Delta DVP14SS211T
Delta DVP14SS211T – SS2 PLC with 8 Inputs and 6 NPN Outputs
Delta DVP14SS211T is a DVP-SS2 main processing unit with 8 digital inputs and 6 NPN transistor outputs. This 8K-step PLC handles sequencing, counting, timing and pulse commands in small machines. It executes its own application and is not an extension module.
Inputs are X0–X7; outputs are Y0–Y5. There are no built-in analog inputs or Ethernet port. Compatible DVP-S extensions add digital, analog and temperature functions. Check CPU compatibility, power requirements and expansion limits for the actual assembly.
24 V DC supply and input wiring
Supply: 24 V DC, operating range 20.4–28.8 V DC. DVP14SS211T CPU consumption is 1.5 W, excluding external loads. Size the power supply for the complete installation. The unit mounts on a 35 mm DIN rail inside a cabinet; body width is 25.2 mm.
The 24 V DC inputs support sink/source wiring through the S/S common. For PNP sensors, connect S/S to 0 V; for NPN sensors, connect S/S to +24 V. Sensor output type and CPU output type are separate matters: an NPN-output CPU does not restrict its inputs to NPN sensors.
For an inductive sensor, photoelectric sensor or limit switch, check voltage, common wiring and response time. The standard X0–X7 input filter is adjustable from 0–20 ms through D1020, with a 10 ms default. Check high-speed counter configuration separately in the relevant manual section.
Fast inputs and pulse outputs
X0–X3 are in the 20 kHz input class; X4–X7 are in the 10 kHz class. When connecting an encoder, account for single-phase/two-phase counting and A/B evaluation. A terminal frequency rating does not establish the same maximum encoder speed in every counting mode.
Y0–Y3 support four independent pulse outputs up to 10 kHz. Y4 and Y5 have a tabulated 1 kHz limit; their actual switching performance also depends on program scan time. Do not transfer the SV/SV2 family's 200 kHz specifications to this SS2 CPU.
For a servo drive or other pulse-commanded motion system, verify NPN open-collector compatibility, input voltage and pulse/direction arrangement. Calculate the pulse frequency required by the mechanical speed in your automation project; reconsider CPU selection if it exceeds 10 kHz.
NPN outputs and UP/ZP auxiliary supply
Outputs are NPN open collector. Connect the auxiliary supply +24 V DC to UP and 0 V to ZP; the load connects between +DC and the corresponding Y output. A running CPU does not prove that the output circuit is powered. Do not apply the relay model's C0/C1 arrangement to this model.
The output table specifies 5–30 V DC load voltage, 0.5 A/point and 3 A/common resistive-load limits. UP/ZP require a 24 V DC auxiliary supply. Assess load current, inrush and switching frequency together.
Do not connect an AC load directly to a transistor output. Use a suitable interposing relay when required and check contactor coil ratings. DC inductive loads require appropriate diode/suppression circuitry, suitable fusing and proper grounding.
Programming software, cable and driver
WPLSoft or ISPSoft can be used. WPLSoft supports DVP Ladder projects; select the supported DVP-SS2 target in ISPSoft. Check CPU support in the software release you use and distinguish the original SS target from SS2.
COM1 RS-232 uses an 8-pin mini-DIN connector. A USB computer can connect through the UC-PRG020-12A USB-to-RS-232 programming cable. For a physical RS-232 port, use a correctly wired cable such as UC-MS020-01A; this can also work with a suitable USB-to-RS-232 converter. This model has no native USB programming socket.
Install the cable's appropriate Windows driver and check its assigned COM number. For ISPSoft, create a serial driver in COMMGR; match COM number, serial format and station address. Back up the project and important machine data before programming.
Communication and retained memory
The CPU provides RS-232 and RS-485. RS-232 can serve the engineering connection and RS-485 the field network. Match Modbus ASCII/RTU, station and serial settings to the application. Assess cable, topology and termination resistance for the RS-485 network.
The SS2 series requires no battery; programs and latched data are stored in flash memory. This does not make every temporary register retentive. Test that recipes and counters requiring power-loss retention use the correct retained areas.
Related models
DVP14SS211R: 8 inputs and 6 relay outputs. Its load-switching arrangement differs and cannot provide the transistor model's fast pulse function.
DVP28SS211T: 16 inputs and 12 NPN transistor outputs, for SS2 applications requiring more onboard digital points.
DVP28SS211R: 16 inputs and 12 relay outputs. Select according to load type and switching frequency.
DVP12SS211S: 8 inputs and 4 PNP transistor outputs. Output count and polarity differ; it is not a replacement using unchanged field wiring.
Editor's Note
Check SS2 and the T suffix on the label first. Original SS and SS2 output terminal layouts differ; compare terminal names instead of transferring wires by position.
If the output LED illuminates but the load does not operate, measure UP/ZP first. Supplying the CPU with 24 V is not sufficient by itself. Check voltage drop under load too.
On a used unit, test all eight inputs and six outputs individually. Check pulse outputs Y0–Y3 with a suitable receiver or oscilloscope; LEDs do not establish high-speed output health.
Check the program and retained-area configuration rather than looking for a battery. After backing up, perform a controlled power-loss test and prevent unexpected movement when power returns.
Inspect for a short circuit and loose terminals with power isolated. Do not rely solely on standard PLC logic for emergency stopping; design the required safety relay and independent stopping arrangement for the machine.
For a used-unit sale, state quantity, label photographs, working/faulty condition and test results. Sales require an invoice; no returns; workshop testing is available. Sellers can send details to otomasyonavm@gmail.com.
PDF documents and related topics
For wiring and technical tables, visit our Delta DVP PLC files page first. Use the DVP14SS211T row in the shared SS2 sheet. Its PWM–DA section applies specifically to DVP12SS211S and does not establish an analog output on this model.
Related topics and navigation: Delta and used models | Delta PLC | DVP PLC series | DVP-SS2 | DVP14SS211T model page
External references
Delta DVP-SS2 instruction sheet – 21 February 2024, DVP-0160030-02
Delta PLC/HMI Cable Selection Guide – SS2, section 1.4
Delta ES2/EX2/SS2/SA2/SX2/SE and TP programming manual