Delta DVP-SE
Delta DVP-SE Series PLC
Delta DVP-SE is a 24 V DC slim PLC main unit with built-in Ethernet. It executes the machine program in its own CPU and is more than a communication interface. Typical uses include Ethernet access to the PLC program, HMI connections and data exchange with devices using supported protocols.
12SE and 26SE models
DVP12SE11R and DVP12SE11T provide 8 digital inputs and 4 digital outputs. DVP26SE11R and DVP26SE11T provide 14 digital inputs and 12 digital outputs. R identifies relay outputs; T identifies NPN transistor outputs. The manufacturer also lists DVP26SE11S with PNP transistor outputs. T and S output wiring must be distinguished.
The series offers 16k program steps and 12k words of data registers. The operating supply range is 20.4–28.8 V DC. Programs and retained data are stored in flash memory, so program retention does not require a battery. RTC operation during a power outage has a limited hold-up period and must be distinguished from permanent program storage.
Programming software
WPLSoft and ISPSoft can program the PLC. WPLSoft supports maintenance of existing ladder projects, program upload/download and online monitoring. In ISPSoft, select DVP-SE as the target PLC and configure the PC connection through COMMGR. Check instruction and feature availability against the CPU firmware.
DCISoft discovers the PLC and configures network parameters such as IP address and subnet mask; it is separate from the ladder editor. DOPSoft edits the HMI screen project. Back up the PLC program, HMI project and network settings separately. Related tools are listed under Delta PLC software.
USB programming cable and driver
DVP-SE has a mini-USB type B port for its PC connection. Manufacturer cable options include UC-PRG015-01A (1.5 m) and UC-PRG030-01A (3 m). An equivalent USB cable must support data transfer and have the correct mini-B connector.
After installing the USB driver, check the COM number assigned by Windows. The manufacturer’s DVP12SE example uses USB (Virtual COM) in COMMGR, with that driver selected in ISPSoft. Tools using serial connection settings, including WPLSoft, must use the same virtual COM port. An RS232 option in the software does not establish the presence of a physical DB9 or 8-pin RS-232 socket on the PLC.
8-pin mini-DIN cables such as DVPACAB230 do not connect to the DVP-SE mini-USB port. Check the device-side connector under Delta PLC cables. Use mini-USB for program transfer and maintenance; consider Ethernet or an appropriate RS-485 connection for continuous plant communication.
Ethernet cable and initial connection
Connect the built-in RJ45 port using CAT5e or better Ethernet cable. The manufacturer’s example cable is UC-PRG030-20A. The port supports Auto MDI/MDIX. A PC can connect directly or through a suitable network switch.
The manufacturer instruction sheet specifies default values of 192.168.1.5 for the IP address and 255.255.255.0 for the subnet mask. A used PLC may have different settings. Discover its current configuration with DCISoft, place the PC in the appropriate network range, then select Ethernet and the target IP in the programming software. IP conflicts, IP filters or the wrong PC network adapter can prevent communication.
Modbus TCP is supported. For EtherNet/IP, the manufacturer distinguishes explicit messaging on DVP12SE from adapter mode and explicit messaging on DVP26SE. An Ethernet socket alone does not establish support for every industrial network protocol or the scanner role.
RS-485, high-speed inputs and pulse outputs
DVP12SE has two RS-485 ports; DVP26SE has one RS-485 port. Match protocol, station address and serial settings when connecting an HMI, drive or other device. The RS-485 connection is separate from the Ethernet RJ45 port.
Series features on transistor-output models include two 100 kHz and two 10 kHz pulse outputs. Relay-output R models do not provide this high-speed pulse function. For encoder or servo connections, check the designated X/Y points, input type, common terminals and frequency limits for the complete model.
Analog channels and expansion differences
The DVP-SE main unit has no built-in analog inputs or outputs. Select suitable DVP expansion modules for 0–10 V, 4–20 mA or temperature measurement. Depending on the application, examine modules such as DVP04AD-S, DVP02DA-S and DVP06XA-S. Obtain signal ranges and register access details from each module’s own documentation.
DVP12SE supports left-side and right-side expansion; DVP26SE supports right-side modules only. This distinction matters when replacing one body size with the other. Although the series specifies a maximum of 480 I/O points, determine actual system capacity from module types, quantity limits and the power budget.
Manuals and technical files
Use Delta DVP PLC files for installation, connection and programming documentation. Preserve the 12SE/26SE distinction, complete model code and applicable firmware requirements.
Editor's Note
Do not reset a PLC simply because it is missing from a network search. Check its current IP and the selected PC network adapter first. Changing the IP of a running machine PLC can also disconnect its HMI and other devices.
When assessing a used PLC, back up the program, required retained data and network settings if access is available. Do not assume that a protected controller provides a readable program or editable source project; establish access before purchase.
If USB communication fails, check the data cable and driver first. Match the COM number shown by Windows to the software setting. Test with a known-good cable before condemning the connector or CPU.
Check relay contacts with a controlled load rather than relying on the output LED. For transistor models, compare output type and field-load wiring. Inspect the board with power removed and prevent unintended machine movement during testing.
When considering 26SE as a replacement for 12SE, compare more than I/O count. Check left-side module support, RS-485 port count, network communication and terminals. More I/O does not establish direct compatibility with the existing system.
Related topics
DVP-SS2 · DVP-SA2 · DVP-SX2 · DVP-SV2 · DVP power supplies
Navigation: Delta DVP PLC series · Delta PLC · DVP PLC files
External references
Delta DVP-SE manufacturer instruction sheet, 2024, multilingual · Delta Starter Kit Manual, 2024, English (DVP12SE USB and Ethernet examples)