Delta DVP12SS211S

Delta DVP12SS211S PLC – 8 Digital Inputs and 4 PNP Transistor Outputs

The Delta DVP12SS211S is a 24 V DC PLC CPU in the Delta DVP-SS2 family with 8 digital inputs and 4 PNP transistor outputs. Its 8K-step program memory and 25.2 mm width suit small panels for sensor, valve and conveyor control. This model can also generate a voltage reference through its Y0-based PWM D/A circuit.

Inputs, PNP outputs and high-speed pulses

X0–X7 accept 24 V DC signals. Wire the S/S common to suit the sensor output type. The Y0–Y3 PNP outputs source current to the load when active. Connect an external 24 V DC output supply to UP and ZP. Use the PNP and NPN sensor guide for the input side and Delta’s PNP circuit diagram for the load side.

Delta specifies maximum input frequencies of 20 kHz for X0–X3 and 10 kHz for X4–X7, and a 10 kHz output limit for Y0–Y3. For encoder counting and positioning, check which input and output pairs the instruction uses. See PLC high-speed counters and high-speed pulse outputs for more on how those functions work.

0–10 V PWM D/A output on Y0

The PWM-based D/A output has a nominal range of 0–10 V DC. Delta specifies a 1–9 V linear region with 0.1 V resolution and a D/A conversion time of less than 70 ms. The output may fall short of the setpoint in the 0–1 V and 9–10 V regions. When driving a 0–10 V reference input, check the input impedance and the operating range you need.

The D/A function uses Y0 and supplies the voltage reference at the DA terminal. Assign Y0 to that function when the project requires an analog reference. Delta’s example selects the PWM time base with M1116, sets a 100 μs period and 50% duty cycle, then adjusts VR in the circuit to obtain V0 = 5 V. Calibrate using the circuit in the instruction sheet with the intended load connected.

Programming software, cable and communications

Use WPLSoft or ISPSoft for the DVP-SS2 project. To read or download the program from a PC, connect the UC-PRG020-12A USB-to-RS-232 cable to the CPU’s 8-pin mini-DIN COM1 RS-232 port. After installing the driver, select the Windows COM port in WPLSoft or in COMMGR for ISPSoft. See Delta DVP programming cables for other connection options.

COM2 RS-485 can exchange Modbus serial data with an HMI or drive. The IFD6500 USB-to-RS-485 converter can connect a PC to the bus for bench checks. To add I/O, fit compatible modules to the CPU’s right-side DVP expansion bus. The DVP08SM11N is one option for adding digital inputs.

Editor’s Note

On a used CPU, verify the DVP12SS211S label. Inspect the front terminals, COM1 socket and right-side expansion connector.

If the output LED lights and the load remains inactive, measure the UP/ZP supply and check the load return. Test the PNP output with a suitable 24 V DC load.

When using an analog reference, check both the PWM on Y0 and the DC voltage at V0. After adjusting for 5 V at 50% duty cycle, verify a second point within the operating range.

Back up the source project, RS-485 station address and communications settings before swapping CPUs. Verify the inputs and communications first, then activate output loads one at a time.

If the project uses Y0 for both positioning and an analog reference, check how its outputs are allocated. Use a separate module such as the DVP02DA-S analog output module for the reference if required.

Related models and files

The DVP14SS211R has 8 inputs and 6 relay outputs. The DVP14SS211T has 8 inputs and 6 NPN outputs. Of the 16-input, 12-output models, the DVP28SS211R has relay outputs, the DVP28SS211T has NPN outputs and the DVP28SS211S has PNP outputs. When replacing a CPU, compare the output types, terminal layouts and how the project uses Y0.