Delta DVP26SE11R | Ethernet PLC with 14 Inputs and 12 Relay Outputs

The Delta DVP26SE11R is a compact PLC CPU in the DVP-SE series with a 24 V DC supply, 14 digital inputs and 12 relay outputs. Its 16k-step program capacity and built-in Ethernet port suit conveyor, packaging and HMI-connected machine control.

Power supply, inputs and relay groups

The 24 V DC supply has an operating range of 20.4–28.8 V DC. Digital input addresses are X0–X7 and X10–X15. Wire the S/S common according to the sink/source diagram and the output type of the inductive sensor or photoelectric sensor. Fit compatible DVP-S expansion modules on the right side of the CPU.

Relay groups are C0 for Y0–Y2, C1 for Y3–Y5, C2 for Y6, Y7 and Y10, and C3 for Y11–Y13. The relay contacts switch the load’s external supply. Delta specifies 100–250 V AC or 5–30 V DC and resistive-load limits of 1.5 A per output and 5 A per common. Check the contact life and suppression guidance for contactor or valve coils.

Relay outputs have a maximum switching rate of 1 Hz. For applications sending high-speed pulses to a stepper or servo drive, compare the pulse channels of the NPN-output DVP26SE11T and the drive’s input requirements. Both models have the same number of I/O points.

WPLSoft, ISPSoft and programming cables

Use WPLSoft or ISPSoft for PLC programming. To transfer or monitor a ladder program locally, connect the Mini USB port with the UC-PRG015-01A or an equivalent USB-to-Mini USB data cable. Install the driver and select the connection on the PC.

For Ethernet programming, use an RJ45 CAT5e cable. Delta’s example cable is the UC-PRG030-20A. In ISPSoft, select Ethernet as the COMMGR connection type and use the PLC’s project IP address. Use DCISoft to read or set the network parameters. Delta lists 192.168.1.5 and 255.255.255.0 as the default IP address and subnet mask.

COM2 is this model’s only RS-485 port. Match the baud rate, framing and address settings on the serial Modbus link. Select ASCII or RTU to match the connected devices. Ethernet supports Modbus TCP and EtherNet/IP. Delta specifies EtherNet/IP Adapter mode and explicit messaging. Establish the protocol and device role before connecting an HMI or remote I/O station.

Editor’s Note

Inspect the label and connectors. When buying used, ask for photos of the DVP26SE11R label, Mini USB and RJ45 sockets and C0–C3 terminals.

Make a backup before replacement. Save the PLC project, IP address, subnet mask and COM2 serial settings. Check that you can open the backup.

Check beyond the Y LED. With a safe test load, verify that a contact switches in each relay group and that the corresponding common is supplied.

Test Ethernet on the bench first. Verify the IP address before connecting to the machine network. If you have no link or connection, check the cable, switch port and any duplicate IP address.

Monitor RS-485 with the loads running. If communication drops when a drive starts, check for interference and inspect the distance between serial and power wiring.