Delta DVP04AD-SL

Delta DVP04AD-SL – 4-Channel High-Speed Analog Input Module

Delta DVP04AD-SL adds four analog inputs to the left side of a compatible PLC CPU. Its A/D converter turns voltage or current into a digital value the PLC can read. Use it to measure analog signals from pressure, level or position transmitters.

CPU compatibility and power supply

Delta lists CPUs with a left expansion bus, including the DVP12SA2 and DVP20SX2. The earlier instruction sheet covers DVP28SV and EH2-L examples. The DVP26SE in the DVP-SE family and the DVP28SA2 lack a left expansion connection. Check the full CPU order code and left connector. The DVP04AD-S2 is a right-side analog input module and the DVP04DA-SL is a left-side analog output module.

The module’s separate 24 V DC power input accepts 20.4–28.8 V DC. Delta specifies a response of 250 µs per channel. Sample averaging and the program scan also affect how soon the reading updates. The analog channels share a circuit without channel-to-channel galvanic isolation.

Signal ranges and wiring

Select each channel independently. Voltage input ranges are ±10 V, ±5 V, 0–5 V and 1–5 V. Current input ranges are ±20 mA, 0–20 mA and 4–20 mA. A 0–10 V signal uses the positive half of the ±10 V range. Bipolar modes have 16-bit resolution and scale to −32,000…+32,000. Unipolar modes have 15-bit resolution and scale to 0…32,000.

Connect CH1 voltage to V1+ and V1−. For CH1 current, jumper V1+ to I1+ as shown in Delta’s wiring diagram and return the current circuit to V1−. Provide loop power for a two-wire loop-powered transmitter. Use the corresponding numbered terminals for other channels. Follow the wiring diagram for shielded cable, separation from power wiring and grounding.

Channel setup, addressing and scaling

Left-side module numbers start at 100 for the module nearest the CPU. CR#0 reports model ID H4400. CR#2–5 set the modes of CH1–CH4. Mode 0 selects ±10 V, 1 ±20 mA, 2 0–20 mA, 3 4–20 mA, 4 ±5 V, 5 0–5 V, 6 1–5 V and HFFFF disables the channel.

Use FROM to read CR#16–19 for present values or CR#12–15 for averages. CR#8–11 set the averaging count from 1 to 20. Set channel modes with TO. In 4–20 mA mode, 4 / 12 / 20 mA ≈ 0 / 16,000 / 32,000 counts. On a 0–10 bar transmitter, 16,000 counts represents about 5 bar.

Programming software and cable

Set up and read the channels in the host CPU’s PLC program. Use WPLSoft or a compatible ISPSoft release according to the CPU and project version. For a DVP12SA211R/T, connect the UC-PRG020-12A to the CPU’s COM1 RS-232 port. Install the USB serial driver and select its virtual COM port. For other CPUs, select the programming cable by the exact model and port.

Editor’s Note

When buying a spare, check the -SL suffix and the left bus connector. Make sure the removable terminal block comes with the unit.

If a current channel stays at zero, check transmitter loop power, the V+/I+ jumper and the channel mode first.

If readings fluctuate, start with cable routing and shield termination. Increasing the averaging count smooths the reading and slows its response.

If the reading stays at 32,767, check whether the channel is disabled. Read CR#43 when troubleshooting power, mode or channel faults.

Commission the channel with 4, 12 and 20 mA from a calibrator. If raw counts agree, check PLC or HMI scaling next.

PDF manuals and related topics

Delta DVP PLC files · Chapter 11 covers channel setup and includes the wiring diagram on printed page 11-16.

Related topics · Analog inputs and outputs · Analog and digital input differences · DIN rail mounting

Navigation · Delta Automation · DVP series · Expansion modules · DVP Slim analog modules

External references

Delta DVP Module Manual, Chapter 11 · DVP04AD-SL instruction sheet (EN/ZH) · Delta PLC/HMI cable guide · Delta CPU programming manual