Delta DVP12SA211R

Delta DVP12SA211R PLC – 8 Digital Inputs and 4 Relay Outputs

The Delta DVP12SA211R is a 24 V DC PLC CPU in the Delta DVP-SA2 series with 8 digital inputs, 4 relay outputs and 16K program steps. Its battery-free design stores the program and retained-area data in Flash memory. It suits compact machines that need sensor monitoring, sequence control or valve and contactor control.

Digital inputs and high-speed counting

The CPU supply range is 20.4–28.8 V DC. The X0–X7 digital inputs accept 24 V DC signals. Wire the S/S common to suit the sensor type. See the PNP and NPN sensor guide for wiring options. For single-phase high-speed counting, X0/C243 and X2/C244 each support up to 100 kHz. When using an A/B incremental encoder, check the input pair and frequency limit for that counter mode in the programming manual.

Relay outputs and the C0 common

The Y0–Y3 relay contacts share the C0 common. The external load circuit supplies the switched voltage. For resistive loads, Delta rates the outputs at 1.5 A per point and 5 A total at the common. For inductive loads such as coils, consult the load curves for contact life and check inrush current. See how relays work for more on contact operation.

The relay outputs have a maximum switching frequency of 1 Hz. Where high-speed pulse outputs are required, compare the transistor-output DVP12SA211T, rated at 100 kHz on Y0/Y2 and 10 kHz on Y1/Y3, with the drive’s input circuit.

Programming cable and RS-485 ports

Use WPLSoft or ISPSoft with SA2 as the project CPU type. To read or transfer a program from a PC, connect the UC-PRG020-12A USB-to-RS-232 programming cable to the CPU’s 8-pin mini-DIN COM1 RS-232 port. After installing the driver, select the Windows COM port in WPLSoft or in COMMGR for ISPSoft. See Delta DVP programming cables for other connections.

COM2 and COM3 are RS-485 ports. They can provide separate Modbus serial links for an HMI and a drive, for example. In an existing project, check D1109 for the COM3 communication format and M1320 for ASCII or RTU mode. Match the station address, speed and data format to the other device.

Expansion and model selection

Fit compatible I/O modules to the standard right-side DVP expansion bus. The DVP08SM11N adds digital inputs. On the left-side high-speed bus, consider the DVP04AD-SL for analog inputs and the DVPEN01-SL for Ethernet. COM3 and the left-side high-speed bus are features of the 12-point SA2 chassis. For 16 inputs and 12 outputs, the DVP28SA211R has relay outputs and the DVP28SA211T has NPN outputs. When replacing an older DVP12SA11R, compare the terminal layouts and available ports.

Editor’s Note

When buying a used unit, verify the DVP12SA211R label. Inspect the removable terminals, COM1 socket and left-side expansion connector.

If the output LED lights and the load stays off, check the external load supply at C0 and the selected Y contact. Test each output individually on the bench.

If a relay contact sticks, check load inrush and the coil suppression circuit. Also consider contact wear on outputs that have switched frequently over a long period.

Before removing the CPU, back up the program, retained data and settings for both RS-485 links. Label the COM2 and COM3 cables in the panel to simplify replacement.

If the machine uses a left-side module, check the expansion connector on the spare CPU. After installation, verify the left-side module IDs in D1386–D1393 in connection order.

Related pages and PDFs

Delta DVP PLC series · Delta PLC models · Used Delta automation equipment · Delta DVP PLC files

External references · Delta DVP-SA2 Installation and Wiring Sheet (2023, EN) · Delta DVP-SA2 Programming Manual (2022, EN) · Delta PLC/HMI Cable Selection Guide (2019, EN)