSoft configures the connection through COMMGR. Match the cable to the CPU port. For example, use DVPACAB2A30 on DVP CPUs that support this cable on their 8-pin Mini‑DIN RS‑232 COM1 port, or a data-capable Mini‑USB cable on a DVP‑SX2 fitted with that port. For projects using FROM and TO, check the module number and control register (CR) address for the exact module. Delta’s manual numbers the closest right-side module 0 and the closest left-side analog module 100. Modbus RS‑485 is a separate option on modules with a built-in serial port that support this operating mode. Delta PLC software
Editor’s Note
When buying used, start with a clear photo of the label. Check the -S, -S2 or -SL suffix, the mounting side, the removable terminal block and the expansion connector.
If a two-wire 4–20 mA transmitter gives no reading, check the loop supply and return path first. Follow the exact module’s wiring diagram for any required terminal jumper.
If readings jump when the motor runs, check signal cable routing, shield termination and grounding before adjusting the filter.
Before testing an output, confirm the voltage or current setting and load impedance at the drive or valve input. Use a suitable test load and a multimeter to verify the low, midpoint and high commands.
During a replacement, compare channel modes, CR addresses and raw scaling against the saved project. During PLC monitoring and troubleshooting, verify how outputs respond to PLC STOP, power interruption and signal loss before commissioning.
Related topics
See Slim temperature modules for direct Pt100 or thermocouple measurement, and Slim load cell modules for bridge-type mV/V weighing signals.
Slim digital modules · Slim specialty modules · Slim positioning modules · Slim communication modules
OtomasyonAVM PDF files and Delta pages
Delta DVP PLC PDF files · DVP expansion modules · DVP PLC series · Delta PLCs · Used Delta Automation
External references
Delta DVP Module Manual, 2026 (EN, PDF) — right-side analog modules in Chapter 8 and high-speed left-side modules in Chapter 11. Delta DVP catalog (EN, PDF) — legacy S models and ordering codes. Delta software support — WPLSoft and ISPSoft.