Delta DVP08SM11N
Delta DVP08SM11N – 8-Channel 24 V DC Digital Input Module
Delta DVP08SM11N is a right-side expansion module in the Delta DVP Slim digital module range. It adds eight digital inputs and has zero outputs. It reads the on/off states of field devices such as limit switches, pushbuttons, photoelectric sensors and proximity sensors. The CPU supplies the module electronics through the expansion bus. The field inputs use 24 V DC signals.
Input specifications and S/S wiring
The removable terminal block has X0–X7 inputs and one S/S common terminal. Delta’s detailed specifications give 5 mA per input, 4.7 kΩ input impedance and a response time of approximately 10 ms in either direction. The voltage across the input and S/S must be above 16.5 V DC for OFF-to-ON and below 8 V DC for ON-to-OFF. The input LED lights when its optocoupler conducts.
PNP sensor: Connect S/S to field supply 0 V. The active sensor applies +24 V to the X input. NPN sensor: Connect S/S to field supply +24 V. The active sensor pulls the X input to 0 V. All eight channels share S/S, so directly connected three-wire sensors must use the same output polarity within the group. See the PNP and NPN sensor comparison for the two wiring arrangements.
Choosing sensors and contacts
Use an inductive sensor for a metal target, consider a capacitive sensor for level detection, or use a photoelectric sensor for products passing on a conveyor. Mechanical position and operator commands can come from a limit switch or pushbutton. To bench-test with a dry contact and S/S at 0 V, wire the contact between +24 V and the selected X input.
Two-wire DC sensors pass a small leakage current in the OFF state. Delta specifies less than 1 mA OFF-state leakage for this arrangement. Check that value along with the rated voltage and output type. For proportional measurements, see analog versus digital inputs. For pulse counting with an encoder, check the CPU’s high-speed counter inputs.
Compatible CPUs, software and cable
Check the exact CPU model for right-side expansion support and module limits in the DVP-SS2, DVP-SA2, DVP-SX2, DVP-SV2 or DVP-SE families. Use WPLSoft or ISPSoft as supported by the CPU. Configure the ISPSoft connection through COMMGR. For a CPU with an 8-pin mini-DIN RS-232 COM1 port, Delta’s CPU-specific cable table lists the UC-PRG020-12A USB-to-RS-232 cable or UC-MS020-01A serial cable where applicable. Connect the cable to the CPU.
X0–X7 are the terminal markings. The CPU’s built-in I/O and preceding modules determine the PLC addresses. If expansion starts at X20 and this is the first module, the addresses are X20–X27. Read the assigned X bits in the ladder diagram and verify them online.
Editor’s Note
Read the model label first when buying second-hand. SM11N takes DC signals. The similar-looking SM10N takes AC.
Check that the terminal block is seated, the S/S terminal clamps properly and the side connector has straight pins.
Apply the same 24 V test signal to all eight inputs in turn. Watch the LED and the assigned X bit in the PLC monitor on every channel.
If the input clears when a sensor is disconnected, check its OFF-state leakage. If all eight channels are inactive, measure the shared S/S reference and field supply first.
If the signal flickers when a drive starts, check where the field wiring runs in relation to motor cables. Review cabinet grounding and sources of electromagnetic interference.
Related topics and models
DVP16SM11N 16 DC inputs · DVP32SM11N 32 DC inputs · DVP08SM10N 8 AC inputs · DVP08SP11TS 4 DC inputs and 4 PNP transistor outputs
Delta DVP expansion modules · Delta DVP PLC series · Second-hand Delta models · Delta DVP PLC PDF files
External references
Delta DVP Series Module Manual (2026, EN) · Delta DVP Slim digital I/O instruction sheet (2018, EN/ZH) · Delta PLC/HMI Cable Selection Guide (EN)