Delta DVP12SA11R

Delta DVP12SA11R — DVP-SA PLC with 8 Inputs and 4 Relay Outputs

The Delta DVP12SA11R is a first-generation Delta DVP-SA PLC CPU with a 24 V DC supply, 8 digital inputs and 4 relay outputs. Delta specifies 7,920 program steps in battery-backed SRAM. It suits machine sequencing, sensor monitoring and contactor control.

Power, inputs and relay commons

Power the CPU at its 24 V and 0 V terminals from a 24 V DC supply. The permitted range is 20.4–28.8 V DC. The X0–X7 inputs accept 24 V DC signals. Wire S/S for the NPN or PNP sensors in the panel. Use +24 V on S/S for NPN sensors or 0 V for PNP sensors. The CPU mounts on a 35 mm DIN rail.

Relay terminal assignment. Y0 → C0, Y1 → C1 and Y2 and Y3 → C2. C0, C1 and C2 are the load supply commons for their respective groups. Delta lists 1.5 A per point and an approximate relay response time of 10 ms. For coils and other inductive loads, check the relay contact ratings and suppression diagrams in the manual.

For additional I/O, attach compatible DVP expansion modules to the right-side connector. Check the CPU generation and total power requirements before selecting a module.

WPLSoft, COM1 and programming cable

Delta lists WPLSoft for this model. Select the first-generation SA CPU profile for your ladder program. The PC connects to COM1 RS-232. Delta’s instruction sheet lists DVPACAB2A30, a 3 m cable with DB9 at the PC end and an 8-pin mini-DIN at the PLC end.

For a USB-equipped PC, use DVPACAB2A30 with a suitable USB-to-RS‑232 adapter, or use the Delta UC-PRG020-12A. Install the converter driver, then select the Windows COM port and match the CPU’s serial settings in the PLC programming software. See Delta PLC cables and the serial interface comparison for connector and cabling details.

COM2 RS-485 provides master/slave communication. For an operator panel connection, select the correct port, enter the target PLC’s station address and match the baud rate, parity and stop bits. See industrial communication for more on field networks.

Field application

On a conveyor, an inductive sensor can detect parts on X0, Y0 can control the motor contactor, and X1 can read the contactor’s auxiliary contact. Match the program’s NO/NC contact logic to the field wiring. Use the machine’s independent safety circuit for the emergency stop.

Editor’s Note

When buying used, check for the exact DVP12SA11R label, the two-pin power plug and the side expansion connector. For a move to SA2, verify the terminal layout and project settings separately.

If BAT.LOW is lit, back up the program and accessible retained data first. Follow Delta’s battery type and timing instructions during replacement.

If the Y LED lights and the load stays off, check supply at the relevant C0, C1 or C2 terminal and test the contact with a suitable load. Use a multimeter where needed.

Use the load manufacturer’s recommended coil suppression. A suitable flyback diode can protect a DC coil circuit. For an AC coil, consider a suitable varistor or RC network. Size the output circuit fuse for the load.

If inputs drop intermittently, check S/S wiring and the PLC supply. If the fault worsens when a contactor closes, inspect the signal cable routing, grounding and sources of electromagnetic interference.

After replacement, check X0–X7 and each relay output with the loads disabled. Then verify timers, retained values and any COM2 communication.

Related models and pages

The DVP12SA11T is the transistor-output model from the same generation. The DVP12SA211R and DVP12SA211T belong to the later SA2 series. The DVP14SS211R belongs to the SS2 family. See Derell PLCs and smart relays for other small automation applications.

Delta DVP-SA · Delta DVP-SA2 · Delta DVP PLC series · Used Delta PLCs · Delta Automation

Manual and wiring diagrams

Delta DVP PLC files · Delta DVP-SA wiring sheet in Turkish

External references · Delta DVP-SA installation sheet in English · Delta DVP-PLC programming manual · Delta USB-to-RS-232 cable note