Delta DVP12SE11R
Delta DVP12SE11R Ethernet PLC with 4 Relay Outputs
The Delta DVP12SE11R is a compact 24 V DC PLC in the DVP-SE series. It has 8 digital inputs, 4 relay outputs and 16K steps of program memory. Built-in RJ45 Ethernet, mini USB and two RS-485 ports suit applications such as packaging, pump control and compact machine panels.
In a pump panel, the PLC can read level and fault contacts and command a contactor. An operator panel can read running and alarm states from the same CPU over Ethernet. The data can also be monitored on a SCADA screen. When pairing devices, check their IP settings and protocol. The DVP-SE supports Modbus TCP and EtherNet/IP Adapter communication. See the EtherNet/IP and Modbus TCP comparison for their respective uses.
Power supply, digital inputs and relay outputs
Supply • Nominal 24 V DC, with an input range of 20.4–28.8 V DC and CPU power consumption of 1.8 W. When sizing the 24 V DC power supply, account for inrush current, expansion modules and field devices sharing the supply.
Digital inputs • Eight 24 V DC inputs at X0–X7. Connect the S/S common to 0 V for PNP sensors and to +24 V for NPN sensors. Verify the output type on the label when connecting an inductive sensor. When wiring an encoder, check the input assignment, signal level and counter mode together.
Relay outputs • Outputs Y0–Y3 share the C0 common terminal. Delta specifies resistive load limits of 1.5 A per output and 5 A per common. The 2024 instruction sheet specifies a working voltage of 100–250 V AC or 5–30 V DC, with a maximum switching frequency of 1 Hz. For valve and contactor coils, check the relay contact’s inductive load limits and choose suitable suppression for the coil.
Expansion • Use compatible Delta DVP expansion modules when more digital points are required. To read a continuous measurement from a pressure or level transmitter, select a DVP Slim analog input module that matches its signal range.
WPLSoft, ISPSoft and programming cables
Use WPLSoft or ISPSoft for ladder programming. In ISPSoft, select the DVP-SE CPU family. Configure the USB or Ethernet channel for your connection in COMMGR.
Mini USB connection • Delta lists UC-PRG015-01A (1.5 m) and UC-PRG030-01A (3 m). Connect the mini USB end of the programming cable to the CPU. On the first connection, install Delta’s USB driver and check the COM number assigned by Windows.
Ethernet connection • Use the UC-PRG030-20A or a Cat 5e RJ45 network cable to connect a PC or HMI. Use DCISoft to locate the PLC and check its IP address and subnet mask. Delta’s starter kit manual lists 192.168.1.5 as the default address. An installed PLC may have a different address. When transferring a program over Ethernet, use the PLC’s current IP address in COMMGR.
RS-485 connection • COM2 and COM3 can connect to an HMI, drive or instrument using serial Modbus. When replacing a CPU on a working machine, record the baud rate, parity, station address and protocol settings for each port.
Editor’s Note
When buying a used CPU, confirm the full DVP12SE11R code in the photos. Inspect the mini USB and RJ45 sockets, power plug and output terminals.
If all four outputs stop working, check the Y LEDs, then the C0 field supply and fuse. Isolate the field supply before checking contact continuity with a multimeter.
If the IP address is unknown, connect by mini USB first and read the network settings in DCISoft. Before replacing the PLC, record its IP address, subnet mask and the target address configured in the HMI.
If the Ethernet link LED is on and the HMI receives no data, compare the devices’ IP settings, the selected protocol and the PLC address in the HMI project.
If communication drops when the motor starts, check that network and RS-485 cables run separately from power cables. Inspect the terminals and panel grounding.
Related PLC models
DVP12SE11T • 8 inputs and 4 NPN transistor outputs. DVP26SE11R • 14 inputs and 12 relay outputs. DVP26SE11T • 14 inputs and 12 NPN transistor outputs. DVP14SS211R • SS2 CPU with 8 inputs and 6 relay outputs. For new panel projects, you can also review Derell B Series PLCs against your I/O and communication requirements.