Delta DVP04AD-S
Delta DVP04AD-S – Four-Channel Analog Input Module
Delta DVP04AD-S is a four-channel voltage/current input module in the DVP Slim analog module family. It converts analog signals from sensors and transmitters into numerical values for the PLC program. Its analog inputs accept ±10 V DC or ±20 mA signals; the selection requires both the correct wiring and channel mode.
Analog-to-digital conversion allows pressure, level and similar process values to be monitored. Unlike a digital input, the result represents a measured quantity rather than only an ON/OFF state. Documented CPU families include DVP-SS/SA/SX/SC/SV. Verify the exact CPU's expansion support when using another generation.
Technical specifications
Voltage input: ±10 V; nominal digital range −8000…+8000; resolution 14 bits / 1.25 mV. Current input: ±20 mA; nominal digital range −4000…+4000; resolution 13 bits / 5 µA. These describe the basic characteristic; the selected mode and modified OFFSET/GAIN settings affect scaling.
Power: External 24 V DC, 20.4–28.8 V; maximum consumption 2 W. Use a suitable 24 V power supply. DVP04AD-S input impedance is 200 kΩ for voltage and 250 Ω for current. Include these values when assessing analog-voltage source loading and the current-loop burden.
Conversion time: 3 ms × number of channels, approximately 12 ms for four channels. CPU scan and averaging can add delay. Manufacturer accuracy is ±0.5% of full scale at 25 °C and ±1% over the 0–55 °C operating range. Resolution and measurement accuracy are different specifications.
Isolation: The analog and digital circuits are isolated, but the analog channels are not isolated from one another. Assess reference potentials and additional signal isolation when connecting devices with different ground potentials. Values are transferred as signed 16-bit two's-complement data.
0–10 V and 4–20 mA wiring
Voltage measurement: Connect signal positive to the channel V+ terminal and signal return to COM. Select a suitable voltage mode for a 0–10 V sensor. Current measurement: Bridge V+ to I+ on the selected channel, connect the current signal to that point and its return to COM. Check both the bridge and mode for a 4–20 mA sensor.
A two-wire pressure transmitter needs an external loop supply; the module input is not a self-contained sensor power source. Check the active/passive output arrangement of the pressure sensor or other analog sensor. Assess shield/FG connections separately from the COM signal return.
Route analog cables away from motor and drive power cables. Follow the manufacturer's grounding and shield diagram, and leave unused terminals unconnected. Confusing voltage and current measurement, or applying a voltage source to a current input, can damage the module.
Channel modes and scaling
CR#1 selects channel modes: CH1 uses b2…b0, CH2 b5…b3, CH3 b8…b6 and CH4 b11…b9. Mode 0: −10…+10 V. Mode 1: −6…+10 V. Mode 2: −12…+20 mA with a 4 mA offset characteristic. Mode 3: −20…+20 mA with zero offset. Mode 7 channel disabling is identified in the shared sheet as a DVP04AD-S2-only feature.
With factory conversion curves: In Mode 0, 0/5/10 V gives approximately 0/4000/8000. In Mode 2, 4/12/20 mA gives approximately 0/2000/4000. In Mode 3, the same 4/12/20 mA gives approximately 800/2400/4000. Do not apply one raw-value range to every 0–10 V and 4–20 mA application.
Calculation example: For a 4–20 mA = 0–10 bar transmitter, Mode 2 and unchanged conversion settings, Pressure (bar) = raw value × 10 / 4000. A raw value of 2000 represents 5 bar. Use suitable 32-bit or floating-point arithmetic to avoid overflow or premature rounding.
Programming, FROM/TO and connection cable
No separate Ladder application is downloaded to the module. Create the PLC program in WPLSoft or ISPSoft as supported by the host CPU; ISPSoft communication uses COMMGR. The Ladder program accesses the module's 49 sixteen-bit control registers through FROM/TO instructions. The module does not consume digital X/Y I/O points.
Read example: If the card is first in the special-module order, FROM K0 K6 D100 K4 reads the CH1–CH4 average values into D100–D103. Present values are in CR#12–CR#15. Change K0 for a different module position and ensure that D100 is available in the actual project.
Setting example: For all four channels in Mode 2, CR#1 is H0492. An initialization-routine instruction example is TO K0 K1 H0492 K1. CR#2–CR#5 set averaging, CR#30 reports errors and CR#34 reports firmware. For model verification, the low byte of CR#0 is H88 for DVP04AD-S and H90 for DVP04AD-S2.
The default averaging count is 10. Edition distinction: The 2021 shared sheet lists K1–K20, while the 2004 DVP04AD-S sheet lists K1–K4096. Verify the allowed upper limit for the installed module/firmware. Larger averaging counts slow the measurement response.
The programming cable connects to the CPU. Where the CPU uses an 8-pin mini-DIN RS-232 port, suitable connections include UC-MS020-01A (2 m) or UC-MS030-01A (3 m), and UC-PRG020-12A (2 m) for the PC USB side. Verify the CPU port and cable selection; install the USB-cable driver and select the correct COM port.
Standalone RS-485 / Modbus operation
The module's own RS-485 interface supports Modbus ASCII/RTU access. Its standalone RS-485 access is disabled when the module operates on the CPU expansion bus; use FROM/TO in that arrangement. Standalone operation requires a 24 V supply and a suitable RS-485 master/converter.
The listed defaults are 9600 baud, 7E1, ASCII, station 1. CH1 average is CR#6 at H4006; CH1 present value is CR#12 at H400C. Check whether the master displays zero-based or one-based addresses. DVP04AD-S firmware V4.10 and earlier uses fixed serial formats; V4.11 and later adds configurable data formats.
Related analog modules
DVP04AD-S2 and DVP04AD-SL are separate generation/model options. Consider DVP06AD-S for more analog inputs, DVP06XA-S for mixed input/output requirements and DVP04DA-S for analog outputs. Compare CPU compatibility, terminal order, input impedance and program scaling when selecting analog I/O.
Editor's Note
A POWER light is only a starting point when assessing a used analog card. Verify the DVP04AD-S label, then read the CR#0 model code and CR#34 firmware information.
Test voltage at known points such as 0, 5 and 10 V, and current at 4, 12 and 20 mA, with the correct wiring and mode. Check all four channels individually; one good channel does not establish that the others work.
Select the current calibrator's SOURCE/SIMULATE function to match the loop. Check the bridge, input mode and loop supply before diagnosing a board fault.
For unstable readings, inspect supply ripple, shielding, COM wiring and the difference between averaged and present values before changing OFFSET/GAIN. Perform resistance and short-circuit checks with power isolated.
Before repair, record CR#18–CR#21 OFFSET and CR#24–CR#27 GAIN values. Test the module and field sensor separately with a reference source when tracing an analog-measurement fault. Check the fuse and supply protection as well.
For a used-unit sale, state quantity, label photographs, working/faulty condition and channel test results. Sales require an invoice; no returns; workshop testing is available. Sellers can send details to otomasyonavm@gmail.com.
PDF documents and related topics
For wiring, control registers and conversion curves, visit our Delta DVP PLC files page first. The shared DVP04AD-S/DVP04AD-S2 manufacturer sheet dated 24 February 2021 contains English and Chinese sections. Observe the terminal and specification distinctions between the two models.