Delta DVP-SS2

Delta DVP-SS2 Series Slim PLC

Delta DVP-SS2 is a second-generation, 24 V DC slim PLC CPU series within the Delta DVP PLC family. It executes the machine control program and offers 8k steps of program memory, 5k words of data registers and built-in RS-232 / RS-485 communication. A suitable expansion arrangement can provide up to 480 digital I/O points; this is the system expansion limit, not the number of terminals on the CPU.

Conveyor sequencing, pump control, packaging auxiliary operations, part counting and sensor-based machine sequences are possible applications. Select the CPU by output technology, pulse frequency, communication and expansion requirements as well as the total I/O count.

DVP-SS2 models and output types

Relay models: DVP14SS211R provides 8 digital inputs and 6 relay outputs; DVP28SS211R provides 16 digital inputs and 12 relay outputs. Relay contacts switch loads within their electrical ratings; they are not the choice for high-speed pulse/step commands.

NPN transistor models: DVP14SS211T has 8 inputs + 6 outputs, while DVP28SS211T has 16 inputs + 12 outputs. NPN outputs sink load current towards 0 V. For pulse applications, verify the output type, designated Y terminal and drive input circuit together.

PNP transistor models: DVP12SS211S offers 8 inputs + 4 PNP outputs. The manufacturer’s 2024 documentation also lists DVP28SS211S with 16 inputs + 12 PNP outputs. PNP outputs switch the positive supply side of the load. R, T and S suffixes identify different output technologies; changing between them requires a wiring review.

Power supply, sensor wiring and addressing

The CPU requires 24 V DC, with a specified range of 20.4–28.8 V DC. Size the supply for the CPU, expansion devices and connected field loads. Connect the S/S input common for the intended PNP or NPN sensor circuit. Sensor output technology and PLC output technology are separate selection issues.

DVP X and Y addresses use octal numbering: X10 follows X7. A 16-input CPU therefore uses X0–X7 and X10–X17; a 12-output model uses Y0–Y7 and Y10–Y13. Match program addresses to the actual terminals rather than assuming decimal numbering.

High-speed counting and pulse outputs

For single-phase, single-input counting, SS2 specifies 4 input points at 20 kHz and 4 at 10 kHz. A/B encoder modes have their own frequency and counter allocation limits. Suitable transistor-output terminals provide up to 4 pulse output points at 10 kHz. This capability does not apply to relay outputs; check the selected instruction and output terminal limitations.

Which programming software does it use?

DVP-SS2 can be programmed with WPLSoft and ISPSoft. WPLSoft supports conventional ladder editing and maintenance; ISPSoft provides project development and online monitoring within the features supported by the target CPU. Select the DVP-SS2 target and confirm that the CPU firmware supports the instructions used. An instruction appearing in the software for another DVP controller does not establish SS2 compatibility.

For an ISPSoft connection, configure the appropriate serial communication driver and PC COM port in COMMGR. WPLSoft also requires the correct cable port and PLC communication settings. The USB-to-RS-232 Windows driver and COMMGR perform different functions. Back up the existing program, available comments and required retained data before changing tools. Successful compilation alone does not confirm identical machine behaviour.

Which programming cable is required?

For a PC with USB, UC-PRG020-12A is a suitable cable for the SS2 COM1 RS-232 / 8-pin mini-DIN programming port. It converts USB to RS-232; it does not provide a native USB connection to the CPU. Install the correct cable driver, identify its COM number in Windows Device Manager and select that same port in the programming software.

For a PC with a genuine RS-232 port, use an appropriate DB9-to-8-pin mini-DIN cable such as UC-MS020-01A. When adding a USB-to-RS-232 converter, verify both its electrical standard and the PLC cable pinout. A USB-TTL adapter or a cable with a physically matching plug is not equivalent. See Delta DVP programming cables for related options.

HMI and Modbus communication

The built-in RS-232 and RS-485 ports support Modbus ASCII/RTU communication with the appropriate configuration. Match the station address, baud rate, data format and protocol between the PLC, HMI, drive or other device. A standard SS2 CPU has no built-in Ethernet or USB port. Network access requires a separate, compatible communication solution; an Ethernet cable cannot connect directly to an SS2 CPU.

Expansion and comparison with other slim PLCs

Explore DVP Slim digital modules for additional digital I/O, DVP Slim analog modules for voltage/current signals and DVP Slim temperature modules for temperature measurement. When choosing DVP expansion modules, verify CPU support, module order, power requirements and addressing rather than relying on a similar enclosure.

Do not assume the older DVP-SS and SS2 use identical output terminal layouts. Compare DVP-SA2, DVP-SV2, DVP-SX2 and DVP-SE when reviewing memory, analog I/O, motion and communication requirements. These related series are not automatically interchangeable with an existing SS2 program and wiring.

Program and retained data

SS2 uses flash memory for program and retained-data storage and does not require a user-installed backup battery. This does not make every D register or operating bit retentive. Place counters, recipe values and setpoints that must survive power loss in the appropriate retained areas, then verify the restart behaviour in the application.

Editor’s Note

A lit POWER indicator is only the beginning of a proper check. Measure the 24 V supply at the CPU terminals and check for voltage drop or excessive ripple when connected loads operate.

For a controller removed from a working machine, back up the program and required data first. Resetting a protected or unreadable CPU without a recovery plan can destroy the only available machine program.

An output LED does not prove that the load is being driven. Test relay contacts with a suitable load; for transistor outputs, check NPN/PNP type, UP/ZP supply and load current. Do not judge the output solely by an unloaded voltage reading.

If the PC cannot connect, check the cable driver, COM number, mini-DIN connection and communication settings before condemning the CPU. Close any other application holding the same serial port.

Test inputs individually with a controlled setup and verify the sensor common and S/S wiring. On used equipment, inspect relay wear, damaged terminals, corrosion and loose expansion connectors.

Locate the fault by measurement before replacing parts. With power disconnected, investigate the supply section, affected input optocoupler or output driver as appropriate. Exclude the field load and wiring before diagnosing a CPU failure. Complete the check with program readback, loaded I/O tests and a power-cycle test.

Manuals and related topics

Use Delta DVP PLC files as the document hub for installation, programming and cable references. Match each document to the exact model, output type and hardware revision. Do not assign specifications from a neighbouring model to a variant absent from an older manual.

Navigation: Delta Automation · Delta PLC · Delta DVP PLC series · DVP-SS2 main page · DVP files

External references

Delta DVP-SS2 instruction sheet, 2024 · Delta DVP/TP catalogue, English, 2024 · Delta PLC/HMI Cable Selection Guide, English