Delta DVP06XA-S2
Delta DVP06XA-S2 4-Input 2-Output Analog Module
The Delta DVP06XA-S2 is a 4-input, 2-output analog expansion module in the DVP Slim analog module family. CH1–CH4 read signals from pressure, level and other transmitters. CH5–CH6 can send a speed reference to a drive or a command to a proportional valve. Each channel can be set to voltage or current mode.
See Delta DVP PLC files for the terminal diagram, operating modes and register map.
Analog input and output specifications
CH1–CH4 inputs. Standard voltage modes are −10 to +10 V and −6 to +10 V (12 bits). Standard current modes are −20 to +20 mA and −12 to +20 mA (11 bits). Module firmware V5.00 or later adds 4–20 mA (10 bits), 0–10 V (12 bits) and 0–5 V (11 bits). Input impedance is at least 1 MΩ for voltage and 250 Ω for current. Response time is 3 ms per channel.
CH5–CH6 outputs. Select 0–10 V, 2–10 V, 0–20 mA or 4–20 mA. Each output has 12-bit resolution and a nominal command range of 0–4000. Load impedance must be at least 1 kΩ for voltage output and at most 500 Ω for current output.
Supply and isolation. External 24 V DC (20.4–28.8 V DC), up to 2 W. Compared with the DVP06XA-S, the S2 isolates the analog circuit from the digital circuit. The analog channels share one isolation group.
Compatible PLCs, software and programming cables
The module connects to the right-side expansion bus of a compatible DVP Slim CPU. Check the specific CPU model and its special-module limit for DVP-SS2, DVP-SA2, DVP-SX2, DVP-SV2 and DVP-SE units. The special module closest to the CPU is numbered K0. Analog channels require no digital X/Y points.
Open the PLC project in WPLSoft or ISPSoft, according to CPU support. For example, use the UC-PRG020-12A cable on COM1 RS-232 for the DVP14SS211R. For the DVP12SE11R, you can use the CPU Ethernet port with an RJ45 network cable. See DVP programming cables for other CPUs.
Control registers and 4–20 mA scaling
The PLC accesses the side-bus module with FROM/TO. CR#0 holds the model code (H’D4) and CR#34 holds the module firmware version. CR#1 selects channel modes, CR#6–9 hold averaged inputs, CR#12–15 hold present inputs, CR#10–11 set output commands, and CR#30 reports errors. The module’s RS-485 port supports Modbus ASCII/RTU in standalone use. Delta’s instruction sheet says this port is unavailable when the module is attached to the CPU expansion bus.
4–20 mA input. On V5.00 or later, mode 4 maps 4–20 mA to 0–1000 raw counts. On earlier firmware, use mode 3 (−20 to +20 mA). With factory gain and offset, 4, 12 and 20 mA give about 200, 600 and 1000 counts. Scale the applicable raw range to the transmitter’s measuring range in the PLC.
4–20 mA output. In mode 2, commands of 0, 2000 and 4000 give about 4, 12 and 20 mA, respectively. Delta’s 2026 manual specifies that on V5.00 or later the output goes to the low end of its configured range in STOP. For this mode, the low end is 4 mA.
Editor’s Note
Check the S2 label. On a used module, inspect the exact model label, removable terminals and side-bus connector. Use CR#0 to confirm the module model from the PLC.
Check the jumper for current input. Switch off power and bridge the channel’s V+ and I+ terminals as shown in Delta’s wiring diagram. For CH1, these are V1+ and I1+. Remove the jumper for voltage input.
Test both outputs under load. Check CH5 and CH6 separately with a suitable test load before commissioning. Measure both outputs again when the PLC enters STOP.
Read raw counts before checking the HMI percentage. Apply low, midpoint and high signals with a calibrator. If counts are correct, check the PLC or HMI scaling.
Check cable routing if the signal fluctuates. Separate analog wiring from drive motor cables. Check the supply, shielding and channel wiring before adjusting the filter.
Related topics
DVP04AD-S2 analog input · DVP06AD-S analog input · DVP04DA-S2 analog output · DVP02DA-S analog output · DVP Slim temperature modules
Delta pages
Delta Automation and used models · Delta PLC · Delta DVP PLC series · DVP expansion modules · Delta PLC software
External references
Delta DVP06XA-S/S2 Instruction Sheet · Delta DVP Series Module Manual · Delta PLC/HMI Cable Selection Guide