Delta DVP14SS211R
Delta DVP14SS211R SS2 PLC with 8 Inputs and 6 Relay Outputs
The Delta DVP14SS211R is a compact 24 V DC PLC in the DVP-SS2 series. The CPU has 8 digital inputs, 6 mechanical relay outputs and 8K steps of program memory. Typical applications include small conveyors, packaging stations, filling equipment and auxiliary machine panels.
On a packaging line, a photoelectric sensor can detect an incoming product while an inductive sensor detects the position of a metal mechanism. The PLC then commands a valve or contactor coil as the sequence advances. When tracing the circuit, check which common terminal supplies the relay contact. The Y LED shows the PLC command. The load receives power through the corresponding C terminal.
Power supply, inputs and relay outputs
Supply • Nominal 24 V DC, with an operating range of 20.4–28.8 V DC. Delta’s instruction sheet specifies 1.8 W power consumption for this CPU. Size the 24 V DC power supply for the CPU, expansion modules and field devices that share it.
Digital inputs • Eight 24 V DC inputs at X0–X7. Connect the S/S common to 0 V for PNP sensors and to +24 V for NPN sensors. Delta specifies input frequency limits of 20 kHz for X0–X3 and 10 kHz for X4–X7. When connecting an encoder, also check the signal level and the frequency limit of the selected counter mode.
Relay outputs • C0 is common to Y0–Y2, and C1 is common to Y3–Y5. Delta specifies resistive load limits of 1.5 A per output and 5 A per common group. The working voltage is 250 V AC or below 30 V DC, with a maximum switching frequency of 1 Hz. For coils, check the inductive load ratings and suitable suppression. For applications that need high-speed pulse outputs, see the transistor-output DVP14SS211T.
Expansion • Add compatible DVP expansion modules on the right when more digital points are needed. To read a pressure or level transmitter, choose a DVP Slim analog input module that matches the transmitter’s output signal.
WPLSoft, ISPSoft and programming cable
Use WPLSoft to write ladder logic, transfer programs and monitor I/O online. Delta’s starter kit manual also demonstrates ISPSoft setup for this CPU. Select the SS2 CPU family for a new project and configure the serial channel in COMMGR when using ISPSoft.
The UC-PRG020-12A cable connects the PC’s USB-A port to the PLC’s COM1 RS-232 port using its 8-pin mini-DIN plug. Install the Delta programming cable driver and select the COM number assigned by Windows. Delta lists 9600 baud, 7E1, ASCII as the default serial format. Match the software settings to the PLC if the field configuration has been changed. COM2 RS-485 can connect to an HMI, drive or instrument using Modbus.
Editor’s Note
When buying a used CPU, confirm the full DVP14SS211R code on the label. Check photos of the power plug, output terminals and right-side expansion connector.
When replacing an older DVP-SS CPU, compare the terminal order with each unit’s wiring diagram. Delta identifies a different output terminal layout on SS2.
If Y0, Y1 and Y2 fail together, start with the supply and fuse for C0. Check C1 for the Y3, Y4 and Y5 group. For an intermittent single channel, isolate the field supply before checking the contact with a multimeter.
If the sensor detects a target and the X LED stays off, check whether the sensor is PNP or NPN and verify the S/S connection. Then see whether the input changes in the WPLSoft or ISPSoft monitor.
Before transferring a program, keep the original project file, serial settings and module order if available. If the PLC works on the bench and drops its connection in the panel, check for loose terminals and inspect the panel grounding.
Related PLC models
DVP14SS211T • 8 inputs and 6 NPN transistor outputs. DVP28SS211R • 16 inputs and 12 relay outputs. DVP28SS211T • 16 inputs and 12 transistor outputs. DVP12SS211S • 8 inputs and 4 PNP transistor outputs. For new panels, you can also review Derell B Series PLCs against the project’s I/O and communication requirements.
Related topics and PDF files
Delta DVP PLC PDF files · Delta DVP PLC series · Used Delta PLC models · Used PLCs and CPUs · Delta main page