Delta DVP-SA2

Delta DVP-SA2 Series PLC

Delta DVP-SA2 is an advanced Slim main PLC series in the Delta DVP family, with a 24 V DC supply and 16K steps of program memory. It suits compact machine control, sequential automation and, on appropriate transistor models, pulse-controlled motion applications. Its battery-free design stores programs and retained-area data in Flash memory.

Assess SA2 separately from the earlier DVP-SA series. Within SA2, the 12-point and 28-point CPUs have different communication and expansion hardware. Match the full model code and the connections used by the existing project when selecting a replacement.

SA2 models and output types

12-point models: DVP12SA211R provides 8 digital inputs and 4 relay outputs; DVP12SA211T provides 8 digital inputs and 4 NPN transistor outputs.

28-point models: DVP28SA211R provides 16 digital inputs and 12 relay outputs; DVP28SA211T provides 16 digital inputs and 12 NPN transistor outputs. Delta's model table also lists DVP28SA211S with PNP transistor outputs. R, T and S outputs require the appropriate wiring.

Transistor models provide independent pulse outputs rated up to 100 kHz at Y0 and Y2, and 10 kHz at Y1 and Y3. These ratings do not apply to R relay models. Likewise, do not treat every X terminal as having the same high-speed input capability. Match the counter, input point and operating mode to the manual.

Which software programs the SA2?

WPLSoft and ISPSoft are programming tools used with DVP-SA2. WPLSoft supports ladder editing, program transfer and online monitoring. In ISPSoft, select SA2 and the correct CPU model as the project target. Features and memory resources from other DVP generations must not be assumed to apply.

ISPSoft 2.0 and later use a COMMGR communication channel. Keep the original .dvp file when importing a WPLSoft project into ISPSoft, then check the converted project's compilation and addressing results. The Delta PLC software page explains the different tools.

Which programming cable is required?

The basic PC connection uses the PLC's COM1 RS-232 port. UC-PRG020-12A is a converter-equipped programming cable with USB at the computer end and an 8-pin male mini-DIN connection at the PLC end. Delta's cable guide shows it for DVP12SA211R/T. Install its Windows driver and check the assigned COM port number in Device Manager.

A computer with a physical RS-232 port can use an appropriate serial cable, such as UC-MS020-01A, or a correctly wired DVPACAB2A30. Without that port, these serial cables need a separate USB-to-RS-232 converter. Distinguish converter-equipped cables from passive serial cables when choosing a Delta PLC cable. The SA2 COM1 connection is not mini-USB.

For ISPSoft, create and start the appropriate serial driver in COMMGR, then select that channel in ISPSoft. The baud rate, data bits, parity, stop bits and station address must match the PLC. On first connection, read the device information to confirm the target CPU before transferring a program. Back up the existing machine first.

RS-232, RS-485 and model differences

DVP12SA2: COM1 is RS-232; COM2 and COM3 are RS-485. DVP28SA2: COM1 is RS-232 and COM2 is RS-485. The 12-point model's COM3 port must not be assumed to exist on the 28-point CPU. Appropriate port settings allow Modbus ASCII/RTU communication and master/slave applications.

When connecting an HMI, drive or another PLC over RS-485, match addresses, communication speed and data format. For Ethernet requirements, assess a CPU with built-in networking such as DVP-SE, or a suitable external solution. Do not assume the SA2 has a built-in Ethernet port.

Expansion modules and application selection

Select Slim digital, analog and temperature modules from the DVP expansion family using the CPU and module manuals. Analog signals, thermocouples and resistance sensors require suitable interfaces rather than a standard digital input.

The left-side high-speed expansion connection is specific to DVP12SA2. Do not assume that left-connected communication modules or positioning modules can also be fitted to DVP28SA2. For a solution such as DVPEN01-SL, first check the 12SA2 CPU and module compatibility. Increasing the built-in I/O count does not necessarily preserve the communication options.

Editor's Note

Start with the basics: 12 or 28 points, relay or transistor? Choosing more I/O can still leave an existing COM3 connection or left-side module without a compatible interface.

Battery-free does not mean backup-free. Save the program, device parameters and required retained data. Record recipes and counter starting values separately; avoid clearing memory as a troubleshooting shortcut on a working machine.

If communication fails, check the USB cable driver and COM number first. UC-PRG020-12A is not an ordinary USB cable. The connector, electrical interface and settings all need to match.

An input LED or output indicator alone does not establish the condition of the whole PLC. Monitor inputs in software and test relay contacts and transistor outputs individually with suitable loads.

For servo or step applications, account for the speed difference between Y0/Y2 and Y1/Y3. Measure the pulse signal and confirm that the drive accepts it. Also check direction, enable and common-terminal wiring.

For intermittent resets or communication loss, measure the 24 V supply under load. Investigate loose terminals, shielding and interference from coils before moving on to internal PLC repair.

Manuals and related topics

Use Delta DVP PLC files for installation, programming and connection documents. Read the 12SA2 and 28SA2 drawings separately rather than applying a series overview to every model.

Related topics: DVP-SS2 · DVP-SX2 · DVP-SV2 · DVP-SE. Compare I/O, analog requirements, pulse speed and communication needs. These links do not establish direct replacement compatibility.

Navigation: DVP PLC series · Delta PLC main category · Used Delta equipment · PLC software · DVP files