Delta DVP04DA-S2

Delta DVP04DA-S2 — Four-Channel Analog Output Module

Delta DVP04DA-S2 is a right-side expansion module that adds four analog voltage or current outputs to supported DVP Slim PLCs. It turns a digital PLC command into a reference signal for devices such as variable frequency drives, recorders and proportional valve controllers. Each channel has its own output mode.

Power, wiring and load

The analog circuit uses an external 24 V DC supply with an allowed range of 20.4–28.8 V DC. Use the channel’s Vn+ and COM terminals for voltage, or In+ and COM for current. On CH1, the signal terminal is V1+ for voltage or I1+ for current.

The receiver load for a voltage output must be at least 1 kΩ. For a current output, the total loop load, including cable and receiver, must be at most 500 Ω. The voltage output can supply up to 10 mA. The analog channels share a common reference. Route shielded signal cables away from power wiring. The manual specifies 3 ms per channel response time.

Output modes and scaling

CR#1 selects each channel’s mode. Mode 0 is 0–10 V, mode 1 is 2–10 V, mode 2 is 4–20 mA and mode 3 is 0–20 mA. The 2026 module manual lists mode 4 for 0–5 V and mode 5 for 1–5 V with firmware V5.00 or later.

The nominal command range is K0–K4000 for every mode. Hardware resolution is 12-bit for the standard 10 V and 20 mA ranges and 11-bit for the 5 V ranges. With the factory curve in 0–10 V mode, K2000 = 5 V. In 4–20 mA mode, K0 = 4 mA, K2000 = 12 mA and K4000 = 20 mA. The physical output at K0 depends on the selected mode.

PLC registers and command example

CR#0 reports the model code, H91 for DVP04DA-S2. CR#1 holds the channel modes. CR#6, CR#7, CR#8 and CR#9 hold the commands for CH1 through CH4 respectively. Read CR#30 for error status and CR#34 for firmware. Within CR#1, CH1 uses bits 2–0, CH2 uses 5–3, CH3 uses 8–6 and CH4 uses 11–9.

The first special module on the CPU’s right-side bus is numbered K0. In this bench example, TO K0 K1 H0002 K1 sets CH1 to 4–20 mA and CH2–CH4 to 0–10 V. TO K0 K6 K2000 K1 commands 12 mA on CH1. On an existing machine, check all four channel settings before writing CR#1. Use FROM to read a CR.

Host, programming cable and RS-485

Check the exact DVP-SS2, DVP-SA2, DVP-SX2, DVP-SV2 or DVP-SE CPU and its right-side expansion support. Edit the host PLC program using WPLSoft or ISPSoft according to CPU support. For CPUs covered by the cable guide with a COM1 mini-DIN RS-232 port, use UC-PRG020-12A for USB or UC-MS020-01A for serial connection. Configure the ISPSoft connection in COMMGR.

The module’s own RS-485 port provides CR access through Modbus ASCII/RTU. CR#31 sets the station address and CR#32 the serial format. CH1–CH4 command registers have protocol addresses 0x4038–0x403B, or 16441–16444 in software that uses one-based holding register numbers. Check station and port settings at both ends when commissioning Modbus RTU.

Editor’s Note

On a used unit, check the DVP04DA-S2 label, removable terminals and expansion connector. Reading CR#0 = H91 is another way to confirm the model.

If the PLC command changes and there is no output, measure the 24 V supply at the module first. Then check the selected mode and whether the load is wired to the voltage or current terminal.

Use a suitable bench test load. In 0–10 V mode, try commands of 0, 2000 and 4000 and measure all four channels. Put the meter in series when measuring current.

If the value fluctuates when the drive runs, check the shield, COM return and cable routing for electrical interference. Include the receiver and cable in the current loop load calculation.

Measure the output on the RUN-to-STOP transition during commissioning. The 2026 manual says firmware V5.00 and later sets the output to the lower limit of the selected range. For a channel set to 4–20 mA, that is 4 mA.

PDF documents

See Delta DVP PLC files for terminal wiring, CR tables and cable references. In the 2026 module manual, 8.4.4 covers the registers and 8.5.6 shows the terminal wiring.

Related modules and topics

DVP04DA-S is the previous four-output generation. DVP02DA-S provides two outputs. DVP04DA-SL mounts on the left. DVP06XA-S2 combines analog inputs and outputs. DVP04AD-S2 provides analog measurement inputs.

DVP04DA-S2 main page · DVP Slim analog modules · DVP expansion modules · Delta DVP PLC series · Second-hand Delta products

External references

Delta DVP Series Module Manual (2026, EN) · Delta DVP04DA-S/S2 instruction sheet (2021, EN/ZH) · Delta PLC/HMI Cable Selection Guide (EN)