Delta DVP28SA211R | DVP-SA2 PLC with 16 inputs and 12 relay outputs

The Delta DVP28SA211R is a compact PLC CPU in the Delta DVP-SA2 family with 16 digital inputs and 12 relay outputs. The nominal supply is 24 VDC, with an operating range of 20.4–28.8 VDC. It reads sensors and sequences contactors and valves in conveyor, packaging and small machine panels.

Inputs, relay groups and expansion

Inputs X0–X7 and X10–X17 support 24 VDC sink or source wiring. Match the S/S common to the PNP or NPN output of the inductive sensor. For high-speed counter applications, the instruction sheet lists input limits of 100 kHz for X0–X3, 10 kHz for X4–X7 and 50 Hz for X10–X17. Check these groups when choosing the counter mode and input filter.

The relay outputs are divided into four common groups. C0 serves Y0–Y2, C1 serves Y3–Y5, C2 serves Y6, Y7 and Y10, and C3 serves Y11–Y13. The manual gives resistive load limits of 1.5 A per point and 5 A per common. The contact voltage range is 100–250 VAC or 5–30 VDC. Feed each load circuit through its common. For coils, check the contact life curve and select appropriate suppression.

The maximum relay switching frequency is 1 Hz. For pulse-command motion, consider the transistor outputs of the DVP28SA211T. Delta specifies the SA2 as a 16k-step class. The programming manual lists 15,872 steps. The DVP28SA211R accepts compatible DVP Slim digital and analog expansion modules on the right side. For analog measurements, choose a module that matches the sensor range.

WPLSoft, ISPSoft and programming cables

Use WPLSoft or ISPSoft to develop the PLC program and select the DVP-SA2 family. Connect the PC to COM1 RS-232, 8-pin mini-DIN. For a USB-equipped PC, install the UC-PRG020-12A USB-to-RS-232 cable driver and check the COM number in Windows. On a PC with a hardware RS-232 port, use a DB9-to-mini-DIN cable such as the UC-MS020-01A.

For ISPSoft, create a serial driver in COMMGR and select the same COM number. For WPLSoft, match the COM number and serial settings to the CPU. The DVP28SA211R has one RS-485 port, COM2. When connecting an HMI or drive, check the Modbus ASCII/RTU mode, station address, baud rate and parity. For field communications, inspect the RS-485 end termination and cable shield.

Editor’s Note

When buying a used unit, verify the DVP28SA211R label and removable terminals. Inspect the right-side expansion connector and DIN rail clip.

When an output LED lights, check the relay contact with a suitable test load. Pay particular attention to outputs that switch often.

If every output in a group is inactive, check the supply to its C0–C3 common first.

Back up the project and retained values before replacing the CPU. Test the machine’s restart behaviour after a power cycle.

If the PC cannot connect, start troubleshooting with COM1 and the cable driver. For COM2 faults, check the serial settings, shield and grounding connections.

Related models

The DVP28SA211T has the same I/O count with NPN transistor outputs. The DVP12SA211R has 8 inputs and 4 relay outputs. The DVP12SA211T has 8 inputs and 4 NPN outputs. The DVP28SS211R is an SS2 CPU with 16 inputs and 12 relay outputs. Compare program capacity, ports, terminals and expansion support before replacement.