Delta DVP28SA211T
Delta DVP28SA211T – DVP-SA2 PLC with 16 inputs and 12 NPN outputs
The Delta DVP28SA211T is a PLC CPU in the Delta DVP-SA2 series with 16 digital inputs and 12 NPN transistor outputs. It runs on 24 V DC, has a supply range of 20.4–28.8 V DC, and holds 16K program steps. Its high-speed pulse outputs can drive a compatible controller for feeding, indexing or positioning.
Digital inputs and transistor output groups
The 24 V DC digital inputs are X0–X7 and X10–X17. Addresses are octal. Check each S/S common against the type of NPN or PNP sensor connected to that group.
Y0–Y7 share ZP0 and Y10–Y13 share ZP1. The outputs are NPN open collector. Delta specifies limits of 0.5 A per output and 4 A per common for resistive loads. Follow the wiring diagram for the auxiliary output supply. The DVP28SA211S has PNP outputs, and the DVP28SA211R has relay outputs.
Pulse outputs and high-speed counting
Delta’s transistor output table lists up to 100 kHz on Y0 and Y2 and 10 kHz on Y1 and Y3. For a stepper motor or servo drive, check the drive manual for the pulse input interface and the pulse/direction assignment. For high-speed counting, select supported CPU inputs and a counter mode that matches the encoder’s single-phase or A/B quadrature signal.
WPLSoft, ISPSoft and programming cable
Program the CPU with WPLSoft or ISPSoft. In a new ladder project, verify the DVP-SA2 family and the 28-point CPU target. The programming port is COM1, 8-pin Mini-DIN RS-232. On a USB-equipped PC, use the UC-PRG020-12A, its driver and the assigned COM port. For a PC with a serial port, use the UC-MS020-01A. For ISPSoft, select the RS-232 driver and COM port in COMMGR.
COM2 provides RS-485 field communication. Match the station address, baud rate and serial framing to the HMI or drive. The 28-point CPU provides COM1 and COM2. Delta’s sheet lists COM3 and the left-side high-speed expansion connector for the 12-point SA2 model. This model uses right-side DVP-S expansion modules. Select a compatible analog I/O module for signals such as 4–20 mA.
Editor's Note
When buying used, check the full DVP28SA211T label and the removable terminal blocks. The T, R and S variants have different load wiring.
On the bench, use a multimeter to check the 24 V DC supply at the CPU and at the output circuit.
If one output group stays off, check its ZP common first. The LED indicates the output command. Measure the load supply separately.
Back up the current program, serial settings and expansion module order before downloading a test program.
Put the machine into a safe test state before checking pulse outputs. If counts are erratic, check encoder cable routing and sources of electromagnetic interference.