Delta DVP02DA-S
Delta DVP02DA-S – 2-Channel Analog Output Module
The Delta DVP02DA-S adds two analog outputs to compatible Delta DVP Slim PLC systems. It converts a digital command from the PLC program into a voltage or current signal. Typical uses include sending a speed reference to a drive such as the Delta VFD-E or a setpoint to a compatible analog controller.
Output ranges and scaling
CH1 and CH2 can be configured individually. In CR#1, mode 0 = 0–10 V, mode 1 = 2–10 V, mode 2 = 4–20 mA and mode 3 = 0–20 mA. The basic 0–10 V and 0–20 mA ranges have 12-bit resolution, with steps of 2.5 mV and 5 µA respectively. Delta specifies a response time of 3 ms per channel.
The nominal command range is K0–K4000. With factory scaling, K2000 produces approximately 5 V in 0–10 V mode and 12 mA in 4–20 mA mode. In 4–20 mA mode, K0 is approximately 4 mA and K4000 is approximately 20 mA. Configure the receiving device’s analog input for the same range.
V+, I+, COM and 24 V DC wiring
Use the channel’s V+ and COM terminals for voltage output or I+ and COM for current output. The voltage input load must be at least 1 kΩ. In current mode, the total loop load must be 500 Ω or less. Include the receiving input, cable resistance and any series measurement resistor when calculating the loop load.
Connect an external 24 V DC supply to the module’s 24V and 0V terminals. The permitted supply range is 20.4–28.8 V DC. Route analog cables away from power wiring. Follow Delta’s wiring diagram and the panel’s grounding arrangement for the shield, FG and protective earth. The two analog channels share a non-isolated analog circuit.
CR addresses and FROM/TO instructions
The module connects to the compatible CPU’s right-side expansion bus. Use TO to write and FROM to read. CR#0 reports the model code (H0049), CR#1 sets the channel modes, CR#10 holds the CH1 command, CR#11 holds the CH2 command and CR#30 reports error status. The special module closest to a compatible CPU is numbered K0.
For example, with the DVP02DA-S at K0 and CH1 in 0–10 V mode, TO K0 K10 K2000 K1 writes a reference of approximately 5 V to CH1. FROM K0 K30 D100 K1 reads the error status into D100. Confirm the module number if the expansion order has changed.
For standalone operation, the module’s RS-485 port supports Modbus ASCII and Modbus RTU. On the serial interface, the CH1 command is at H403C and the CH2 command is at H403D. Delta’s model sheet specifies that the module’s RS-485 port is disabled when it is attached to the PLC expansion bus.
Programming software and cable
Download the program to the host CPU. For CPUs such as the DVP-SS2, DVP-SA2 and DVP-SX2, select a compatible version of WPLSoft or ISPSoft. In ISPSoft, select the connection through COMMGR. For the SS2 CPU’s COM1 RS-232 port, use the UC-PRG020-12A or the UC-MS020-01A with a PC serial port. The UC-PRG015-01A is an option for the SX2’s mini-USB port.
Editor’s Note
When buying a used unit, confirm the DVP02DA-S marking and inspect the terminal block and side expansion connector.
On the bench, measure the 24 V supply at the module terminals. Then read CR#0 to confirm the CPU sees the correct module.
In voltage mode, connect a multimeter across V+ and COM and test K0, K2000 and K4000 in turn. Repeat on both channels.
In current mode, measure in series with the test load. Across a 250 Ω resistor, 4, 12 and 20 mA produce approximately 1, 3 and 5 V respectively.
If the reading is off, check the CR#1 channel mode, V+/I+ terminal selection and receiver input range before adjusting calibration. Then read CR#30 for error status.
Related models and topics
The DVP04DA-S and DVP04DA-S2 have four analog outputs. The DVP06XA-S combines analog inputs and outputs. The DVP04AD-S provides four analog measurement inputs. For a reference adjusted manually at the panel, the standalone Derell DTPV-37 and Derell DTPM-37 digital potentiometers provide 0–10 V and 4–20 mA respectively.
What is an analog signal? · Where are analog signals used?
Manual and wiring diagram
The DVP-S analog I/O chapter of the DVP Series Module Manual covers output wiring and control registers. See the Delta DVP PLC files page for series documentation.
DVP02DA-S · DVP Slim analog modules · Used Delta PLC models · Delta Automation